This 80% continuous budget changes under three conditions:

  • Low power factor (non-PFC) chargers: Chargers without active power factor correction (PF 0.65–0.75) draw higher RMS amperes per watt of DC output than nameplate DC watts suggest; size strictly by nameplate maximum AC amperes, not DC wattage divided by 120V.
  • Pedestal and cord voltage sag: Constant-power switching chargers pull more AC current as shore voltage drops across long campsite feeders, 25–50 ft (7.6–15.2 m) cords, and "dogbone" adapters.
  • 50A split-phase single-leg loads: A 50A (120V/240V) pedestal provides two 120V legs (L1 and L2). A single-leg 120V charger draws from only one leg and remains capped at 40 A continuous on that leg, not 80 A.

Regional AC Note (UK/AU 230V/50Hz): This reference applies to North American 120V/60Hz pedestals. UK and Australian campsites and marinas supply 230V/50Hz single-phase power (typically 16A CEE/IEC 60309 or 15A AS/NZS 3112), where the same DC power draws roughly half the AC current and requires 230V/50Hz-rated shore equipment.

For broader shore-charger selection, multi-source priority, and AC/DC coordination, see Shore Chargers Overview.


North American 120V/60Hz Pedestal Input Budgets

Values below assume continuous charging (>=3 hours) at 80% of breaker rating, 120V nominal vs. 108V sagged (10% drop), and an illustrative switching charger with 88% efficiency and 0.95 power factor (PF). Always verify actual efficiency, PF, and maximum AC input amperes on the charger nameplate.

Pedestal Service Connector Type Breaker Rating (Per 120V Leg) Max Continuous AC Budget (80%) Max Apparent Power at 120V (VA) Max Apparent Power at 108V Sag (VA) Illustrative Max DC Output at 108V Sag (88% Eff, 0.95 PF)
15A 120V NEMA 5-15 15 A 12 A 1,440 VA 1,296 VA ~1,083 W (~75 A at 14.4V)
20A 120V NEMA 5-20 20 A 16 A 1,920 VA 1,728 VA ~1,444 W (~100 A at 14.4V)
30A 120V NEMA TT-30 (RV) / L5-30 (Marine) 30 A 24 A 2,880 VA 2,592 VA ~2,167 W (~150 A at 14.4V / ~75 A at 28.8V)
50A 120V/240V (Single Leg) NEMA 14-50 (RV) / SS2-50 (Marine) 50 A (L1 or L2) 40 A (per leg) 4,800 VA 4,320 VA ~3,612 W (~250 A at 14.4V / ~62 A at 58.4V)
50A 120V/240V (Dual Leg) NEMA 14-50 / SS2-50 (240V or balanced L1+L2) 50 A x 2 legs 40 A x 2 9,600 VA 8,640 VA ~7,223 W (combined L1 + L2)

Note on DC voltage ceilings: All battery-side charge calculations stay strictly <=60V DC (12.8V/25.6V/51.2V LiFePO4 nominal with typical 14.2–14.6V / 28.4–29.2V / 56.8–58.4V absorb; 12.0V/24.0V/48.0V AGM/lead-acid nominal).


Core Budgeting Formulas (Plain Text)

Use these equations to check whether a charger fits a pedestal after accounting for voltage sag and concurrent AC loads:

  1. Available Charger AC Current Budget (I_ac_budget)

    I_ac_budget = (0.80 * I_pedestal_leg) - I_ac_other_loads
    
    • I_pedestal_leg: 15, 20, 30, or 40/50 A on the specific 120V leg feeding the charger.
    • I_ac_other_loads: Sum of concurrent AC loads on that same leg (e.g., air conditioner, electric water heater element, microwave, refrigerator AC mode).
  2. Worst-Case Charger AC Input Current (I_ac_worst)

    I_ac_worst = (V_dc_absorb * I_dc_max) / (V_ac_min * Efficiency * PF)
    
    • V_dc_absorb: Peak absorption voltage (e.g., 14.4V, 28.8V, or 58.4V for LiFePO4).
    • I_dc_max: Charger DC output current setting.
    • V_ac_min: Minimum expected shore voltage at the charger input terminals under load (use 108V AC for 10% sag, or 105V AC on long/crowded park runs).
  3. Maximum Safe DC Charge Current (I_dc_budget)

    I_dc_budget = (I_ac_budget * V_ac_min * Efficiency * PF) / V_dc_absorb
    
  4. Illustrative Derivation (30A Pedestal with Concurrent Load)

    • Pedestal: 30A 120V -> 80% leg limit = 24 A.
    • Concurrent AC load on same leg: 11 A (water heater element or converter auxiliary load).
    • Remaining charger AC budget: 24 A - 11 A = 13 A.
    • With sagged shore voltage V_ac_min = 108V, Efficiency = 0.88, PF = 0.95, charging a 25.6V LiFePO4 bank at V_dc_absorb = 28.8V: I_dc_budget = (13 * 108 * 0.88 * 0.95) / 28.8 = 40.7 A DC
    • Action: Cap the charger DC output at 40 A (or set an inverter-charger's AC input limit to 24 A total if it supports dynamic shore-current limiting/PowerAssist).

Step-by-Step Budgeting and DC-Side Coordination

  1. Read the charger nameplate and pedestal rating. Record the charger's maximum AC input amperes, rated AC voltage range (e.g., 90–135V AC), power factor (or VA rating), and maximum DC output current. Inspect the pedestal receptacle (15A, 20A, 30A, or 50A) and confirm whether any adapter ("dogbone") down-rates the connection; the lowest-rated link in the cord/adapter chain sets the ceiling.

  2. Map concurrent AC loads per 120V leg. Identify every AC appliance that can run simultaneously during bulk charging. On a 50A split-phase hookup, verify which leg (L1 or L2) feeds the charger so you subtract only loads on that same leg.

  3. Compute I_ac_worst at sagged voltage (105–108V AC). Verify I_ac_worst <= I_ac_budget. If I_ac_worst exceeds the budget:

    • Lower the AC input current limit on an adjustable inverter-charger (e.g., dial to 12 A on 15A, 16 A on 20A, 24 A on 30A), or
    • Reduce the charger's DC output current limit (I_dc_max) to match I_dc_budget, or
    • Shed/interlock high-draw AC appliances during bulk charging.
  4. Verify DC-side wire sizing, fuses, and battery limits.

    • DC cable ampacity & drop: Size charger-to-battery DC conductors using round-trip length (2 x one-way), 75°C copper resistivity (0.02097 ohm·mm²/m), <=3% voltage drop for critical charging sense/power runs, and >=1.25x continuous ampacity (>=3h), respecting 75°C terminal temperature limits and avoiding undersized SAE J1128 / CCA cable traps.
    • DC fuse ratings: Verify DC fuse ampacity <= cable ampacity, prospective fault current <= fuse AIC at operating voltage, and fuse maximum voltage rating >= max charging voltage (for example, a 58.4V LiFePO4 absorption target on a 48V nominal bank exceeds 58V-rated terminal fuses).
    • Cold-temperature charging check: At <=+5°C (41°F), verify the battery BMS minimum charge temperature threshold (some commercial packs lock out at +5°C). Hard-block charging at <=0°C (32°F) unless the pack is actively self-heated.

Sign-Off Criteria

Before leaving a shore-charging setup unattended:

  • Continuous AC margin: Measured AC clamp-meter draw on the charger's 120V leg at peak bulk/absorption power plus concurrent leg loads is <=80% of the pedestal breaker and lowest-rated cord/adapter.
  • Sagged-voltage stability: Under full charger load, AC voltage at the charger input remains within the charger's rated minimum AC input spec (typically >=105V AC) without brownout faults or breaker tripping.
  • Thermal check: After 30–60 minutes at steady bulk current, pedestal plug blades, dogbone adapters, and DC charger terminals show no excessive heating (no softening, discoloration, or hot-to-the-touch joints).
  • DC protection & BMS alignment: DC charge voltage and current stay within battery BMS limits, DC fuse voltage rating exceeds peak absorption voltage (e.g., >=60V DC rating for 58.4V charge), and battery cell temperature is safely above the BMS low-temp cutoff.

Real-World Failure Modes

  • Nuisance pedestal breaker trips during bulk absorption: Budgeting against 120V nominal with a 1.0 PF assumption underestimates real RMS current when pedestal voltage sags to 106V and a non-PFC charger runs at 0.70 PF—pushing a "1,400 W" charger past 18 A on a 15A or 20A circuit.
  • Melted 15A/20A adapters and dogbones: Running a 30A-capable charger at 20–24 A through a 15A NEMA 5-15 adapter overheats the small blade contacts and trips thermal cutouts or damages the pedestal receptacle, even if the RV/vessel's internal 30A breaker never trips.
  • 50A split-phase single-leg overload: Treating a 50A 120V/240V pedestal as "50 A total for all 120V loads" while running a 30 A single-leg charger alongside a 15 A air conditioner on the same L1 leg trips the 50A L1 pole at 45 A continuous while L2 sits idle.
  • 58V-rated DC fuse failure on 48V LiFePO4 banks: Using 58V-rated battery terminal fuses on a 51.2V nominal LiFePO4 system charged to 58.4V absorption violates the fuse's maximum voltage rating and risks arc-clearing failure during a DC fault.
  • Cold-weather BMS charge disconnect: Starting a high-current shore bulk charge at <=0°C (32°F) (or <=+5°C / 41°F on strict commercial BMS packs) triggers an immediate BMS charge-FET lockout, causing charger over-voltage spikes if the charger lacks battery-disconnect protection.