Verify worst-case DC current at low-voltage cutoff, startup surge duration, BMS peak limits, fuse DC voltage and interrupt rating (AIC).

Interactive calculator

Inverter and load
Battery, BMS and cable
Candidate fuse and minimum-melt curve

Use the selected fuse’s DC datasheet (Class T, MRBF or ANL, for example). Enter AIC with its stated DC test voltage and a minimum-melt point at or above the calculated surge current. Initial values describe an example.

Engineering reference

The low-voltage cutoff and conversion efficiency determine worst-case input current. BMS and inverter peak ratings cover surge duration; fuse voltage and AIC cover maximum charge voltage and prospective fault current.

I_DC = P_AC / (V_min × η)
AC powerCutoff voltageDC current (88%)
1000 W10.5 V108.23 A
1000 W21 V54.11 A
1000 W42 V27.06 A