Battery Runtime Calculator (12V, 24V & 48V)

Calculate how long an existing LiFePO₄ or AGM battery bank runs DC and AC loads with usable capacity, inverter losses and K_temp to −10 °C.

Interactive calculator

Loads

Presets supply example device inputs. Daily energy combines running power, scheduled time, duty cycle and conversion efficiency.

Energy and operating conditions

Enter idle hours only for periods when the inverter stays switched on with no AC load. Active AC loads already include inverter conversion efficiency.

Existing battery bank

Enter the net usable percentage directly (for example, 85% default for LiFePO₄, 50% for AGM, or 72% if you combine 90% usable capacity with a 20% trip reserve) so reserve is never deducted twice.

Engineering reference

Usable energy equals nominal capacity times the entered net usable fraction, divided by K_temp. Daily load energy includes active conversion losses and independent idle consumption.

t_d = V_nom × Ah × DoD / (K_temp × Wh/day)
12.8 V LiFePO₄ at 25 °C85% usable256 Wh/day
50 Ah544 Wh2.125 d
100 Ah1088 Wh4.25 d
200 Ah2176 Wh8.5 d