On this page
Use LPG mode whenever running off a house battery or portable power station. Reserve 120V/60 Hz (North America) or 230V/50 Hz (UK/AU) AC mode for shore power or generator operation, and restrict the 12V DC heating element (present on three-way models only) to active engine/alternator charging via an ignition-switched or voltage-sensing relay. For 12V/24V compressor fridges that run directly from batteries without gas, see the refrigeration loads overview.
Mode Specifications and Duty Cycles
Two-way absorption fridges support AC and LPG only; three-way models add a 12V DC resistive heating element for road transit. Because absorption units use resistive heaters rather than a motor-driven compressor, they have no inductive startup surge (1.0x steady-state current).
| Operating Mode | Typical Power (W) | Line Current | Duty Cycle | Daily Energy (Wh/day) | Primary Supply Source |
|---|---|---|---|---|---|
| 12V DC Heater (3-way only) | 120–210 W | 10.0–17.5 A at 12.0 V (9.4–16.4 A at 12.8 V) | ~100% while driving (often un-thermostated) | 2,880–5,040 Wh (if run 24 h) | Tow-vehicle/RV alternator (>30 A spare capacity) |
| 120V/60 Hz AC Heater | 250–380 W | 2.1–3.2 A AC | 50–80% (ambient dependent) | 3,000–7,300 Wh AC | Shore power or generator |
| 230V/50 Hz AC Heater (UK/AU) | 250–380 W | 1.1–1.7 A AC | 50–80% (ambient dependent) | 3,000–7,300 Wh AC | Shore power or generator |
| LPG Mode (12V control + igniter) | 4–15 W steady (10–25 W ignition spike) | 0.3–1.25 A at 12.0 V | 100% board / intermittent gas valve & fan | 96–360 Wh DC | 12V house battery or regulated 12V DC port |
Check the fridge nameplate inside the fresh-food compartment for exact wattage; some 12V elements are rated at 13.5 V or 14.0 V, which slightly reduces wattage at 12.0 V.
Battery, Inverter, and Portable Power Station Feasibility
House Battery Runtime Comparison
Illustrative comparison using a 12.8 V 100 Ah LiFePO4 battery (1,280 Wh nominal; 1,088 Wh usable at 85% default DoD) and a 12.0 V 100 Ah AGM battery (1,200 Wh nominal; 600 Wh usable at 50% DoD):
- LPG Mode (assuming 8 W average / 192 Wh/day; 15 W max with cabinet fan / 360 Wh/day):
- 100 Ah LiFePO4: 3.0 to 5.7 days
- 100 Ah AGM: 1.7 to 3.1 days
- 12V DC Heater (assuming 180 W / 15.0 A at 12.0 V, 100% duty cycle):
- 100 Ah LiFePO4: 6.0 hours (
1,088 Wh / 180 W) - 100 Ah AGM: 3.3 hours (
600 Wh / 180 W)
- 100 Ah LiFePO4: 6.0 hours (
- AC Heater via 12V Inverter (assuming 325 W AC element, 65% duty cycle, 85% inverter efficiency, 15 W inverter idle tare):
- Active DC draw:
325 W / 0.85 + 15 W = 397 W(~33 A at 12.0 V) - Daily DC energy:
(325 W * 24 h * 0.65) / 0.85 + (15 W * 24 h) = 6,325 Wh/day - Worst-case inverter DC current at low-voltage cutoff (
V_min = 10.5 V, 380 W element, 85% efficiency):I_dc = 380 W / (10.5 V * 0.85) = 42.6 A - 100 Ah LiFePO4 runtime: ~2.7 hours of active heating (~4.2 hours wall-clock before cutoff).
- Active DC draw:
Portable Power Station Feasibility
- 12V DC Element via Car Socket: Not feasible for most units. Standard 12V cigarette-lighter ports are typically rated 10 A (120 W) to 15 A (180 W) max, though limits vary by station. Running a 150–210 W continuous load through a barrel/car plug overheats the plug spring and trips port overcurrent protection.
- AC Element via Inverter Output: A 500 W+ continuous inverter easily handles the 250–380 W resistive load (no surge), but a 1,000–2,000 Wh power station still depletes in 2.5 to 5.5 hours once 15% conversion loss and 10–25 W idle tare are included.
- LPG Mode via DC Output: Fully feasible. A 500 Wh power station runs LPG control power for 1.5 to 4 days if the 12V DC port does not auto-sleep below 5–10 W.
12V DC Wiring, Isolation, and Protection
Most three-way fridges separate the high-current 12V heater feed from the low-current 12V control/LPG feed. Never bridge the control board feed off an undersized or voltage-dropped heater wire.
Wire Sizing (75°C Copper, Round-Trip Method)
Because resistive heating power drops with the square of voltage (P = V^2 / R), a 10% voltage drop reduces heating output by 19%. Target <=3% voltage drop on the 12V heater circuit (treat <=10% only as an absolute ceiling for non-critical circuits).
Using 75°C copper resistivity (0.02097 ohm·mm²/m):
A_min (mm²) = (I_dc * L_round_trip_m * 0.02097) / V_drop_max
Worked example (illustrative 180 W element, 15.0 A at 12.0 V, 20 ft / 6.1 m one-way = 40 ft / 12.19 m round-trip):
- Continuous ampacity check (
>= 1.25xfor loads >= 3 hours):15.0 A * 1.25 = 18.75 A. - Voltage drop check at
<= 3%(0.36 Vmax drop at12.0 V):A_min = (15.0 * 12.19 * 0.02097) / 0.36 = 10.65 mm² - Conductor selection:
- 8 AWG (8.37 mm²) yields
0.458 Vdrop (3.82%)—acceptable only on shorter runs (<= 15 ftone-way). - 6 AWG (13.3 mm²) or 16 mm² metric yields
0.288 Vdrop (2.40%)—meets<= 3%and handles 75°C terminal limits cleanly.
- 8 AWG (8.37 mm²) yields
- Cable traps to avoid: Do not use Copper-Clad Aluminum (CCA) or thin-wall SAE J1128 GPT automotive wire sized purely by 105°C ampacity; follow 75°C terminal ratings and pure copper cross-section.
Overcurrent Protection and Alternator Isolation
- Heater Circuit Fuse: Size at
>= 1.25xcontinuous current (20 Aor25 Afor a 15 A load), strictly<=cable ampacity. Verify fuse max voltage>=max charging voltage (e.g.,>= 14.6 Vfor 12.8 V LiFePO4; standard 32 V or 58 V automotive/marine fuses qualify) and AIC>=battery/alternator prospective fault current. - Control Board Fuse: Typically
3 Ato5 Aon a dedicated 14–16 AWG (2.08–1.31 mm²) feed from the house battery bus so the fridge stays lit on LPG when the engine is off. - Engine-Off Isolation: Feed the 12V heater through a 40 A+ continuous-duty relay triggered by alternator D+, ignition ACC, or a voltage-sensing relay (VSR) set to close above
13.3 Vand open below12.7 V(adjust higher for LiFePO4 resting voltage of13.3–13.4 Vso the fridge does not stay on after engine shutdown).
Installation Verification and Sign-Off
- Nameplate check: Confirm exact 12V DC and 120V/230V AC wattages and whether the model is 2-way or 3-way.
- Loaded terminal voltage: With the engine running and 12V DC mode active, measure voltage directly at the fridge rear 12V heater terminal block.
- Pass:
>= 12.6 Vunder full heater load (<= 3%drop from alternator/distribution bus).
- Pass:
- Engine-off cutoff: Shut off the engine and confirm 12V heater terminal voltage drops to
0 Vwithin 5–30 seconds (depending on VSR delay). - Control feed check: Switch to LPG mode with engine off and verify 12V control terminal stays energized (
12.0–13.6 V) and gas valve holds open.
Common Failure Modes
- Dead Battery from Un-Isolated 12V Heater: Leaving 12V mode wired to a constant-hot bus drains a 100 Ah AGM to 50% DoD in ~3.3 hours and trips a 100 Ah LiFePO4 BMS in ~6 hours.
- Warm Fridge in Transit (Tow-Vehicle 7-Pin Drop): Factory 7-pin trailer pin-4 auxiliary wires (often 10–12 AWG through a long chassis run) commonly drop 1.5–2.5 V under a 15 A load. At
10.5 V, a 12V heater produces only ~76% of its rated heat, stalling the ammonia boiler. Use a dedicated 6–8 AWG Anderson/high-current trailer feed or run LPG in transit where legally permitted. - Auto-Mode Draining Inverter Bank: Leaving the fridge in
Autowhile connected to an inverter causes the control board to prioritize 120V/230V AC over LPG, draining the battery at ~400 W DC instead of 8 W. - LPG Shutdown at Low-Temperature or BMS Cutoff: Even with a full propane tank, LPG mode stops cooling immediately if the 12V house battery hits low-voltage cutoff or if a LiFePO4 battery is depleted after cold-charging lockout (
<= 0°C/32°Fhard block unless self-heated; verify BMS minimum charge limit at<= +5°C/41°F).
Part of Refrigeration Loads