This conceptual specification governs how mobile inverter-chargers and 12V, 24V, or 48V DC battery systems (<=60V DC bus) interface with Australian 230V/50Hz shore power. Practical wiring procedures below remain strictly on the <=60V DC side; 230V AC mains installation is outside this document's scope. For broader AC interface architecture, see AC-Side Inverter Concepts.

Supply Ratings and Interface Conditions

The governing interface choice depends on the shore pedestal rating, the inverter-charger's AC input current limit, and whether the system is in shore-connected pass-through or islanded inverter mode.

Parameter 15A Caravan Park Pedestal 10A Domestic / Temporary Supply Islanded Inverter Mode (Off-Grid)
Nominal AC Voltage / Frequency 230V AC / 50 Hz 230V AC / 50 Hz 230V AC / 50 Hz (inverter output)
Plug / Inlet Geometry Wide earth pin (15A AS/NZS 3112) Standard earth pin (10A AS/NZS 3112) Internal AC output bus
Continuous AC Current Limit 15 A 10 A Limited by inverter continuous W and DC bus
Maximum Apparent / Real Power (PF = 1.0) 3,450 W 2,300 W Inverter nameplate continuous rating
Supply Neutral-Earth (N-E) State MEN-bonded at park supply MEN-bonded at premises switchboard Isolated from shore; inverter N-E relay closed
Vehicle Inverter N-E Bond State Open (separated) Open (separated) Closed (bonded at inverter output)
Required AC Protection Concepts 30 mA RCD + double-pole switching 30 mA RCD + inline 10A MCB limit + double-pole 30 mA RCD + double-pole switching

Conditions That Change the Interface Configuration

  • 15A Inlet on a 10A Supply: A 15A caravan inlet plug cannot physically mate with a 10A domestic socket. Connecting to a 10A supply requires a compliant inline 10A-protected (10A MCB + 30 mA RCD) adapter lead and setting the inverter-charger's AC input current limit to <=10 A (or <=8 A where thermal derating or long extension leads cause voltage sag).
  • Pass-Through vs. Battery Charging Share: On a 15A (3,450 W) or 10A (2,300 W) supply, AC pass-through loads and the inverter-charger's AC-to-DC battery charger share the same input budget. If AC loads draw 2,000 W on a 10A supply, only 300 W remains for battery charging before the 10A breaker trips unless the inverter-charger supports dynamic input current limiting or PowerAssist.
  • MEN Neutral-Earth Separation: In an Australian MEN system, Neutral and Earth are bonded at the upstream supply. If a mobile inverter-charger keeps its internal N-E bond closed while connected to shore power, it creates a parallel neutral return path through the protective earth conductor, bypassing or false-tripping the 30 mA RCD.

Conceptual AC Protection Architecture

Mobile 230V/50Hz AC interfaces rely on three coordinated mechanisms to ensure fault clearing in both shore-connected and islanded states:

  1. Double-Pole Switching and Isolation: Every AC circuit breaker, changeover switch, and main isolator in a mobile installation must break both Active (L) and Neutral (N) conductors simultaneously. Because portable leads or upstream supplies can experience polarity anomalies or open-neutral faults, single-pole switching leaves the Neutral conductor live relative to earth.
  2. Source-State Neutral-Earth (N-E) Transfer:
    • Shore-Connected: The transfer switch connects shore Active and Neutral to the vehicle AC bus, and the inverter's internal N-E relay remains open. Fault current returns via the park's MEN link to trip the 30 mA RCD.
    • Inverting (Islanded): The transfer switch opens both shore Active and Neutral (double-pole isolation), and the inverter's internal N-E relay closes to establish a single local N-E reference upstream of the vehicle's 30 mA RCD.
  3. 30 mA Residual Current Device (RCD): Placed downstream of the N-E bond point, the 30 mA RCD monitors current balance between Active and Neutral. Any earth leakage >=30 mA trips both poles. Verify on the inverter-charger nameplate and manual whether a Type A (or Type B, if required by specific transformerless topologies) RCD is specified.

DC-Side Coupling and Sizing Baseline

While the shore supply operates at 230V/50Hz, the inverter-charger's DC bus must stay strictly <=60V DC (12V, 24V, or 48V nominal). High-power 230V inverter-chargers—especially those sized to match a 15A (3,450 W) shore supply or supplement a 10A (2,300 W) supply—impose high DC currents during inversion, surge, and bulk charging.

DC-Side Electrical Formulas (Plain Text)

Worst-Case DC Inverter Current:
I_dc_max = P_ac_continuous / (V_min * efficiency)

DC Cable Round-Trip Voltage Drop (75°C copper, rho = 0.02097 ohm*mm2/m):
V_drop = (2 * L_one_way_m * I_dc_max * 0.02097) / A_mm2
Percent_Drop = (V_drop / V_nominal) * 100

Minimum Continuous Cable Ampacity (continuous >= 3 hours):
I_cable_min = I_dc_max * 1.25

Illustrative DC Bus Sizing for a 3,000 W / 230V Inverter-Charger

Illustrative assumptions: 3,000 W continuous AC output (matching a ~13 A / 230V load), 90% (0.90) inverter efficiency, 1.5 m (4.9 ft) one-way DC cable run (3.0 m / 9.8 ft round-trip), LiFePO4 battery chemistry (85% default usable DoD), <=3% critical voltage drop target, 75°C copper conductor terminals. Always verify exact V_min, V_max, and efficiency on the inverter and BMS nameplates.

Nominal DC Bus LiFePO4 Operating Window (V_min to V_max) Worst-Case I_dc_max at V_min Minimum 1.25x Continuous Ampacity Min Copper Area for <=3% Drop (3.0 m RT) Fuse Voltage Rating Requirement
12.8V (12V) 10.8V – 14.6V 308.6 A 385.8 A 50.6 mm² (1/0 AWG; check ampacity for 2x parallel runs or 70–95 mm²) >= 14.6V (e.g., 32V or 58V rated)
25.6V (24V) 21.6V – 29.2V 154.3 A 192.9 A 12.7 mm² (6 AWG for drop; size up to 70 mm² / 2/0 AWG for 193 A 75°C ampacity) >= 29.2V (e.g., 32V or 58V rated)
51.2V (48V) 43.2V – 58.4V 77.2 A 96.5 A 3.2 mm² (12 AWG for drop; size up to 35 mm² / 2 AWG for 96.5 A 75°C ampacity) >= 58.4V (must exceed 58V; use >=60V–80V rated fuse)

Note on 48V Fuse Voltage Ratings: A 51.2V LiFePO4 bank absorbing at 58.4V exceeds the 58V maximum rating of standard 58V-rated terminal fuses. Select a fuse and holder rated above the maximum charging voltage (e.g., 60V–80V DC) with an Interrupting Rating (AIC) exceeding the battery bank's prospective short-circuit current.

Cold Charging Note: When operating in alpine or winter caravan parks where battery cell temperatures drop to <=+5°C (41°F), verify the BMS minimum charge temperature threshold (some commercial packs lock out charging at +5°C). Hard-block AC-to-DC charging at <=0°C (32°F) unless the battery is equipped with an active self-heating system.

Job-Specific Verification and DC-Side Steps

  1. Confirm Nameplate Ratings: Record the inverter-charger's continuous AC output (W), surge rating (W and duration), AC-to-DC maximum charge current, low-voltage DC cutoff (V_min), efficiency, and internal N-E relay specification from the equipment nameplate and manual.
  2. Configure AC Input Current Limit: Program the inverter-charger AC input limit to match the shore source—15 A for a dedicated 15A caravan park pedestal, or 10 A (or lower) when using a compliant 10A inline RCD/MCB adapter lead.
  3. Verify DC Cable Sizing by Both Drop and Ampacity: Calculate I_dc_max at V_min. Compute required copper cross-section (mm² / AWG) for <=3% round-trip voltage drop at 75°C (0.02097 ohm·mm²/m), then verify the selected cable's 75°C derated ampacity meets or exceeds 1.25 * I_dc_max. Use the larger of the two cable sizes.
  4. Verify DC Overcurrent and Precharge: Confirm the main DC fuse ampacity is <= cable ampacity and >= 1.25 * I_dc_max, fuse max voltage >= battery V_max, and fuse AIC >= battery prospective fault current. If connecting a high-capacitance inverter to a LiFePO4 BMS, use a precharge circuit or resistor per the inverter manual to prevent BMS overcurrent trip on initial energization.
  5. Confirm N-E Transfer Logic: Verify from the inverter-charger configuration and manual that the internal N-E bonding relay is enabled for automatic open-on-shore / close-on-invert operation, and confirm that no fixed aftermarket N-E link exists downstream of the transfer switch.

Sign-Off Criteria

  • AC Input Limit: Inverter-charger AC input current limit matches the connected supply rating (<=15 A on 15A pedestal; <=10 A on 10A supply).
  • DC Voltage Drop: Measured or calculated round-trip DC voltage drop at I_dc_max is <=3% of nominal DC bus voltage.
  • Fuse Compliance: Main DC fuse voltage rating >= V_max (strictly >58.4V for 48V LiFePO4), fuse AIC >= prospective fault current, and fuse ampacity <= DC cable 75°C derated ampacity.
  • N-E State Separation: With shore power connected, N-E continuity is provided solely by the park MEN supply (inverter N-E relay open). With shore power disconnected and inverter active, the inverter N-E relay closes to reference the local 30 mA RCD.
  • RCD Functional Test: Pressing the 30 mA RCD test button trips both Active and Neutral poles in both shore-connected and islanded inverter modes.

Real Failure Modes

  • Nuisance 30 mA RCD Tripping on Shore Power: Occurs when an inverter's internal N-E bond remains closed (or a fixed N-E link is wired) while connected to an MEN-bonded caravan park pedestal, splitting neutral return current onto the earth conductor.
  • Blind RCD in Islanded Mode: Occurs when an inverter-charger's N-E relay is disabled or absent, leaving the AC output floating relative to chassis/earth. A single line-to-chassis fault will not trip a 30 mA RCD until a second fault occurs.
  • 10A Supply Breaker Trip or Overheated Lead: Occurs when a 15A-capable inverter-charger is connected to a 10A supply via an adapter without lowering the AC input current limit, causing combined pass-through loads and battery charging to exceed 2,300 W.
  • DC Low-Voltage Cutoff During AC Surge / PowerAssist: Undersized DC cables (sized only for average load or one-way length instead of round-trip I_dc_max at V_min) drop voltage below V_min during motor start surges, tripping the inverter off-line even when the battery state of charge is high.
  • 48V Terminal Fuse Failure: Using a standard 58V-rated fuse on a 51.2V LiFePO4 bank absorbing at 58.4V exceeds the fuse's DC voltage rating, risking sustained arcing if the fuse opens under fault.