Cold Voc stays below the controller limit and at or below 150 V DC. Above 60 V DC, touch protection and a DC-rated PV disconnect are required. Startup and running margins come from the controller datasheet.
Voc_cold = N_s × Voc × (1 + |βVoc| × (25 − T)); I_backfeed = (N_p − 1) × 1.25 × Isc | Parallel strings | Isc per string | Design backfeed |
|---|---|---|
| 1 | 10 A | 0 A |
| 2 | 10 A | 12.5 A |
| 3 | 10 A | 25 A |