Three conditions change how the bond is managed across AC-Side Concepts:
- Inverter architecture: Inverter-chargers with an automatic ground relay switch the bond dynamically by source state; basic standalone inverters either ship with a permanent internal N-G/N-E bond or a floating neutral.
- Upstream shore or generator bonding: North American 120V/60Hz shore pedestals and most 230V/50Hz UK/AU shore supplies provide the N-G/N-E bond at the source transformer or distribution pillar, whereas small portable generators may have a floating neutral.
- External transfer switch design: If an external automatic transfer switch (ATS) sits downstream of a standalone inverter and shore inlet, the inverter does not see shore power and cannot open its internal bond automatically unless neutral switching or relay control is coordinated.
Bonding Behavior by Source State
| Source State | Active AC Supply | Inverter Internal N-G / N-E Relay | Upstream Bond Location | Total Active Bonds | Resulting System Behavior |
|---|---|---|---|---|---|
| Standalone inverting (inverter-charger) | Inverter DC-to-AC stage (120V/60Hz or 230V/50Hz) | Closed (bonded) | None (shore disconnected) | 1 | Neutral references chassis/earth; GFCI/RCD trips on line-to-ground fault |
| Shore power pass-through (inverter-charger) | Shore pedestal (120V/60Hz or 230V/50Hz) | Open (unbonded) | Shore supply transformer / pillar | 1 | Shore bond governs; no parallel neutral current on ground conductor |
| Floating-neutral generator pass-through | Portable generator with floating neutral | Depends on model (must close if unbonded upstream) | None at generator | 0 if relay stays open; 1 if closed | If relay stays open on unbonded generator, system floats (0 bonds) |
| External ATS on shore (standalone bonded inverter) | Shore pedestal via ATS | Permanently closed (no relay) | Shore supply | 2 (if ATS does not isolate or inverter stays live) | Double bond splits neutral current onto ground; trips shore GFCI/RCD |
| Standalone floating-neutral inverter | Inverter DC-to-AC stage | None (permanently open) | None | 0 (unless externally bonded at receptacle/inlet) | Neutral floats at ~60V AC (120V) or ~115V AC (230V) to chassis; GFCI/RCD may not trip |
Regional AC Baselines and Inverter Interface Ratings
Mobile AC interfaces operate conceptually as isolated, single-source-referenced systems fed from a <=60V DC battery bank (12V, 24V, or 48V nominal). Check the inverter nameplate and installation manual for the following ratings before integrating the AC output:
- North America (120V / 60Hz): Uses Neutral-to-Ground (N-G) terminology. Standard mobile shore inlets are rated at 15A, 30A (120V), or 50A (120V/240V split-phase). Ground-fault protection relies on 4–6 mA Class A GFCI receptacles or breakers, which require an upstream N-G bond to sense imbalance when a hot conductor faults to chassis ground.
- UK / Australia / Europe (230V / 50Hz): Uses Neutral-to-Earth (N-E) terminology. Standard mobile shore inlets are typically 16A or 32A at 230V/50Hz. Residual Current Devices (RCDs, typically 30 mA trip threshold) and Residual Current Circuit Breakers with Overcurrent (RCBOs) require a single upstream N-E bond for reliable fault clearing.
- Inverter internal ground relay rating: Verify on the equipment datasheet whether the inverter-charger includes an automatic N-G/N-E switching relay and whether that relay is enabled by default or controlled via a DIP switch or software setting.
- DC-side chassis reference (<=60V DC): The inverter chassis and DC negative bus (12V/24V/48V nominal) share a common vehicle frame or vessel ground reference. Keep all practical conductor sizing and termination work on the in-scope DC side, and keep mobile AC interface checks to plug-in ratings, state behavior, and continuity verification.
Plain-text fault-current relationship when a single bond is present:
V_line / (Z_line + Z_ground + Z_bond) = I_fault
When the bond is open (Z_bond = infinite), I_fault drops to capacitive leakage only, preventing reliable overcurrent or GFCI/RCD operation on a chassis fault.
Verification and DC-Side Interface Steps
- Check the inverter nameplate and manual for bond topology: Confirm whether the unit is an inverter-charger with an automatic N-G/N-E relay, a permanently bonded standalone inverter, or a floating-neutral inverter. Record the AC output voltage/frequency (120V/60Hz or 230V/50Hz) and rated continuous AC current.
- Verify the DC-side chassis bonding conductor: On the <=60V DC side (12V/24V/48V nominal), verify that the inverter's DC chassis ground lug is bonded to the vehicle chassis or vessel ground bus using copper cable sized per the inverter manual (typically at least 8 AWG / 10 mm² or matching the DC negative conductor requirement). Confirm clean, tight mechanical lugs rated for 75°C (167°F) or higher.
- Verify standalone inverter state (shore disconnected): With shore power unplugged and the inverter running in standalone mode, measure AC voltage at an output receptacle:
- North America 120V/60Hz: Hot-to-Neutral ~120V AC, Hot-to-Ground ~120V AC, Neutral-to-Ground <2V AC.
- UK/AU 230V/50Hz: Line-to-Neutral ~230V AC, Line-to-Earth ~230V AC, Neutral-to-Earth <2V AC.
- Verify shore pass-through state (inverter-charger connected to shore): With bonded shore power active and the inverter-charger in pass-through mode, confirm that the inverter's internal bond opens. Measure Neutral-to-Ground (or Neutral-to-Earth) voltage at the mobile distribution output (<2V AC due to the upstream shore bond) and confirm that no upstream shore GFCI/RCD trips under a 50–100% resistive load.
- Check external transfer switch coordination: If using an external ATS between a standalone inverter and shore power, verify that the ATS switches both Line (Hot) and Neutral poles together (break-before-make) and that the inverter's N-G/N-E bond is active only on the inverter side of the switch.
Sign-Off Criteria
- Single bond count: Exactly 1 active N-G or N-E bond exists in standalone inverting mode, shore pass-through mode, and generator pass-through mode.
- Neutral-to-ground voltage: Measured N-G (120V/60Hz) or N-E (230V/50Hz) voltage is <2V AC under normal load in every source state.
- Relay isolation in pass-through: With shore power disconnected and the inverter unpowered/isolated (or relay manually commanded open per manual), continuity between the inverter's internal neutral output and ground lug reads open (OL) when testing relay release.
- GFCI / RCD trip verification: Pressing the test button or applying a calibrated plug-in GFCI/RCD tester trips the downstream protective device in both standalone inverting and shore pass-through states.
- DC chassis continuity: Resistance between the inverter chassis ground lug and the main DC negative/chassis ground point is <0.1 ohm.
Failure Modes
- Zero bonds (floating neutral): Occurs when a floating-neutral inverter runs standalone or an inverter-charger passes through an unbonded portable generator while keeping its internal relay open. Neutral and Line float at approximately half of system voltage relative to chassis (~60V AC on 120V/60Hz; ~115V AC on 230V/50Hz). Downstream GFCI/RCD outlets may fail to trip on a line-to-chassis fault, and sensitive appliances (such as shore-sensing chargers or HVAC controls) often report an open-ground or reverse-polarity fault.
- Double bond (parallel neutral path): Occurs when an inverter-charger's internal N-G/N-E relay fails closed during shore pass-through, or when a permanently bonded standalone inverter is wired through an external ATS that does not isolate neutral. Normal return current splits between the neutral conductor and the protective ground/chassis conductor. This energizes the chassis with voltage drop proportional to load current, creates galvanic/stray-current corrosion in marine hulls, and causes immediate nuisance tripping of shore pedestal GFCIs (4–6 mA) or RCDs (30 mA).
- Uncoordinated transfer switch overlap: A single-pole ATS that switches only Line (Hot) while leaving Neutral tied together creates a permanent double bond whenever a bonded inverter and bonded shore supply are connected simultaneously.
- Mismatched UK/AU 230V/50Hz shore earth: Connecting a mobile system to a faulty or reversed-polarity 230V/50Hz shore outlet without double-pole isolation or RCD protection can place line potential on the neutral conductor; verify shore polarity before enabling pass-through.