This configuration governs the battery-charging stage within shore chargers for 12V, 24V, and 48V nominal DC systems strictly at or below 60V DC.

Conditions That Change the Configuration

  • Shore Pedestal and Cord Rating: North America 120V/60Hz pedestals typically supply 15A, 20A, 30A, or 50A; UK/AU 230V/50Hz shore supplies typically provide 10A, 13A, 16A, or 32A. The AC input limit must never exceed the weakest link between the pedestal breaker, shore cord, and inlet rating.
  • Pass-Through Appliance Loads: High-draw AC loads (water heaters, induction cooktops, space heaters, air conditioners) share the same AC input budget. If automatic charge throttling is disabled or set too high, combined pass-through and charger draw trips the pedestal breaker.
  • Battery Chemistry and BMS Limits: LiFePO4 packs enforce strict high-voltage and over-current disconnects, while AGM/lead-acid banks require lower C-rate ceilings (typically 0.1C–0.3C) to avoid overheating.
  • Concurrent DC Charging Sources: When solar MPPT or alternator chargers operate alongside shore power, the inverter-charger DC current ceiling must leave headroom so combined charge current stays below the battery BMS maximum.
  • Ambient and Cell Temperature: Charging at or below +5°C (41°F) requires verifying the battery BMS minimum charge temperature (some commercial packs lock out at +5°C), and charging at or below 0°C (32°F) must be hard-blocked unless the battery has active self-heating.

AC Input-Limit and Pass-Through Coordination

An inverter-charger with dynamic current limiting monitors total AC input current (I_AC_in) and continuously subtracts pass-through appliance current (I_AC_loads) from the configured AC input ceiling (I_AC_limit) to determine the current left for battery charging (I_AC_charge_avail):

I_AC_charge_avail = max(0, I_AC_limit - I_AC_loads)
P_DC_charge_max   = I_AC_charge_avail * V_AC_nom * PF * Eff_chg
I_DC_from_AC      = P_DC_charge_max / V_DC_bulk

Where:

  • V_AC_nom = 120V (North America 60Hz) or 230V (UK/AU 50Hz)
  • PF = charger power factor (check equipment nameplate; typically 0.90–0.99 for PFC chargers)
  • Eff_chg = charger AC-to-DC conversion efficiency (check equipment nameplate; typically 0.85–0.93)
  • V_DC_bulk = instantaneous battery charging voltage (rising toward absorb voltage)

If I_AC_loads exceeds I_AC_limit, charging throttles to 0A DC. Units equipped with inverter-assist (PowerAssist) then invert from the battery bank to cover the deficit (I_AC_loads - I_AC_limit) without tripping the shore breaker; units without assist pass the overload directly to the shore breaker.

Shore Supply Region & Standard Typical Pedestal / Inlet Rating Recommended AC Input Limit (Sustained) Max Gross AC Power at Limit Typical Pass-Through Margin Notes
North America 120V / 60Hz 15A (NEMA 5-15) 12A (80% continuous) to 15A 1,440W – 1,800W One 1,500W (12.5A) appliance leaves 0–2.5A for charging
North America 120V / 60Hz 20A (NEMA 5-20) 16A (80% continuous) to 20A 1,920W – 2,400W Supports one 1,500W appliance plus modest charging
North America 120V / 60Hz 30A (NEMA TT-30 / L5-30) 24A (80% continuous) to 30A 2,880W – 3,600W Standard RV/marine single-leg shore cord
UK / AU 230V / 50Hz 10A – 13A (domestic/adapter) 8A – 10A (continuous) 1,840W – 2,300W Adapter cords require strict thermal derating
UK / AU 230V / 50Hz 16A (CEE / IEC 60309) 13A – 16A 2,990W – 3,680W Standard caravan/marine single-phase shore supply
UK / AU 230V / 50Hz 32A (CEE / IEC 60309) 26A – 32A 5,980W – 7,360W High-capacity marine/off-grid shore connection

Battery Charging Baselines and Combined-Source Ceilings

For full 12V, 24V, and 48V chemistry profiles, nominal and absorb voltage targets, and usable DoD baselines, see Shore Power Battery Chargers. Keep all charging stages strictly at or below 60.0V DC, verify exact absorb, float, and maximum continuous charge current values on the battery datasheet before programming, and enforce temperature-based charge inhibit at or below 0°C (32°F) unless self-heated (verifying BMS lockout thresholds at or below +5°C / 41°F).

When programming the inverter-charger DC charge-current ceiling (I_DC_shore_max), bound it by the battery bank's continuous charge limit (typically 0.5C or per BMS nameplate for LiFePO4; 0.1C–0.3C per datasheet for AGM/lead-acid) minus any concurrent DC charging sources operating on the same bus:

I_DC_shore_max = min(I_charger_nameplate, I_bank_continuous - I_DC_other_sources)

Where I_DC_other_sources is the combined maximum continuous output of active solar MPPT controllers or alternator chargers. If multiple inverter-chargers or parallel battery strings share the bus, verify the ceiling against the weakest BMS or string limit rather than the aggregate bank capacity when one string can disconnect independently.

DC-Side Conductor and Fuse Verification

Even when shore charging current is lower than peak inverter discharge current, verify that the DC feeder and overcurrent protection satisfy both directions of operation:

  1. Continuous Ampacity: Size DC cables and terminals for at least 1.25 * I_DC_continuous for loads or charge cycles lasting 3 hours or more.
  2. Voltage Drop (<=3% Critical): Calculate round-trip drop (2 * L_one_way) using 75°C copper resistivity (0.02097 ohm·mm²/m):
    V_drop = I_DC * (2 * L_m * 0.02097) / A_mm2
    
    Keep voltage drop <=3% of nominal bus voltage so the charger senses true battery terminal voltage and transitions from bulk to absorb accurately.
  3. Terminal Temperature and Wire Traps: Size conductors to the 75°C ampacity column when connected to 75°C-rated inverter-charger terminals. Do not use SAE J1128 105°C/125°C insulation ratings to downsize gauge on 75°C terminals, and do not use copper-clad aluminum (CCA) cable.
  4. Fuse Voltage and Interrupt Rating:
    • V_fuse_max >= V_charge_max: A 51.2V LiFePO4 bank absorbing at 58.4V exceeds the 58V maximum rating of standard bolt-on terminal fuses; use fuses rated >=60V DC (such as 70V–80V DC Class T or rated MEGA/ANL fuses).
    • I_fault_prospective <= AIC at operating DC voltage, and I_fuse <= I_cable_ampacity.

Worked Configuration Example (Illustrative)

Illustrative Assumptions (replace with actual equipment nameplate values):

  • Shore supply: North America 120V/60Hz, 20A pedestal (sustained AC input limit set to 16A).
  • Battery bank: 25.6V 200Ah LiFePO4 (absorb 28.8V, BMS max continuous charge 100A / 0.5C).
  • Inverter-charger: 3000VA / 70A DC max charger, nameplate PF = 0.95, Eff_chg = 0.90.
  • Pass-through load: 1,500W space heater (1500W / 120V = 12.5A AC).

Calculation:

  1. No AC Pass-Through Loads (I_AC_loads = 0A):
    P_DC_avail = 16A * 120V * 0.95 * 0.90 = 1,641.6W
    I_DC_avail = 1,641.6W / 28.8V = 57.0A DC
    
    The 57.0A DC output is below both the charger's 70A nameplate max and the battery's 100A BMS ceiling. Set the DC charge-current ceiling to 70A (or lower if a 30A MPPT is also active, e.g., 60A shore + 30A solar = 90A <= 100A).
  2. With 1,500W Space Heater Running (I_AC_loads = 12.5A):
    I_AC_charge_avail = 16.0A - 12.5A = 3.5A AC
    P_DC_avail        = 3.5A * 120V * 0.95 * 0.90 = 359.1W
    I_DC_throttled    = 359.1W / 28.8V = 12.5A DC
    
    The inverter-charger automatically throttles DC charging from 57.0A down to 12.5A while keeping total pedestal draw at 16.0A.

Configuration Steps

  1. Inspect the Shore Source: Read the pedestal breaker and shore cord ratings (120V/60Hz or 230V/50Hz). Note whether the outlet is shared with other loads or fed through an adapter.
  2. Verify DC Cabling and OCPD: Confirm DC feeder gauge meets <=3% voltage drop at I_DC_max, 1.25x continuous ampacity at 75°C terminal ratings, and that the main battery fuse voltage rating exceeds maximum absorb voltage (<=60V DC bus).
  3. Program Battery Charge Profile: Set bulk/absorb and float voltages per the battery nameplate (e.g., 14.4V / 28.8V / 57.6V for LiFePO4, strictly <=60.0V DC). Enable temperature-based charge inhibit at <=0°C (32°F) and verify BMS lockout threshold at <=+5°C (41°F).
  4. Set the DC Charge-Current Ceiling: Enter the lowest of: charger nameplate max DC amps, battery BMS continuous charge limit, or (BMS max charge amps - max concurrent solar/alternator charge amps).
  5. Set the AC Input-Current Limit: Program I_AC_limit to the shore pedestal or cord rating (use 80% for sustained full-power charging on thermal-sensitive cords/outlets).
  6. Enable Dynamic Current Limiting: Turn on AC input current limiting (and PowerAssist if supported and desired for transient appliance surges above I_AC_limit).

Sign-Off Criteria

  • Total AC input current stabilizes at or below I_AC_limit when bulk charging runs with zero pass-through loads.
  • Switching on a high-draw pass-through appliance causes DC charge current to drop within 1–2 seconds without tripping the shore pedestal breaker.
  • Measured voltage at the battery terminals during bulk/absorb matches the charger's target within <=3% DC feeder drop and remains <=60.0V DC.
  • Battery BMS reports zero over-current, over-voltage, or low-temperature fault flags during a 15-minute sustained bulk-charge check.

Failure Modes

  • Pedestal Breaker Trips on Appliance Startup: I_AC_limit is set above the pedestal rating, dynamic current limiting is disabled, or a motor/compressor surge exceeds the breaker trip curve faster than the charger throttles (enable PowerAssist or lower I_AC_limit).
  • BMS High-Voltage or Over-Current Disconnect: The DC charge-current ceiling ignores concurrent solar MPPT output, or absorb voltage is set too high for imbalanced cells, causing the BMS to open the charge FETs and spike the DC bus.
  • 58V Fuse Failure on 48V (51.2V) LiFePO4: Using a 58V-rated terminal fuse on a bank absorbing at 58.4V exceeds the fuse's DC voltage rating, risking arc-flash or failure to clear a fault.
  • Cold-Weather Lithium Plating or BMS Lockout: Charging LiFePO4 at <=0°C (32°F) without a temperature sensor/BMS block damages cells; charging at <=+5°C (41°F) without checking the BMS datasheet triggers unexpected mid-charge lockouts.
  • DC Terminal Overheating: Sizing DC feeders using 105°C automotive wire tables or CCA cable instead of 75°C copper ampacity causes terminal insulation degradation during multi-hour shore bulk cycles.