On this page

This specification covers the DC output side from the shore charger terminals to the battery bank or DC main bus within the charging circuits sizing framework. On the AC input side (120V/60Hz in North America; 230V/50Hz in UK/AU), verify only that the charger's AC input rating matches the shore power pedestal and breaker; keep all practical wiring work on the <=60V DC side.


Electrical & Environmental Baselines

Parameter 12V Nominal System 24V Nominal System 48V Nominal System
LiFePO4 Nominal / Absorb 12.8V / 14.2–14.6V 25.6V / 28.4–29.2V 51.2V / 56.8–58.4V
AGM / Lead-Acid Nominal 12.0V (absorb ~14.4–14.8V) 24.0V (absorb ~28.8–29.6V) 48.0V (strictly <=60V DC; exclude >60V equalization)
Max Voltage Drop (Round-Trip) <=3% (0.38V at 12.8V) <=3% (0.77V at 25.6V) <=3% (1.54V at 51.2V)
Continuous Duty Factor >=1.25x (bulk stage >=3 h) >=1.25x (bulk stage >=3 h) >=1.25x (bulk stage >=3 h)
Copper Resistivity (75°C) 0.02097 ohm·mm²/m 0.02097 ohm·mm²/m 0.02097 ohm·mm²/m
Cold Charge Gate (LiFePO4) Flag <=+5°C (41°F); block <=0°C (32°F) unless self-heated Flag <=+5°C (41°F); block <=0°C (32°F) unless self-heated Flag <=+5°C (41°F); block <=0°C (32°F) unless self-heated

Conditions That Change the Cable Size

  • Enclosed locker ambient temperature: Shore chargers convert AC to DC at ~85–92% efficiency, rejecting 8–15% of input power as heat into small, unventilated compartments. Standard 30°C (86°F) free-air ampacity tables overstate capacity in 45–60°C (113–140°F) lockers.
  • Terminal temperature ceiling: Even when using 105°C (221°F) marine-grade wire, the usable ampacity is limited to the 75°C (167°F) column if either the charger output stud or battery busbar is rated at 75°C.
  • Sense wires vs. main cables: If the charger lacks dedicated remote voltage-sense leads, exceeding 3% drop on the main DC cables causes the charger to read artificially high terminal voltage and exit bulk stage prematurely.

Illustrative Sizing Calculation (60A, 12.8V LiFePO4 Charger)

Illustrative assumptions (verify actual values on your charger nameplate):

  • Charger DC output: 60 A continuous at 12.8V nominal (14.4V absorb), fed from 120V/60Hz AC shore power (or 230V/50Hz in UK/AU).
  • One-way cable run: 10 ft (3.05 m); round-trip length = 20 ft (6.10 m).
  • Enclosed locker ambient: 50°C (122°F) with 75°C (167°F) rated terminals.
  • Target voltage drop: <=3% of 12.8V = 0.384 V max.

1. Check 3% voltage drop:

A_min (mm²) = (0.02097 ohm·mm²/m x Round_Trip_m x Current_A) / Max_Drop_V
A_min       = (0.0209664 x 6.096 x 60) / 0.384 = 19.97 mm²
  • 4 AWG (21.2 mm²) gives V_drop = (0.0209664 x 6.096 x 60) / 21.2 = 0.362 V (2.83% of 12.8V), which passes voltage drop.

2. Check continuous derated ampacity:

Required Continuous Ampacity = 60 A x 1.25 = 75 A
  • At 50°C (122°F) ambient, a 75°C-rated conductor carries an ambient correction factor of ~0.75 (check the specific standard table for bundling/conduit):
Required 30°C Base Rating = 75 A / 0.75 = 100 A
  • 4 AWG (21.2 mm²) at 75°C is rated 125 A (Blue Sea Systems / ABYC, 30°C free air outside engine room), or 93.75 A after derating.
  • 2 AWG (33.6 mm²) at 75°C provides 170 A base rating (127.5 A derated at 50°C), clearing the 75 A continuous requirement and cutting voltage drop to 0.228 V (1.78%).

Result: Size the run to 4 AWG (21.2 mm²) pure copper—both voltage drop and derated ampacity pass.


Step-by-Step Sizing & Installation

  1. Read the charger nameplate: Record maximum continuous DC output current (A), maximum charging voltage (V), terminal stud size, and terminal temperature rating (typically 75°C / 167°F).
  2. Measure round-trip cable length: Trace the actual physical routing for both positive and negative conductors between the charger and the battery busbar. Multiply one-way distance by 2.
  3. Calculate minimum cross-section for <=3% drop:
    A_min (mm²) = (0.02097 x 2 x One_Way_m x I_charger) / (0.03 x V_nominal)
    
    Convert mm² to the next larger standard AWG size.
  4. Calculate derated continuous ampacity: Multiply charger rated DC current by 1.25 for continuous bulk-stage duty (>=3 hours). Apply the ambient temperature derating factor for the enclosed compartment (typically 45–60°C / 113–140°F) and any bundling factor using the 75°C ampacity column.
  5. Select conductor type and size: Pick the larger AWG from Step 3 and Step 4. Use fine-stranded pure copper cable only—reject copper-clad aluminum (CCA) and thin-wall automotive SAE J1128 primary wire not rated for continuous marine/off-grid compartment duty.
  6. Verify conductor-protection compatibility: Confirm that the selected cable's derated continuous ampacity supports the overcurrent device window (Charger_I_max x 1.25 <= Fuse_Rating <= Derated_Cable_Ampacity). For fuse selection, DC voltage and interrupt (AIC) ratings, battery-end placement, and multi-bank protection, follow Protecting the Shore-Charger-to-Battery Cable.
  7. Check cold-charging interlocks: If the battery bank can experience <=+5°C (41°F), confirm the battery BMS minimum charge temperature threshold (some commercial packs lock out at +5°C). Hard-block shore charging at <=0°C (32°F) unless the battery has active self-heating.

Sign-Off Criteria

  • Cable gauge meets both <=3% round-trip voltage drop at full bulk current and >=1.25x continuous current after enclosed-locker thermal derating at the 75°C terminal limit.
  • Positive and negative conductors are identical gauge pure copper, crimped with closed-end lugs sized to the exact stud diameter, and torqued to manufacturer specification.
  • Derated cable ampacity meets or exceeds the overcurrent device rating (>= 1.25x charger output), with fuse voltage, AIC, and placement verified per Protecting the Shore-Charger-to-Battery Cable.
  • Under full bulk load after 30 minutes in the closed locker, measured voltage drop between charger terminals and battery bus is <=3%, and terminal temperatures remain below 75°C (167°F).

Real Failure Modes

  • Premature absorb/float transition: Undersized or overly long DC cables (>3% drop) make the charger sense a higher voltage than the battery actually sees, tapering current early and leaving the bank undercharged.
  • Thermal damage inside unventilated lockers: Sizing cables from 30°C (86°F) open-air tables ignores the charger's own waste heat, softening insulation and loosening crimped lugs over multi-hour bulk cycles.
  • Conductor-to-fuse ampacity mismatch: Pairing a derated cable with an overcurrent device rated above the cable's 75°C derated ampacity leaves the conductor unprotected during sustained bulk overloads; see Protecting the Shore-Charger-to-Battery Cable for fuse voltage, AIC, and placement failure modes.
  • CCA and SAE J1128 cable traps: Copper-clad aluminum has higher resistance (~1.6x copper), causing unexpected voltage drop and terminal heating; thin-wall SAE J1128 insulation abrades easily on bulkheads.
  • Cold-weather BMS disconnect during shore charging: Leaving a shore charger connected in freezing conditions (<=0°C / 32°F) without a low-temperature cutoff causes the BMS to open the charge FET under load or permanently plate lithium onto the anode if unprotected.