On this page
I_dc_max = P_ac_continuous / (V_min * eta)
I_dc_design = I_dc_max * 1.25 (for continuous loads >= 3 hours)
Three operating conditions change this result:
- Terminal low-voltage cutoff (
V_min): As battery state of charge drops and internal resistance causes voltage sag under load, DC current rises to hold constant AC wattage. Calculating with nominal voltage (12.8V, 25.6V, or 51.2V for LiFePO4; 12.0V, 24.0V, or 48.0V for AGM) instead ofV_minunderestimates worst-case current. - Full-load conversion efficiency (
eta): Inverter efficiency varies with load and input voltage. Use the efficiency reported at continuous rated output and low input voltage, not the peak efficiency headline figure. - Continuous-duty duration: Loads operating for three hours or longer require the 1.25x continuous-duty multiplier on
I_dc_maxbefore selecting conductor ampacity and overcurrent protection.
For broader inverter selection, surge duration matching, and standby loss trade-offs, see the Inverter Sizing and Surge parent reference.
Specifications and System Baselines
Check the inverter nameplate, datasheet, and battery management system (BMS) manual for each input variable before calculating:
| Parameter | Symbol | Where to Verify | Engineering Condition |
|---|---|---|---|
| Continuous AC output power | P_ac_continuous |
Inverter nameplate / manual | Use continuous watts (W) at ambient operating temperature (e.g., 77°F / 25°C or derated at 104°F–122°F / 40°C–50°C), not surge W or VA alone. Applies equally to North America 120V/60Hz and UK/AU 230V/50Hz AC output models. |
| Minimum terminal operating voltage | V_min |
Inverter LVD setting & BMS cutoff | Use the inverter low-voltage disconnect (LVD) or minimum full-power terminal voltage, whichever is higher. DC bus and battery bank remain strictly <=60V DC. |
| Inverter conversion efficiency | eta |
Inverter datasheet efficiency curve | Expressed as a decimal (e.g., 0.88 for 88%). Use full-load efficiency at low DC voltage, not peak efficiency at mid-load. |
| Duty cycle multiplier | 1.25 |
Load runtime profile | Required when continuous inverter load runs >=3 hours; use 1.0 only for documented intermittent loads <3 hours. |
| Terminal temperature rating | 75°C (167°F) |
Inverter DC lug & fuse holder spec | Governs downstream conductor ampacity selection from I_dc_design (common 75°C / 167°F terminal limit). |
Illustrative 12V, 24V, and 48V Comparison
The table below shows how DC input current scales across nominal 12V, 24V, and 48V systems using illustrative assumptions: a 2,000 W continuous AC load (120V/60Hz North America or 230V/50Hz UK/AU), 0.88 (88%) full-load inverter efficiency, and representative low-voltage terminal cutoffs (V_min). Replace these illustrative values with your equipment's actual nameplate figures.
| Nominal System Voltage | Chemistry Nominal Baseline | Typical Absorb Ceiling | Illustrative V_min |
I_dc_max (at V_min, 88% eta) |
I_dc_design (1.25x for >=3h) |
|---|---|---|---|---|---|
| 12V DC | 12.8V LiFePO4 / 12.0V AGM | 14.2–14.6V (LiFePO4) | 10.5V DC | 216.5 A | 270.6 A |
| 24V DC | 25.6V LiFePO4 / 24.0V AGM | 28.4–29.2V (LiFePO4) | 21.0V DC | 108.2 A | 135.3 A |
| 48V DC | 51.2V LiFePO4 / 48.0V AGM | 56.8–58.4V (LiFePO4) | 42.0V DC | 54.1 A | 67.6 A |
Step-by-Step Calculation
Confirm continuous AC load (
P_ac_continuous): Sum the continuous AC loads (in watts) powered simultaneously, or use the inverter's continuous rated AC output if sizing cables and overcurrent protection for full inverter capacity. If a load or inverter rating is listed only in VA, divide VA by the load power factor (or use the datasheet's continuous W rating). Verify whether the inverter derates continuous W above 77°F (25°C).Determine minimum terminal voltage (
V_min): Read the inverter's low-voltage cutoff / low-voltage alarm threshold and the battery BMS low-voltage disconnect from their manuals. Account for round-trip DC cable voltage drop (kept <=3% for critical inverter feeders):V_min_terminal = V_battery_loaded - V_cable_dropUse the lowest steady operating voltage at which the inverter still delivers full continuous output before shutting down.
Select full-load efficiency (
eta): Locate the efficiency curve in the inverter manual atP_ac_continuousandV_min. If only a single "efficiency" value is published without a curve, check whether it is peak efficiency; if so, apply the manufacturer's full-load figure or derate accordingly rather than using peak efficiency.Compute worst-case continuous DC current (
I_dc_max): Divide continuous AC watts by the product ofV_minandeta. Illustrative 12V example (2,000 W, 10.5VV_min, 0.88eta):I_dc_max = 2000 / (10.5 * 0.88) = 2000 / 9.24 = 216.5 AApply the continuous-duty multiplier (
I_dc_design): If the inverter can run at that continuous load for three hours or more, multiplyI_dc_maxby1.25:I_dc_design = 216.5 A * 1.25 = 270.6 AUse
I_dc_designas the minimum required derated ampacity for DC feeder conductors (AWG / mm²) and the basis for fuse/breaker sizing.
Sign-Off Criteria
Before finalizing wire gauge and overcurrent protection from your calculated I_dc_design:
- Worst-case
V_minverified: Calculation usesV_minat the inverter DC terminals under load, not nominal battery voltage (12.8V/25.6V/51.2V or 12.0V/24.0V/48.0V) or resting open-circuit voltage. - Full-load efficiency used:
etareflects continuous full-load conversion efficiency at low DC voltage, not peak efficiency. - Continuous-duty rule applied:
1.25xmultiplier is included for any load profile >=3 hours. - Conductor and terminal limits matched: Selected AWG (mm²) cable ampacity—derated for ambient temperature (in °F / °C) and bundling—meets or exceeds
I_dc_designat the inverter's terminal temperature limit (typically 75°C / 167°F), and round-trip voltage drop (2 x one-way length in feet or meters) stays <=3%. - Overcurrent protection coordinated: Fuse or DC breaker rating satisfies
I_dc_design <= I_fuse <= I_cable_ampacity, fuse maximum voltage rating meets or exceeds maximum charging voltage (for example, a 58.4V LiFePO4 absorb voltage exceeds 58V-rated terminal fuses), and fuse interrupting rating (AIC) exceeds prospective fault current at operating voltage.
Failure Modes
- Sizing at nominal voltage instead of
V_min: Calculating a 2,000 W 12V inverter at 12.8V (or 12.0V) instead of 10.5V underestimates DC current by 18%–22%, causing nuisance fuse blows or breaker trips as the battery nears empty. - Using peak efficiency instead of full-load efficiency: High-frequency inverters often advertise 92%–94% peak efficiency at 25%–35% load, while dropping to 85%–88% at full continuous load and low input voltage. Using peak efficiency undersizes DC feeders and fuses.
- Omitting the 1.25x continuous-duty multiplier: Running a non-derated fuse or conductor at 100% of
I_dc_maxfor three hours or more overheats lugs and fuse clips, leading to thermal tripping or terminal insulation damage at 75°C (167°F) limits. - Ignoring charger voltage ceiling on 48V fuses: A 51.2V LiFePO4 bank charging to 58.4V exceeds the 58V maximum rating of common bolt-on terminal fuses, creating an arc-clearing hazard during a fault even when the current calculation is correct.
- Confusing surge current with continuous
I_dc_design: Sizing fuses solely for surge watts oversizes the fuse beyond safe cable protection, whereas ignoring surge duration against the inverter limit, BMS peak duration, and fuse time-current curve causes nuisance trips on motor startup.