DC Wire Size & Voltage Drop Calculator

Size 12V, 24V and 48V copper wire in AWG and mm² from round-trip voltage drop, 75 °C resistance and Blue Sea VI-A derated ampacity.

Interactive calculator

Circuit and voltage drop

Selecting DC input power (W) divides watts by nominal battery voltage. For AC inverter loads, calculate worst-case DC current at minimum battery voltage and inverter efficiency first, then enter amperes (A).

Conductor and terminals

Engineering reference

Blue Sea / ABYC VI-A uses single copper conductors in free air at 30 °C. The lowest insulation or terminal rating and combined ambient/bundle derating determine the cable current ceiling.

ΔV = 2 × L × I × ρ / A; ρ(75 °C) = 0.0209664 Ω·mm²/m

Blue Sea VI-A reference

CurrentOne-way lengthCopper areaVoltage drop
104 m4 mm²0.419 V
104 m6 mm²0.280 V
204 m10 mm²0.335 V