Governing choice: Size every conductor for the worst-case thermal zone along its route, not the open-air segments. Select the larger cross-section required by:

  1. Derated ampacity (applying continuous-duty >=1.25x for loads running >=3 h, compartment ambient temperature, and bundling/conduit fill, capped at the lowest terminal temperature limit—typically 75 °C / 167 °F).
  2. Round-trip voltage drop (<=3% for critical circuits, <=10% for non-critical circuits).

For general open-air conductor sizing and voltage-drop tables, see Wire Sizing.


Compartment Environments and Derating Drivers

Routing Environment Heat Dissipation Mechanism Primary Thermal Risk Sizing & Protection Action
Open air / ventilated chase Free convection carries heat away from the jacket. Minimal unless routed near an engine block or inverter exhaust. Apply standard ambient temperature and >=1.25x continuous (>=3 h) factors.
Sealed / unventilated battery box Trapped air stratifies; heat from batteries, busbars, and fuses accumulates. Elevated box ambient temperature (40–55 °C / 104–131 °F) plus 75 °C (167 °F) terminal heating. Derate ampacity to the elevated box ambient; verify fuse and breaker thermal ratings inside the box.
Thermally insulated wall or hull cavity Foam, wool, or spray-foam insulation blocks convection around the jacket. Localized hot spots where conductor insulation softens even while exposed cable ends feel cool. Apply severe insulation-contact derating per cable/standard tables, or route cables in an uninsulated ventilated chase.
Bundled or conduit run inside insulated cavity Mutual heating between adjacent current-carrying conductors plus zero airflow. Compounded temperature rise across all bundled positives and negatives. Multiply ambient/insulation derating by the conductor-count bundling factor; separate high-current feeds where possible.

Baseline Specifications and Hard Limits

  • DC Voltage Boundary: Applies strictly to battery and DC bus circuits <=60 V DC (12 V, 24 V, and 48 V nominal; LiFePO4 12.8 V / 25.6 V / 51.2 V with typical absorb 14.2–14.6 V / 28.4–29.2 V / 56.8–58.4 V; AGM/lead-acid 12.0 V / 24.0 V / 48.0 V).
  • Terminal Temperature Ceiling: Most DC lugs, busbars, circuit breakers, and fuse blocks are rated for 75 °C (167 °F). Using 90 °C (194 °F) or 105 °C (221 °F) marine-grade cable does not permit running the conductor above 75 °C at its terminations; size using the 75 °C ampacity column as the baseline.
  • Continuous Duty Factor: Multiply continuous loads (>=3 hours) by 1.25x before comparing against derated cable ampacity.
  • Voltage Drop Constants: Use round-trip length (2 x one-way length) and 75 °C copper resistivity (0.02097 ohm·mm²/m). Keep critical circuits (inverters, chargers, navigation, primary distribution) <=3% drop and non-critical circuits <=10% drop.
  • Cable Construction Traps:
    • Copper-Clad Aluminum (CCA): Higher resistance and lower ampacity than pure copper; produces excessive I²R heat in enclosed spaces. Use pure copper conductors only.
    • SAE J1128 Automotive Wire: Thin-wall primary wire rated for engine-bay intermittent chassis harnesses lacks the jacket thickness and continuous enclosed ampacity tables required for <=60 V cabin, RV, or marine DC distribution feeders.

Step-by-Step Sizing Procedure

  1. Map the Worst-Case Thermal Zone: Identify the hottest or most heavily insulated section of the cable path (e.g., passing behind narrowboat spray-foam lining, inside an insulated campervan wall, or through a sealed battery enclosure). That segment sets the derating for the entire run.
  2. Establish Peak Compartment Ambient: Check the nameplate ambient ratings and heat-rejection specs of nearby equipment (inverter/charger, MPPT controller, DC-DC charger) plus solar heat gain on unventilated hull sides or roofs.
  3. Compute Worst-Case DC Current:
    • For inverter feeds (e.g., North America 120 V / 60 Hz AC output; UK/AU 230 V / 50 Hz AC output), calculate maximum DC current at the inverter's low-voltage cutoff (V_min) and nameplate efficiency (eff): I_dc = P_ac_continuous / (V_min * eff)
    • For >=3 h continuous loads, apply the continuous factor: I_design = I_dc * 1.25
  4. Apply Compartment and Bundling Derating: Divide I_design by the combined thermal ambient and bundling factor from the cable manufacturer's datasheet or governing marine/RV wiring standard (using the 75 °C terminal-limited column): I_table_required = I_design / (K_ambient * K_bundle)
  5. Check Round-Trip Voltage Drop: Calculate voltage drop using 75 °C copper resistivity (0.02097 ohm·mm²/m) and round-trip length (L_rt = 2 * L_one_way): V_drop = I_dc * (0.02097 * L_rt / Area_mm2) %V_drop = (V_drop / V_nominal) * 100
  6. Select Conductor & Verify Overcurrent Protection: Choose the larger gauge from Step 4 (derated ampacity) and Step 5 (voltage drop). Confirm the fuse or breaker rating satisfies:
    • I_fuse <= I_cable_derated
    • V_fuse_max >= V_charge_max (for example, 58.4 V LiFePO4 absorb exceeds 58 V-rated terminal fuses).

Illustrative Worked Example (24 V Insulated Cavity Inverter Feed)

Assumptions labeled as illustrative; verify exact V_min, efficiency, and cable derating factors on equipment nameplates and cable datasheets.

  • System: 24 V nominal LiFePO4 (25.6 V nominal, 29.2 V max absorb, illustrative V_min = 21.6 V).
  • Load: 2000 W continuous AC inverter (120 V / 60 Hz North America, or 230 V / 50 Hz UK/AU) at 88% (0.88) efficiency.
  • Route: 9.8 ft (3.0 m) one-way (19.7 ft / 6.0 m round-trip), passing through a 122 °F (50 °C) thermally insulated van wall / narrowboat hull cavity bundled with two other loaded conductors. Illustrative combined derating factor: K_total = 0.75.
  1. Worst-Case DC Current: I_dc = 2000 W / (21.6 V * 0.88) = 105.2 A
  2. Continuous Duty (>=3 h): I_design = 105.2 A * 1.25 = 131.5 A
  3. Required 75 °C Baseline Ampacity: I_table_required = 131.5 A / 0.75 = 175.3 A
    • A 2/0 AWG (67.4 mm²) conductor with an illustrative 175 A 75 °C free-air rating derates to 175 A * 0.75 = 131.25 A, which falls short of 131.5 A. Upsize to 3/0 AWG (85.0 mm², or 95 mm² metric).
  4. Round-Trip Voltage Drop Check (3/0 AWG / 85.0 mm²): V_drop = 105.2 A * (0.02097 * 6.0 m / 85.0 mm²) = 105.2 A * 0.001480 ohm = 0.156 V %V_drop = (0.156 V / 25.6 V) * 100 = 0.61% (well under the 3% critical limit).

Takeaway: On short enclosed runs, derated ampacity—not voltage drop—governs the required conductor gauge.


Sign-Off Criteria

  • Every enclosed, sealed, or insulated segment along the route is identified and used as the governing thermal baseline.
  • Conductor selection meets both I_cable_derated >= I_design (>=1.25x continuous >=3 h) and round-trip voltage drop (<=3% critical, <=10% non-critical).
  • Baseline ampacity does not exceed the lowest terminal rating in the circuit (typically 75 °C / 167 °F).
  • Pure copper conductors are specified (zero CCA; zero unrated thin-wall SAE J1128 in enclosed power feeders).
  • Overcurrent protection satisfies I_fuse <= I_cable_derated, V_fuse_max >= V_charge_max, and AIC >= prospective fault current at operating voltage.

Real Failure Modes

  • Hidden Insulation Softening: A cable sized only for open-air ampacity or 3% voltage drop passes through spray-foam hull lining or closed-cell van insulation. Heat cannot escape, softening the jacket and risking a ground fault against a metal hull or chassis while exposed ends appear normal.
  • Terminal & Fuse-Block Overheating: Using 105 °C (221 °F) cable at full 105 °C ampacity inside a sealed battery box conducts excessive heat directly into 75 °C-rated breaker studs, busbars, and fuse holders, loosening torque over time and causing high-resistance thermal runaway.
  • Premature Breaker Tripping: Thermal-magnetic breakers mounted inside unventilated battery boxes trip below their nameplate current rating because elevated box ambient temperature pre-heats the thermal element.
  • CCA & Thin-Wall Wire Degradation: Copper-clad aluminum or undersized automotive primary wire exhibits higher resistance per unit length, accelerating heat buildup inside enclosed chases and leading to brittle, cracked insulation.