Calculation and review methodology

Shared equations, primary engineering sources, worked validation cases and review boundaries for DC Power Specs.

Scope and equipment-specific limits

Every calculator on DC Power Specs operates inside one electrical boundary: 12 V, 24 V and 48 V nominal battery systems strictly ≤ 60 V DC across all charge stages, and off-grid PV arrays strictly ≤ 150 V DC cold open-circuit voltage. Every numerical output is labeled as either a deterministic formula result from user inputs, a cited primary-source reference value, or a site planning default (new-bank sizing uses fixed 85% LiFePO₄ / 50% AGM usable DoD baselines, while existing-battery runtime mode lets you edit usable capacity percentage directly).

Primary engineering sources

Wire resistance, voltage drop and ampacity

rho(T) = 0.01724 * (1 + 0.00393 * (T_C - 20))   [ohm·mm²/m]
L_roundtrip = 2 * L_one_way
A_min = (L_roundtrip * I * rho(T)) / (V_nom * drop_fraction)
I_design = I * 1.25   (continuous load >= 3 h)
Ampacity = Base_ABYC_VI_A(min(T_insul, T_term)) * derating_factor

Conductor area is chosen as the smallest standard AWG and metric mm² size meeting both A_min and derated ampacity >= I_design. Entering DC input power (W) divides by nominal battery voltage (12.0/12.8 V, 24.0/25.6 V, 48.0/51.2 V); AC inverter feeds should first be converted to worst-case DC amperes at minimum cutoff voltage and inverter efficiency.

Battery energy, runtime and inverter losses

Daily_Wh (bank/runtime) = sum(AC_Wh / eta_AC) + sum(DC_Wh / eta_DC) + sum(Native_DC_Wh) + (Idle_W * Idle_h_no_AC)
Daily_Wh (portable)     = sum(AC_Wh / eta_AC) + sum((DC_Wh + Native_DC_Wh) / eta_DC) + (Idle_W * Idle_h_no_AC)
Bank_Wh                 = (Daily_Wh * Days * K_temp) / Usable_DoD   [Usable_DoD = 0.85 LiFePO4, 0.50 AGM]
Runtime_days            = ((Existing_Ah * V_nom * (Usable_pct / 100)) / K_temp) / Daily_Wh
Portable_cont_h         = Station_Wh / (AC_W / eta_AC + (DC_W + Native_DC_W) / eta_DC)   [rated reference conditions]

In battery-bank and existing-runtime modes, native DC loads connect directly to the battery bus without DC conversion loss, and Usable_pct is entered as a percentage (1–100%, e.g., 72 -> 0.72). In portable power station mode, all DC outputs pass through the internal regulator (eta_DC), idle hours count only inverter-on periods without an active AC load, and runtime reflects rated reference conditions without cold-temperature capacity loss (temperature inputs govern cold-charging guidance only).

Solar cold Voc, hot Vmp and parallel backfeed protection

Voc_cold       = N_series * Voc * (1 + |beta_Voc| / 100 * (25 - T_cold_C))
Vmp_hot        = N_series * Vmp * (1 + beta_Vmp / 100 * (T_hot_C - 25))
Isc_array      = N_parallel * Isc   <= MPPT_Isc_max   (controller input check)
I_backfeed_STC = (N_parallel - 1) * Isc
I_backfeed_des = (N_parallel - 1) * 1.25 * Isc   vs. Module Max Series Fuse
String fuse window: 1.5625 * Isc <= I_fuse <= Module Max Series Fuse

Controller PV short-circuit current (N × Isc) is kept separate from string fuse sizing (1.5625 × Isc floor). Whenever 3 or more parallel strings are entered, the calculator never issues an unconditional fuse-free pass: if design backfeed exceeds the module limit it flags required protection (and flags infeasible inputs when 1.5625 × Isc > max series fuse), otherwise it prompts verification against the module manual and conductor ampacity.

Inverter DC current, BMS surge and fuse AIC

I_dc_max   = P_ac_continuous / (V_min * eta_inverter)
I_dc_surge = P_ac_surge / (V_min * eta_inverter)
Fuse rules: 1.25 * I_dc_max <= I_fuse <= I_cable_derated; V_fuse >= V_charge_max; AIC(at V_charge_max) >= I_fault

Worked validation boundary cases

  • Wire temperature transition: 10 A, 15 ft one-way (30 ft round-trip), 3% drop, 12.0 V AGM → 10 AWG at 20 °C (2.50% drop) steps up to 8 AWG at 75 °C (1.91% drop); at 12.8 V LiFePO₄ both temperatures stay on 10 AWG (2.34% / 2.85%); metric stays 6 mm² across all four cases.
  • PV 3-string backfeed boundary: 3 parallel strings × 9 A Isc with 20 A module max series fuse → STC reverse = 18 A, design backfeed (1.25×) = 22.5 A > 20 A → per-string gPV fuse required (1.5625 × 9 A = 14.06 A floor ≤ 20 A ceiling). At 2P × 9 A with a 10 A limit → 11.25 A > 10 A and 14.06 A > 10 A → flagged as no valid fuse window.
  • Existing 100 Ah two-night fridge runtime: 12.8 V 100 Ah LiFePO₄ at 72% net usable (72 Ah / 921.6 Wh), 51.2 W (4 A) fridge 24 h + 12.8 W fan 8 h + 6.4 W lights 4 h → at 25% duty (34 Ah/day) lasts 2.12 days (50.8 h); at 40% duty (48.4 Ah/day) drops to 1.49 days (35.7 h).
  • 48 V LiFePO₄ fuse voltage & AIC boundary: 58.4 V absorption voltage vs. 58 V / 2,000 A MRBF terminal fuse on a 3,000 A prospective fault → rejected on both DC voltage rating (58.4 V > 58 V) and AIC (3,000 A > 2,000 A).