On this page

For DC-side inverter sizing, surge margins, and standby tare losses, see Inverters.


Regional Mobile AC Conventions and Interface Ratings

Mobile AC interfaces must match the voltage, frequency, shore inlet current rating, and protective device conventions of the region where the vehicle or boat operates. Verify exact input/output ratings on the equipment nameplate rather than assuming universal shore pedestal limits.

Parameter North America (RV & Marine) United Kingdom (Campsite Hookup & Narrowboat) Australia (Caravan Park Supply)
Nominal Voltage / Frequency 120V AC / 60Hz (some 50A RVs use 120/240V split-phase) 230V AC / 50Hz 230V AC / 50Hz
Common Shore Inlet Ratings 15A, 30A (120V), 50A (120/240V) 16A, 32A 15A (standard caravan inlet; 10A domestic leads are undersized for 15A loads)
Conductors & Naming Hot (L), Neutral (N), Equipment Ground (G) Line (L), Neutral (N), Protective Earth (E / PE) Active (A), Neutral (N), Protective Earth (E)
Bonding Convention Single N-G bond at active source Single N-E bond at active source Single N-E bond at active source
Ground-Fault Protection GFCI (4–6 mA Class A trip threshold) RCD (typically <=30 mA trip threshold, double-pole switching) RCD / RCBO (typically <=30 mA trip threshold, double-pole switching)
Polarity / Reversal Risk Possible on older pedestals; monitored by surge/EMS units Common on older campsite/marina posts; requires double-pole switching Possible on adapted leads; requires double-pole switching

Source Transfer, Pass-Through, and Neutral-to-Ground Bonding

An inverter-charger uses an internal break-before-make transfer relay (ATS) to switch AC loads between shore power (pass-through state) and the inverter stage (inverting state). The two sources must never be connected in parallel unless the unit is explicitly rated for grid-interactive synchronization.

Single-Point Bond Rule by Source State

An AC distribution system requires exactly one N-G (North America) or N-E (UK/Australia) bond at any given time, located at the active power source:

  1. Pass-Through State (Shore Power Present): The shore pedestal transformer provides the N-G or N-E bond upstream. The inverter's internal bonding relay must open so the vehicle chassis or boat hull does not create a second parallel neutral return path.
  2. Inverting State (Shore Power Absent): The inverter is the AC source. Its internal bonding relay must close (or use a fixed bonded output on inverter-only systems) to tie Neutral to Ground/Earth. Without this bond, downstream GFCI or RCD devices cannot detect a ground fault until a second fault occurs, and ground-referenced appliances may report open-ground faults.
[Shore Pedestal] --(N-G/N-E Bonded Upstream)--> [ATS Relay] ---> [AC Loads]
                                                     ^
   Pass-Through State: ATS = Shore; Internal N-G/N-E Relay = OPEN
   Inverting State:    ATS = Inverter; Internal N-G/N-E Relay = CLOSED

[Battery <=60V DC] ---> [Inverter] --(Internal N-G/N-E Relay)--+
                                                               |
                                                      [Chassis / Hull Ground]

Floating-Output Portable Inverters

Small portable inverters often have a floating (unbonded) AC output where neither AC output leg is referenced to the DC chassis ground (sometimes measured as ~60V AC from each leg to ground on a 120V output, or ~115V AC on a 230V output). A floating output is safe only for isolated single-appliance cord use; it cannot properly operate a standard downstream GFCI/RCD distribution panel unless an intentional N-G/N-E bond is established at the inverter output per the manufacturer's interface specification.


GFCI and RCD Protection Principles

Ground-fault devices protect against shock by measuring the differential current between the ungrounded conductor and the neutral conductor:

I_diff = |I_hot - I_neutral|   (North America 120V)
I_diff = |I_line - I_neutral|  (UK 230V / Australia 230V)

Under normal operation, all current leaving on Hot/Line returns on Neutral, so I_diff is near zero. If current leaks to a grounded chassis, hull, or person, I_diff rises and trips the device:

  • North America (GFCI): Trips at 4–6 mA within milliseconds. Modified-sine-wave inverters and unbonded outputs frequently fail to trip a GFCI test button or cause nuisance tripping due to high-frequency harmonics and capacitive leakage.
  • UK Campsite Hookups and Australian Caravan Parks (Double-Pole RCD): Trips at <=30 mA and opens both Line/Active and Neutral simultaneously. Double-pole interruption is critical in mobile 230V/50Hz environments because a reversed-polarity shore post swaps Line and Neutral; a single-pole breaker would leave the "neutral" conductor energized at 230V relative to Earth even after tripping.

Marine Shore-Supply Galvanic Isolation (Boats and Narrowboats)

Connecting a boat's shore protective earth (PE) directly to the onboard DC negative and underwater metal (propeller, shaft, thru-hulls, or a submerged steel narrowboat hull) creates a galvanic cell through the water with neighboring boats and steel marina pilings. Dissimilar metals in water generate small DC voltages (typically 0.2V to 1.2V DC) that drive continuous corrosion current through the shore earth wire, rapidly consuming sacrificial anodes and pitting hulls or stern gear.

Two interface concepts break this DC galvanic path while preserving AC fault safety:

Concept How It Works Strengths Limitations
Galvanic Isolator Two pairs of opposing semiconductor diodes in series on the shore earth conductor; blocks low-voltage DC (< ~1.2V–1.4V) while conducting AC fault current if a line-to-hull fault occurs. Compact, low heat, minimal weight; mounts inline on the shore earth path. Does not isolate against stray AC voltage gradients in the water or higher-voltage DC shore faults (>1.4V); must match or exceed shore inlet ampacity.
Isolation Transformer Magnetic coupling between primary (shore) and secondary (onboard) windings; no direct conductive path between shore earth/neutral and the boat's hull or AC ground. Eliminates galvanic DC currents, blocks stray shore-earth voltages, and establishes a clean onboard N-E/N-G reference immune to shore polarity reversal. Heavy, bulky, and generates magnetizing standby losses and heat; requires correct primary/secondary voltage matching (e.g., 120V/60Hz or 230V/50Hz).

UK Narrowboat Shore Power Specifics: Steel narrowboats sitting in conductive fresh or brackish canal water are highly susceptible to hull pitting if shore PE is bonded directly to the steel hull without a galvanic isolator or isolation transformer. Because UK canal-side hookups can also exhibit reversed polarity or elevated earth potential, an isolation transformer or a properly rated galvanic isolator paired with a double-pole 30 mA RCD and polarity indicator is standard practice.


Job-Specific Verification Steps (Nameplate and DC-Side Supply)

Keep practical installation steps within the <=60V DC bus and equipment nameplate boundary; treat the AC side strictly by input/output interface ratings.

  1. Read the Equipment Nameplate: Record the AC output rating (V, Hz, continuous W/VA, surge W/VA), the pass-through transfer relay rating (A), and the DC input limits (12V/24V/48V nominal, low-voltage cutoff V_min, and maximum charging voltage).
  2. Calculate Worst-Case DC Input Current: Size the DC supply at V_min and full continuous load, not at nominal battery voltage:
    I_dc_max = P_ac_continuous / (V_min * efficiency)
    
    Illustrative example (assumed values): A 2,000 W continuous inverter on a 24V LiFePO4 bank (25.6V nominal, V_min = 21.0 V, assumed efficiency 0.88):
    I_dc_max = 2000 / (21.0 * 0.88) = 108.2 A
    
  3. Size DC Conductors and Overcurrent Protection:
    • Apply a >=1.25x continuous-duty factor (108.2 A * 1.25 = 135.3 A for the illustrative 2,000 W example) when selecting ampacity and fuse rating.
    • Calculate voltage drop using round-trip length (2 * one-way distance) and 75°C copper resistivity (0.02097 ohm·mm²/m), keeping inverter DC feed drop <=3% so V_min is not triggered prematurely under surge.
    • Verify fuse maximum voltage rating >= maximum charging voltage (for example, a 48V LiFePO4 absorb voltage of 58.4V exceeds a 58V-rated terminal fuse).
    • Verify fuse AIC >= prospective battery fault current and fuse rating <= cable derated ampacity, honoring terminal temperature limits (often 75°C / 167°F).
  4. Match Shore Pass-Through and Cold-Charging Limits:
    • Verify the inverter-charger's ATS pass-through rating is >= the shore inlet rating (e.g., 30A for NA 120V, 16A for UK 230V, 15A for AU 230V) or configure input current limiting on the charger interface.
    • Flag battery charging at <= +5°C (41°F) to verify the BMS minimum charge temperature (some commercial packs lock out at +5°C), and hard-block shore/inverter charging at <= 0°C (32°F) unless the battery is self-heated.
  5. Verify Source-State Bonding and Isolation Ratings: Confirm from the manual whether the inverter switches N-G/N-E dynamically on transfer, and confirm any marine galvanic isolator or isolation transformer matches or exceeds the shore inlet current rating.

Sign-Off Criteria

  • Nameplate & Regional Match: Inverter AC output voltage/frequency matches regional loads (120V/60Hz NA or 230V/50Hz UK/AU), and ATS pass-through rating matches or is current-limited to the shore inlet.
  • Single-Point Bond Verified: Only one N-G or N-E bond exists in pass-through state (at the shore pedestal) and one bond exists in inverting state (at the inverter).
  • Ground-Fault Function: Downstream GFCI (4–6 mA, NA) or double-pole RCD (<=30 mA, UK/AU) trips on test in both shore pass-through and inverting states.
  • Marine Isolation Integrity: On boats and narrowboats, no direct low-voltage DC continuity bypasses the galvanic isolator or isolation transformer between shore PE and the underwater hull/DC negative.
  • DC Supply Margins: DC cables meet both <=3% round-trip voltage drop and >=1.25x continuous ampacity at V_min; DC fuse voltage rating exceeds peak absorb voltage (14.6V / 29.2V / 58.4V for LiFePO4) and sits within cable ampacity and battery BMS peak surge duration.

Failure Modes

  • Dual N-G / N-E Bond in Pass-Through: Leaving a fixed inverter bond active while connected to shore power splits neutral return current onto the chassis or hull and immediately trips upstream pedestal GFCI/RCD breakers.
  • Floating Neutral on Distribution Panels: Feeding a chassis-grounded AC panel from an unbonded inverter prevents downstream GFCI/RCD devices from seeing ground-fault differential current, leaving a first fault undetected.
  • Reversed-Polarity Shore Pedestal (UK/AU): Swapping Line and Neutral at a campsite or marina post energizes the neutral bus; single-pole breakers fail to isolate the fault, requiring double-pole RCD and breaker protection.
  • Unisolated Marine Shore Earth: Tying shore PE directly to a boat's DC negative or steel narrowboat hull without a galvanic isolator or isolation transformer accelerates sacrificial anode depletion and underwater metal pitting.
  • DC Feed Under-Sizing or Fuse Voltage Mismatch: Undersized DC cables drop battery terminal voltage below V_min during motor or compressor startup surges, causing inverter low-voltage shutdown; using a 58V-rated fuse on a 58.4V 48V LiFePO4 absorb profile violates fuse voltage rating.