On this page

The first diagnostic split depends on which protective device opens and how fast it trips:

  • Delayed trip (seconds to minutes under load) on the thermal-magnetic breaker (MCB): Total AC current drawn by the inverter-charger plus pass-through appliances exceeds the pedestal rating (or a hot, high-resistance plug causes thermal tripping). Lowering the charger's AC input current limit or shedding pass-through loads resolves it.
  • Instantaneous trip (on plug-in or within milliseconds of charger relay closure) on the RCD or GFCI: Leakage current to earth exceeds the protective threshold (typically 4–6 mA on North American 120 V / 60 Hz Class A GFCI receptacles; 30 mA on UK/AU/EU 230 V / 50 Hz Type A/AC RCDs), or the vehicle/vessel creates a second neutral-to-earth bond downstream of the pedestal.
  • Trip occurs only when the inverter-charger transfers from shore to invert or switches heavy AC output circuits: Suspect a downstream AC output fault or transfer-relay issue rather than the charging stage itself; see Inverter & AC Output Troubleshooting.

For broader shore-charging system behavior and inlet selection, see Shore Charging Troubleshooting.


Competing Causes & Diagnostic Signatures

Symptom / Trip Pattern Most Likely Cause Governing Mechanism First Verification
Breaker trips 10 s to 15 min after charging starts Overcurrent (charger + AC pass-through) Thermal trip curve on 120 V or 230 V pedestal MCB exceeded Check inverter-charger AC input limit vs. pedestal rating
Breaker trips immediately when charger engages (no RCD trip) Short circuit or high inrush current Magnetic trip from shorted AC input stage or large un-buffered transformer inrush Test with all AC pass-through breakers off and charger disabled
GFCI (4–6 mA) or RCD (30 mA) trips immediately on plug-in, before charging starts Neutral-to-earth bond conflict or cord/inlet moisture Current splits between neutral and protective earth (PE), creating imbalance Inspect shore cord and inlet for moisture; verify bonding state
RCD trips only when charger or DC loads run on a UK narrowboat or marina berth Galvanic earth path, hull leakage, or missing isolation transformer Leakage current returns via water/hull earth instead of shore neutral Check galvanic isolator / isolation transformer status and PE continuity
Pedestal trips only when heavy AC appliances run alongside charging Pass-through summation overload Charger current + water heater/AC unit exceeds 15 A / 16 A / 30 A supply Compare total VA against pedestal limit; test charger-only load

Relevant Specifications & Shore Supply Baselines

Regional Shore Pedestal & RCD/GFCI Ratings

Mobile AC interfaces (RV, caravan, marine, and narrowboat shore inlets) operate within fixed pedestal current limits and regional earth-fault thresholds:

Region & Supply Nominal Voltage / Frequency Common Pedestal Ratings Apparent Power Limit (Nominal) Earth-Fault Protection Threshold
North America (RV / Marine) 120 V / 60 Hz (single-phase) 15 A / 20 A / 30 A 1,800 VA / 2,400 VA / 3,600 VA 4–6 mA (Class A GFCI)
North America (Split-phase RV / Marine) 120/240 V / 60 Hz 50 A (two 120 V legs) 12,000 VA total (6,000 VA per leg) 4–6 mA (GFCI where fitted)
UK / Europe / Australia (Caravan / Narrowboat / Marina) 230 V / 50 Hz (single-phase) 10 A / 16 A / 32 A 2,300 VA / 3,680 VA / 7,360 VA 30 mA (RCD / RCBO)

AC Input Demand vs. DC Charging Power

An inverter-charger's AC input current depends on DC battery charging power, converter efficiency, and power factor (PF), plus any AC pass-through loads:

I_ac_charger = (V_dc_charge x I_dc_charge) / (V_ac x Eff x PF)
I_ac_total   = I_ac_charger + I_ac_passthrough

Where:

  • V_dc_charge: Battery absorption/bulk voltage on the <=60 V DC bus (LiFePO4 12.8 V nominal: 14.2–14.6 V; 25.6 V nominal: 28.4–29.2 V; 51.2 V nominal: 56.8–58.4 V; AGM/lead-acid 12.0/24.0/48.0 V nominal: keep all charging stages <=60 V DC).
  • Eff: Typical charger efficiency (0.85–0.92; check equipment nameplate).
  • PF: Power factor (0.95–0.99 for active PFC chargers; 0.65–0.80 for non-PFC chargers).

Illustrative Example (120 V / 60 Hz, 15 A Pedestal vs. 51.2 V LiFePO4 Bank):

  • Assume a 48 V-class (51.2 V nominal) LiFePO4 bank charging at 56.8 V and 30 A DC (1,704 W DC), with charger Eff = 0.88 and PF = 0.95.
  • I_ac_charger = 1,704 / (120 x 0.88 x 0.95) = 17.0 A AC.
  • On a 15 A (1,800 VA) North American pedestal, this charger alone exceeds the 15 A breaker rating and trips the pedestal even with zero pass-through loads.

Illustrative Example (230 V / 50 Hz, 16 A UK Narrowboat / Caravan Pedestal):

  • Assume a 24 V-class (25.6 V nominal) LiFePO4 bank charging at 28.4 V and 70 A DC (1,988 W DC), with Eff = 0.90 and PF = 0.95.
  • I_ac_charger = 1,988 / (230 x 0.90 x 0.95) = 10.1 A AC.
  • Charging alone holds under 16 A, but adding a 1,500 W (6.5 A) electric kettle brings I_ac_total to 16.6 A, tripping the 16 A pedestal MCB.

DC-Side & Temperature Constraints

  • Bus Voltage Ceiling: Keep all battery and DC bus charging voltages strictly <=60 V DC.
  • Cold-Temperature BMS Lockout: If battery temperature is <=+5°C (41°F), verify the BMS minimum charge temperature; at <=0°C (32°F), block charging unless the pack is self-heated. A sudden BMS charge-FET disconnect under high AC input can cause transient current spikes on some older chargers, though it rarely trips an MCB by itself.

Ordered Diagnostic Checks

Perform these checks in order to isolate overcurrent from earth-leakage and bonding faults without modifying shore pedestal hardware.

  1. Identify the Tripped Device on the Pedestal

    • Confirm whether the overcurrent MCB/breaker tripped (handles overloads and short circuits) or the RCD/GFCI test/reset button popped (handles earth leakage).
    • If a combined RCBO tripped, note whether the trip occurred instantaneously on plug-in (earth fault/bonding) or after several seconds to minutes of charging (overload/thermal).
  2. Isolate AC Pass-Through Loads

    • Turn off all downstream AC branch breakers inside the RV, caravan, boat, or portable distribution unit (water heater, space heater, air conditioning, microwave).
    • Reconnect shore power with only the charger/inverter-charger enabled.
    • If the pedestal now holds, the fault was cumulative I_ac_total overcurrent, not a charger defect.
  3. Verify and Lower the Charger's AC Input Current Limit

    • Check the inverter-charger's configured AC input current limit (often labeled "Shore Limit", "AC Input Current", or "PowerControl") via its remote panel, DIP switches, or app.
    • Set the limit at or below 80% of the pedestal rating for continuous charging (>=3 h) where supported (for example, 12 A on a 15 A 120 V supply, or 12–13 A on a 16 A 230 V supply), and verify Power Assist is enabled if the unit supports supplementing shore power from the battery.
    • Confirm the charger's DC bulk/absorb current limit matches the battery bank's nameplate and <=60 V DC bus limits.
  4. Inspect the External Shore Cord and Inlet (Visual & Non-Invasive)

    • With the shore cord unplugged from both ends, inspect the plug blades/pins, locking ring, and vehicle/vessel inlet for heat discoloration, melted plastic, verdigris, salt crust, or water droplets.
    • In rain, fog, or marina spray, moisture bridging between line/neutral and protective earth inside a worn inlet can exceed the 4–6 mA (GFCI) or 30 mA (RCD) trip threshold immediately upon plug-in.
  5. Check the DC Charging Bus (<=60 V DC) and Battery State

    • Inspect DC charger-to-battery cables, terminal lugs, and DC fuse holders (<=60 V DC side) for loose connections or heat damage.
    • Verify the DC fuse voltage rating exceeds the maximum charging voltage (for example, a 58 V-rated terminal fuse is undersized for a 51.2 V LiFePO4 bank charging to 58.4 V; use a fuse rated >=60 V DC).
    • Confirm battery temperature is above the BMS charge cutoff (>+5°C / 41°F check; >0°C / 32°F hard floor unless self-heated) and that no DC short or reversed polarity exists.
  6. Evaluate Neutral-to-Earth Bonding Conflicts

    • When connected to shore power, the shore pedestal provides the single upstream neutral-to-earth (N-E) bond.
    • If an onboard inverter-charger fails to open its internal N-E relay when transferring to shore power—or if a downstream manual bond or miswired adapter ties neutral to ground/earth—normal neutral return current splits onto the protective earth conductor.
    • Even a few milliamperes of diverted neutral current will trip a 4–6 mA GFCI or 30 mA RCD immediately when any load or charger turns on.
  7. Check UK Narrowboat & Marina Galvanic / Hull Earth Paths

    • On steel-hulled UK narrowboats and metal-hulled boats on 230 V / 50 Hz (or 120 V / 60 Hz) marina supplies, protective earth (PE) connected directly to the hull without a functioning galvanic isolator or isolation transformer can create a low-impedance earth path into the water.
    • Small AC filter leakage from switch-mode battery chargers (typically 1–5 mA per unit, higher when multiple chargers or EMI filters run in parallel) or minor dampness in bilge/engine-room AC appliances can sum past the 30 mA RCD threshold.
    • Test by disconnecting secondary AC chargers/appliances one by one to see if cumulative EMI filter leakage drops below the RCD trip point.
  8. Isolate Transfer-Switch and Inverter Output Faults

    • If the pedestal trips only when the inverter-charger switches between inverting and charging, or when a specific AC output circuit is energized after transfer, diagnose the transfer relay and downstream AC output path using Inverter & AC Output Troubleshooting.

Sign-Off Criteria

Before returning the shore-charging setup to unattended service, verify all of the following:

  • Sustained Charging Stability: The pedestal breaker and RCD/GFCI hold continuously for at least 30 minutes at peak bulk/absorption DC charge current with typical expected AC pass-through loads active.
  • Input Current Margin: Configured AC input current limit on the inverter-charger is at or below the pedestal rating (targeting <=80% for continuous >=3 h bulk charging on 120 V / 60 Hz circuits).
  • Thermal Check: Shore plug, inlet pins, and DC battery terminals remain cool to the touch (no unusual warmth or odor) after 30 minutes of full-rate charging.
  • DC Bus Compliance: Maximum charging voltage stays <=60 V DC, DC fuse voltage rating exceeds maximum charge voltage, and battery temperature is within the BMS charge window.

Real Failure Modes

  • Cumulative Pass-Through Overload: An inverter-charger set to a 30 A or 32 A default limit is plugged into a 15 A (120 V) or 16 A (230 V) campsite/marina pedestal using an adapter. Charging alone may hold until a water heater or kettle cycles on, tripping the thermal MCB.
  • High-Resistance Shore Plug Heating: Oxidized or loose inlet pins raise contact resistance, heating the plug housing until the pedestal's thermal trip mechanism opens well below its nominal current rating.
  • Double Neutral-to-Earth Bond: A stuck internal transfer/ground relay in an inverter-charger leaves the vehicle or vessel neutral bonded to earth while on shore power, causing immediate GFCI/RCD trips as soon as current flows.
  • Cumulative Switch-Mode Charger Leakage on 30 mA RCDs: Multiple onboard AC-to-DC chargers, solar-inverter EMI filters, and damp marina/narrowboat wiring each leak 2–8 mA to earth; individually they pass, but together they exceed 30 mA and trip the berth RCD.
  • Undersized DC Fuse Voltage Rating on 48 V-Class Banks: A 58 V-rated DC terminal fuse installed on a 51.2 V LiFePO4 bank experiences 58.4 V absorption voltage, risking arcing or nuisance failure during fault interruption on the DC side.