On this page

This reference specifies the complete 12V bill of materials (BOM), compact utility-bay protection layout, and DC branch distribution plan for a stationary tiny house on wheels operating within a <=60V DC battery bus and <=150V DC cold-weather PV array envelope.


System Baseline and Operating Boundaries

All calculations below use an illustrative stationary tiny house on wheels baseline: a 12.8V 400Ah LiFePO4 battery bank, an 800W roof PV array, and a 1,500W continuous (3,000W surge) pure sine inverter (120V/60Hz AC output for North America; 230V/50Hz AC output for UK/AU). Verify exact continuous watts, surge duration, and cutoff voltages on each device nameplate before purchasing hardware.

Parameter LiFePO4 Baseline AGM / Lead-Acid Alternative Engineering Constraint
Nominal Voltage 12.8V DC 12.0V DC Battery & DC bus strictly <=60V DC
Typical Absorb / Max Charge 14.2–14.6V DC 14.4–14.8V DC Fuse voltage rating must be >= max charge V
Usable Depth of Discharge (DoD) 85% default (80–90% range) 50% 400Ah LiFePO4 = 4,352 Wh usable (5,120 Wh nominal)
Low-Voltage Cutoff (V_min) 11.0V DC (inverter/BMS) 10.5–11.0V DC Size main DC cables and fuses at V_min
Cold Charging Limit Flag <=+5°C (41°F); block <=0°C (32°F) Temperature-compensated Check BMS min charge temp; hard-block <=0°C unless self-heated
PV Array Cold Voc Limit <=150V DC <=150V DC Add lockable disconnect & touch-safety labels if >60V DC

Complete 12V Bill of Materials (BOM)

Quantities and ratings below assume a single compact utility bay (such as a bench seat, loft bulkhead, or exterior-vented mechanical closet) with the battery bank within 3 ft (0.91 m) one-way of the inverter.

Subsystem Component Illustrative Specification Qty Key Selection & Nameplate Checks
Energy Storage 12.8V LiFePO4 Battery Bank 400Ah total (e.g., 2x 200Ah or 4x 100Ah in parallel) 1 bank Integrated BMS with >=200A continuous discharge; verify BMS peak surge duration and <=+5°C (41°F) charge lockout
Main Protection Class T Fuse & Holder 200A, 125V DC, 20,000A AIC 1 Mount within 7 in (180 mm) of positive bank terminal; AIC must exceed bank short-circuit current
Main Isolation Battery Disconnect Switch 275A–300A continuous, <=60V DC 1 Continuous rating >= 1.25x max steady load; never switch under heavy inverter load
Bus Distribution Positive & Negative Busbars 250A–300A tin-plated copper, insulated cover 1 pair Stainless hardware; match stud size to 3/0 AWG and 2 AWG ring lugs
Monitoring Battery Shunt 300A–500A shunt on negative leg 1 All DC loads and charge sources land on the busbar side of the shunt, never directly on battery negative
Inverter Pure Sine Wave Inverter 1,500W cont / 3,000W surge; 120V/60Hz (or 230V/50Hz UK/AU) 1 Standalone AC output receptacles only; confirm >=88% efficiency and V_min = 11.0V DC
Inverter Cable Marine/UL 1426 Copper Cable 3/0 AWG (85.0 mm²), 105°C insulation, 75°C terminals 6 ft (1.83 m) Round-trip length (3 ft / 0.91 m one-way); 200A ampacity at 75°C terminal limit
Solar Array Monocrystalline PV Modules 800W total (4x 200W wired 2S2P) 4 Same-manufacturer MC4-style connectors; never cross-mate third-party solar connectors
PV Isolation 2-Pole DC PV Disconnect >=100V DC (or >=150V DC), 30A non-polarized 1 Required on all PV arrays; mandatory touch-safety labeling if cold Voc exceeds 60V DC
Solar Charge MPPT Charge Controller 100V/60A (or 150V/60A) MPPT 1 Cold Voc < MPPT_Vmax; parallel Isc <= MPPT_Isc_max; hot Vmp above controller startup window
MPPT Output Cable + MIDI/ANL Fuse 4 AWG (21.2 mm²) + 80A fuse (>=32V DC) 1 set 60A * 1.25 = 75A continuous sizing; 4 AWG rated 85A at 75°C
Auxiliary Charge Isolated AC-to-DC Charger (Optional) 40A–60A 12V LiFePO4 profile; 120V/60Hz (or 230V/50Hz) input 1 Plugs into external dedicated power inlet; keep AC input/output ratings strictly isolated from DC bus
DC Distribution 12-Circuit ATC/ATO Fuse Block 100A max bus, negative bus included 1 Fed by 2 AWG (33.6 mm²) cable and 100A MIDI/ANL fuse from main positive busbar
Branch Wiring Tinned Stranded Copper 8 AWG (8.37 mm²) to 14 AWG (2.08 mm²) As mapped Size by larger of voltage drop and 1.25x continuous ampacity; avoid CCA and thin-wall SAE J1128
Grounding Equipment Grounding Bus 6 AWG (13.3 mm²) to chassis frame 1 Single-point chassis bond per inverter/charger manual; verify DC negative-to-chassis bond rules

Compact Utility-Bay Protection Layout

Keep high-current conductors as short and straight as possible inside the utility bay. Every ungrounded positive conductor leaving a battery or busbar must be protected where ampacity decreases.

[12.8V 400Ah LiFePO4 Bank]
   | (+) <= 7 in (180 mm)                 | (-)
   v                                      v
[200A Class T Fuse]                [500A Battery Shunt]
   |                                      |
   v                                      v
[300A Disconnect Switch]           [Negative Busbar (300A)]
   |                                  |       |       |
   v                                  |       |       +---> [Chassis Ground Bond (6 AWG)]
[Positive Busbar (300A)]              |       |
   |                                  |       +-----------> [Inverter (-)]
   +--(3/0 AWG, 3 ft)--> [1,500W Inverter (+)] -> Dedicated 120V/60Hz (or 230V/50Hz) AC Outlets
   |
   +--(4 AWG, 80A Fuse)--> [60A MPPT Controller] <--[2-Pole PV Disconnect] <-- [800W PV (2S2P)]
   |
   +--(4 AWG, 75A Fuse)--> [60A AC-to-DC Charger] <-- Standalone AC Input Concept
   |
   +--(2 AWG, 100A Fuse)-> [12-Circuit DC Fuse Block] ---> Branch Circuits (10A–20A ATC Fuses)

Worst-Case Inverter Current and Fuse Verification

Calculate maximum DC current at the inverter's low-voltage cutoff (V_min = 11.0V) and full-load efficiency (eta = 0.88), not at 12.8V or 14.4V:

I_dc_max = P_ac_cont / (V_min * eta)
I_dc_max = 1,500W / (11.0V * 0.88) = 154.96A (~155A)

Apply the 1.25x continuous-duty multiplier for loads running >=3 hours:

I_cont_sized = 155A * 1.25 = 193.75A
  • Fuse Selection: Choose a 200A Class T fuse (193.75A <= 200A <= 200A 3/0 AWG 75°C ampacity).
  • Fuse Voltage & AIC: A 125V DC Class T fuse exceeds the 14.6V charging ceiling and provides 20,000A AIC. Standard automotive Maxi/ATO fuses (typically 1,000A AIC at 32V) will arc and weld shut under a LiFePO4 dead short.
  • Surge Check: A 3,000W AC surge draws ~310A DC at 11.0V. Verify on the Class T time-current curve that 310A clears slower than the inverter's surge window (typically 2–5 seconds) and that the battery BMS peak discharge rating exceeds 310A for that duration.

MPPT and PV Array Window Checks

For an illustrative 4x 200W array wired 2S2P (per-panel STC: Voc = 24.5V, Vmp = 20.4V, Isc = 10.4A, Imp = 9.8A, Temp Coeff Voc = -0.28%/°C):

  • Cold Voc Check at -20°C (-4°F) (deltaT = -45°C from 25°C STC): Voc_cold = (2 * 24.5V) * [1 + (-0.0028 * -45)] = 49.0V * 1.126 = 55.2V DC This stays under a 100V MPPT limit and remains below the 60V DC touch-safety threshold. If wired 4S1P, Voc_cold = 110.4V DC, which requires a 150V MPPT and >60V DC touch-safety disconnect labeling.
  • Array Isc Check: 2 parallel strings produce 2 * 10.4A = 20.8A, well within a 60A MPPT's MPPT_Isc_max (check controller nameplate).
  • Backfeed Check: With 2 parallel strings, worst-case backfeed is 1 string (10.4A), which is below typical 15A–20A panel max series fuse ratings. If you expand to 3 or more parallel strings, install inline PV string fuses on every positive string rated <= panel max series fuse.
  • Hot Vmp Check: At +65°C (149°F) cell temperature, 2S Vmp_hot drops to ~34–35V DC, staying well above a 12V MPPT's V_batt + 5V startup threshold.

Wire Sizing and DC Branch Distribution Plan

Always size DC conductors using round-trip length (2 x one-way distance) and 75°C copper resistivity (0.02097 ohm·mm²/m). Select the larger gauge required by:

  1. Voltage drop: <=3% for critical circuits (inverter, fridge, heater, CPAP interface, water pump) and <=10% for non-critical circuits (lighting, fans, USB outlets).
  2. Derated ampacity: >=1.25x continuous current (>=3h) at the lowest terminal temperature limit in the circuit (typically 75°C on breakers, busbars, and fuse blocks).
V_drop = I_load * (0.02097 * L_round_trip_m / Area_mm2)
% Drop = (V_drop / V_system) * 100
Circuit Priority Load (A) One-Way / Round-Trip Selected Gauge Drop at 12.8V Fuse (ATC/Class T) Notes
Inverter Main Critical <=3% 155A (at 11.0V) 3 ft / 6 ft (1.83 m) 3/0 AWG (85.0 mm²) 0.64% (at 11.0V) 200A Class T 10 ft one-way raises drop to 2.12%; >14 ft exceeds 3%
Compressor Fridge Critical <=3% 5A run / 15A start 15 ft / 30 ft (9.14 m) 8 AWG (8.37 mm²) 2.68% (at 15A) 15A–20A 10 AWG drops 4.27% at 15A startup, risking low-V cutout
Diesel/Hydronic Heater Critical <=3% 10A glow / 3A run 12 ft / 24 ft (7.32 m) 10 AWG (5.26 mm²) 2.28% (at 10A) 15A–20A Never share ground or power with high-draw pumps
CPAP 12V Interface Critical <=3% 4–7A (check plate) 10 ft / 20 ft (6.10 m) 10 AWG (5.26 mm²) 1.33% (at 7A) 10A–15A Regulated 12V–24V DC-DC adapter; supply interface sizing only
Water Pump Critical <=3% 8A 12 ft / 24 ft (7.32 m) 10 AWG (5.26 mm²) 1.82% 15A Check pump nameplate for locked-rotor current
LED Interior Lights Non-critical 3A 20 ft / 40 ft (12.19 m) 14 AWG (2.08 mm²) 2.88% 10A Split into 2 zones if total length exceeds 40 ft round-trip
USB-C PD / 12V Outlets Non-critical 10A 15 ft / 30 ft (9.14 m) 12 AWG (3.31 mm²) 4.52% 15A Use 10 AWG if powering 100W USB-C laptops continuously
Roof Exhaust Fan Non-critical 4A 15 ft / 30 ft (9.14 m) 14 AWG (2.08 mm²) 2.89% 10A Use 10A fuse to match 14 AWG ampacity

Cable Traps to Avoid

  • Copper-Clad Aluminum (CCA): Reject any wire labeled CCA for tiny house power; CCA has ~1.6x higher resistance than copper, suffers galvanic corrosion in humid utility bays, and creeps under screw terminals.
  • SAE J1128 Automotive Primary Wire: Thin-wall SAE J1128 insulation is rated for open engine-bay routing, not bundled residential-style walls where abrasion and higher conductor temperatures occur. Use UL 1426 marine tinned copper or NEC-listed THHN/MTW in loom/conduit.

Job-Specific Installation Steps

  1. Map and isolate the utility bay: Position the battery bank, main Class T fuse, disconnect switch, busbars, and inverter on a non-conductive mounting board so the inverter-to-battery one-way run stays <=3 ft (0.91 m). Ensure ventilated clearance per the inverter and charger manuals.
  2. Pre-wire the negative shunt path: Mount the shunt directly off the negative battery bank terminal (or busbar jumper) and land the negative busbar, inverter negative, and chassis ground bond on the load/system side of the shunt.
  3. Install battery-side overcurrent protection: Mount the 200A Class T fuse holder within 7 in (180 mm) of the positive bank terminal, followed immediately by the 300A disconnect switch and positive busbar. Keep the disconnect switch OFF and the fuse removed until all terminations are torqued.
  4. Terminate and torque heavy cables: Crimp hydraulic-compressed tinned copper lugs onto 3/0 AWG, 2 AWG, and 4 AWG cables with adhesive-lined heat shrink. Torque all busbar, shunt, and inverter studs to the manufacturer's spec (check manual; typically 8–12 ft-lb / 11–16 N·m for 5/16" or 3/8" studs).
  5. Run and label DC branch circuits: Route 8–14 AWG branch runs through grommeted framing holes or split-loom conduit away from sharp metal edges and plumbing lines. Label every positive and negative conductor at the fuse block.
  6. Connect PV and MPPT in strict order: Connect the MPPT to the battery busbar first (so the controller auto-detects 12V) with the PV disconnect OFF. Verify roof PV array polarity and Voc with a multimeter before closing the 2-pole PV disconnect.

Sign-Off Criteria

Do not put the tiny house into service until every check passes:

  • Voltage-drop verification: Measure voltage at the inverter DC terminals and the compressor fridge terminals under full load; confirm <=3% drop from the battery busbar.
  • Polarity and isolation: Confirm 0V across open disconnects and correct polarity at the MPPT, inverter, and every DC branch socket before inserting fuses.
  • Cold-charge interlock: Verify the MPPT and AC-to-DC charger low-temperature cutoff or battery BMS charge-block setting is active at <=+5°C (41°F) / <=0°C (32°F) if the tiny house operates in freezing climates.
  • Thermal check: Run the inverter at ~1,200–1,500W for 20 minutes and inspect all 3/0 AWG lugs, the Class T fuse holder, and the disconnect switch with an IR thermometer; no termination may exceed its 75°C (167°F) terminal limit.

Real Failure Modes

  • Inverter low-voltage shutdown on long 12V runs: Placing the battery bank 12–15 ft (3.66–4.57 m) from a 1,500W 12V inverter causes >3% cable drop plus lug resistance, tripping the inverter's 11.0V cutoff while the battery still holds 40% state of charge.
  • BMS cold-weather charge lockout: Commercial 12.8V LiFePO4 packs commonly lock out charging at +5°C (41°F) or 0°C (32°F). Leaving an unheated utility bay in winter disables solar recharging even on sunny days.
  • Low-AIC fuse arc failure: Using a 32V automotive ANL or Maxi fuse as the main battery fuse on a 400Ah LiFePO4 bank risks sustained DC arcing during a dead short because fault current exceeds the fuse's 1,000A interrupting rating.
  • Cross-mated solar connectors: Mixing MC4-style connectors from different manufacturers on the roof PV array creates high-resistance contacts that overheat and melt inside roof penetrations.
  • Shunt bypass: Landing a DC-to-DC charger, heater, or chassis ground directly on the battery negative post instead of the load side of the shunt corrupts state-of-charge tracking.