Solar Array & MPPT Charge Controller Calculator

Check cold PV Voc up to 150 V DC, hot Vmp startup headroom, controller Isc limits and 1.25× parallel-string backfeed fuse sizing.

Interactive calculator

Modules and array

Backfeed protection compares (N − 1) × 1.25 × Isc against the module maximum series fuse rating. Controller PV Isc is checked separately against N × Isc. Follow the module manual where per-string fusing is required.

Battery and MPPT ratings

Enter the startup and running voltage margins from the controller manual. The initial +5 V and +1 V are example settings.

Daily energy

Engineering reference

Cold Voc stays below the controller limit and at or below 150 V DC. Above 60 V DC, touch protection and a DC-rated PV disconnect are required. Startup and running margins come from the controller datasheet.

Voc_cold = N_s × Voc × (1 + |βVoc| × (25 − T)); I_backfeed = (N_p − 1) × 1.25 × Isc
Parallel stringsIsc per stringDesign backfeed
110 A0 A
210 A12.5 A
310 A25 A