On this page

Choose an active-limiting inverter-charger (configured to throttle DC charge current as AC loads rise) whenever shore power is 15A–30A at 120V/60Hz (or 10A–16A at 230V/50Hz) and high-draw AC appliances run concurrently. Use a fixed-output standalone AC-DC charger only when its worst-case AC VA draw plus peak concurrent AC appliance load stays below the shore-cord continuous limit, or when you manually step down its DC charge current limit.

Conditions that change the available DC charging rate:

  • Shore interface limit: Pedestal breaker rating, cord ampacity, and any step-down adapter (for example, a 30A RV/marine cord adapted to a 15A household receptacle caps total input at 15A, not 30A).
  • Charger power factor (PF) and efficiency: Non-PFC chargers draw 30%–55% more AC amps than their DC wattage suggests; active PFC chargers keep PF near 0.95–0.99.
  • Peak charging voltage: DC power peaks at absorption voltage (14.6V, 29.2V, or 58.4V for LiFePO4), not nominal voltage (12.8V, 25.6V, 51.2V).
  • Battery temperature: At <=+5°C (41°F), verify the BMS minimum charge temperature (some commercial LiFePO4 packs lock out charging at +5°C). At <=0°C (32°F), hard-block charging unless the battery is actively self-heated; zero AC headroom can be used for charging when the BMS blocks current.

For broader charger topology selection and shore-input sizing, see Shore Chargers.


Core Conversion Formulas (Plain Text)

Do not divide DC charge watts directly by AC line voltage. Convert DC output power through charger efficiency to real AC watts, then divide by power factor to get apparent power in volt-amperes (VA):

P_dc_charge (W) = V_charge_max (V) * I_dc_charge (A)
P_ac_real (W)   = P_dc_charge (W) / Efficiency
S_ac_VA (VA)    = P_ac_real (W) / Power_Factor
I_ac_charger (A)= S_ac_VA (VA) / V_ac_nominal (V)

To find the maximum DC charging current left over after concurrent AC appliances take their share:

I_ac_headroom (A)    = I_shore_limit (A) - I_ac_loads (A)
I_dc_max_charge (A)  = (I_ac_headroom (A) * V_ac_nominal (V) * Power_Factor * Efficiency) / V_charge_max (V)
  • Continuous-duty rule: For steady charging lasting >=3 hours alongside continuous AC loads, cap I_shore_limit at 80% of the pedestal breaker rating (0.80 * I_breaker) unless the inverter-charger's AC input limit is explicitly set to hold total pass-through plus charger current below the thermal trip threshold of the weakest plug or adapter.

Specifications and Headroom Reference Tables

Charger Input Current: PFC vs. Non-PFC (Illustrative)

Illustrative assumptions: 12.8V LiFePO4 bank at 14.6V absorption, 60A DC charge current (P_dc_charge = 876W), 120V/60Hz North America shore input (and 230V/50Hz UK/AU comparison). Always verify rated AC input amps, efficiency, and PF on the charger nameplate.

Charger Type Assumed Efficiency Assumed Power Factor Real AC Power (P_ac_real) Apparent Power (S_ac_VA) AC Current @ 120V AC Current @ 230V (UK/AU)
Active PFC Charger 90% (0.90) 0.98 973 W 993 VA 8.3 A 4.3 A
Non-PFC Charger 85% (0.85) 0.65 1,031 W 1,585 VA 13.2 A 6.9 A

A non-PFC 60A charger consumes nearly 90% of a 15A / 120V outlet's 80% continuous rating (12.0A) by itself, leaving zero margin for a refrigerator, laptop, or water pump.

Shore-Cord Headroom and Remaining DC Charge Amps (Illustrative)

Illustrative assumptions: Active PFC charger (Efficiency = 0.90, PF = 0.98), 80% continuous shore target (0.80 * I_breaker), 12.8V LiFePO4 at 14.6V absorption. Divide the resulting DC amps by 2 for a 25.6V bank (29.2V absorb) or by 4 for a 51.2V bank (58.4V absorb).

Region & Shore Rating Breaker / Cord Rating 80% Continuous Limit Example Concurrent AC Load Remaining I_ac_headroom Max DC Charge Amps @ 14.6V Max DC Charge Amps @ 29.2V Max DC Charge Amps @ 58.4V
NA 120V / 60Hz (NEMA 5-15) 15 A 12.0 A 6.0 A (fridge + electronics) 6.0 A 43.5 A 21.7 A 10.9 A
NA 120V / 60Hz (NEMA 5-20) 20 A 16.0 A 10.0 A (A/C or space heater) 6.0 A 43.5 A 21.7 A 10.9 A
NA 120V / 60Hz (NEMA TT-30) 30 A 24.0 A 14.0 A (roof A/C + misc) 10.0 A 72.5 A 36.2 A 18.1 A
UK/AU 230V / 50Hz (10A GPO) 10 A 8.0 A 4.0 A (kettle/heater cycle) 4.0 A 55.6 A 27.8 A 13.9 A
UK/AU 230V / 50Hz (16A CEE) 16 A 12.8 A 6.0 A (induction/appliances) 6.8 A 94.5 A 47.2 A 23.6 A
UK/AU 230V / 50Hz (32A CEE) 32 A 25.6 A 10.0 A (A/C + water heater) 15.6 A 216.7 A 108.4 A 54.2 A

Step-by-Step Sizing and Coordination Procedure

  1. Determine the weakest shore-input rating: Record the lowest amp rating across the pedestal breaker, shore cord, and any plug adapter (for example, 15A / 120V on a household extension cord, or 10A / 230V on a UK/AU domestic socket). Apply 0.80 for continuous loads lasting >=3h.
  2. Sum concurrent AC appliance amps: Add the nameplate running amps (or VA / V_ac) of all AC loads that operate simultaneously while charging. Note motor/compressor loads (air conditioners, microwaves) that draw higher startup surge currents.
  3. Calculate remaining AC headroom: Subtract concurrent AC load amps from the shore-input limit (I_ac_headroom = I_shore_limit - I_ac_loads).
  4. Convert AC headroom to DC charge amps: Use V_charge_max (14.6V, 29.2V, or 58.4V for LiFePO4; 14.4V, 28.8V, or 57.6V typical for AGM), charger efficiency, and PF from the charger nameplate.
  5. Configure charger coordination:
    • Inverter-charger with AC input limiting: Program the AC input current limit to the weakest shore-chain rating. The unit passes AC power to appliances first and dynamically reduces DC battery charging to stay under the programmed limit.
    • Standalone AC-DC charger (no load-sharing): Set the charger's DC current limit (or select a lower-amp unit) so I_ac_loads + I_ac_charger <= I_shore_limit at V_charge_max.
  6. Verify DC-side wiring and overcurrent protection: Even when shore headroom throttles charging most of the time, the DC cable and fuse between the charger and battery bus must handle 100% of the charger's maximum rated DC output:
    • Calculate round-trip DC cable length (2 * one-way feet or meters) using 75°C copper resistivity (0.02097 ohm·mm²/m).
    • Keep critical charging circuit voltage drop <=3% at full rated DC output.
    • Size conductor ampacity at >=1.25x continuous DC output (>=3h), honoring terminal temperature limits (commonly 75°C) and avoiding undersized SAE J1128 or copper-clad aluminum (CCA) cable traps.
    • Verify fuse max voltage rating >= V_charge_max (for example, 58.4V LiFePO4 absorption exceeds 58V-rated terminal fuses) and fuse rating <= cable ampacity.

Sign-Off Criteria

  • I_ac_loads + I_ac_charger <= I_shore_limit holds during peak concurrent appliance operation using nameplate VA (P_dc / (Efficiency * PF)).
  • Inverter-charger AC input limit matches the lowest-rated shore cord, adapter, or pedestal in the active setup.
  • DC charge conductors have <=3% round-trip voltage drop and >=1.25x continuous ampacity at 75°C terminal ratings for the charger's full rated DC current.
  • DC charge fuse voltage rating is >= V_charge_max and prospective fault current is <= fuse AIC at battery operating voltage.
  • Cold-charging controls are verified: BMS minimum charge temperature checked at <=+5°C (41°F), and charging hard-blocked at <=0°C (32°F) unless self-heated.

Real Failure Modes

  • VA underestimation tripping 15A/20A pedestals: Calculating charger AC draw as P_dc / V_ac ignores efficiency (0.85–0.90) and non-PFC power factor (0.60–0.75). A charger expected to draw 7.3A at 120V actually draws 13.2A and trips a 15A breaker when a refrigerator compressor starts.
  • Adapter and cord overheating before breaker trip: Leaving an inverter-charger's AC input limit at 30A while plugged into a 30A-to-15A adapter lets concurrent AC loads and charging pull 20A–25A long enough to melt the 15A plug blades before a thermal breaker trips.
  • Absorption-tail breaker trip: Sizing shore headroom at nominal battery voltage (12.8V / 25.6V / 51.2V) underestimates peak DC watts by ~14% compared to absorption voltage (14.6V / 29.2V / 58.4V), causing nuisance trips near full charge.
  • Unthrottled standalone charger + motor surge: A fixed-output charger running at full bulk current cannot shed load when an air conditioner or microwave cycles on, tripping the shore breaker on compressor startup.
  • 58V fuse rating exceeded on 51.2V LiFePO4: Using a 58V-rated DC terminal fuse on a 51.2V LiFePO4 bank whose charger reaches 58.4V absorption violates the fuse's maximum voltage rating.