On this page
- Direct DC bus (12V, 24V, or 48V nominal, strictly <=60V DC): Use this for DC roof vent fans, standalone DC extract fans, DC evaporative coolers, and native DC inverter-driven mini-splits. Direct DC eliminates inverter conversion losses (typically 10–15%) and continuous inverter idle tare draw (typically 15–50 W).
- Pure sine wave AC inverter (120V/60Hz North America; 230V/50Hz UK/AU): Required for standard AC rooftop air conditioners, AC mini-splits, and AC compressor dehumidifiers. Fixed-speed AC compressors demand 3x to 6x running current during startup (Locked Rotor Amps, LRA), which typically forces a 24V (25.6V) or 48V (51.2V) battery bus and a high-surge inverter or soft-starter.
- Portable power stations: Feasible for roof vent fans, evaporative coolers, small dehumidifiers, and low-draw inverter mini-splits. Most mid-size portable stations fail on fixed-speed RV rooftop air conditioners due to LRA surge limits and rapid battery depletion from inverter tare draw.
For multi-appliance load summing and system-wide power budgets, see the Loads Overview.
Consolidated Appliance Specifications and Supply Feasibility
All wattage, surge, and duty-cycle figures below are illustrative ranges. Always verify the exact Rated Load Amps (RLA), Full Load Amps (FLA), Locked Rotor Amps (LRA), voltage, and frequency (50 Hz, 60 Hz, or 50/60 Hz) on the equipment nameplate before finalizing wire, fuse, or inverter sizing.
| Appliance Type | Typical Interface | Illustrative Running Power | Startup / Surge Profile | Typical Duty Cycle | Primary Supply & Feasibility Constraint |
|---|---|---|---|---|---|
| Rooftop Air Conditioner (Fixed-Speed) | 120V/60Hz AC (NA) or 230V/50Hz AC (UK/AU) | 1,100–1,800 W (cooling); 150–300 W (fan only) | High LRA surge: 3,000–5,500 W for 0.1–0.5 s unless fitted with a soft-starter | 40–85% in hot sun; 100% during initial cabin pull-down | Inverter surge rating, BMS peak-current limit, and high DC amps on 12V buses; 24V/48V bus recommended |
| Mini-Split Air Conditioner (Inverter-Driven) | 120V/60Hz AC, 230V/50Hz AC, or native 12V/24V/48V DC | 250–900 W modulated (up to 1,200 W max pull-down) | Soft-start ramp: <=1.2x running power; negligible LRA spike | 60–100% (compressor modulates speed rather than cycling hard) | Continuous >=3 h thermal derating on DC wiring; overnight Wh capacity and inverter tare draw on AC models |
| Roof Vent Fan | 12V or 24V DC (native) | 4–45 W (speed-dependent) | Negligible: ~1.2x–1.5x for <0.1 s | 30–100% (often >=3 h continuous overnight) | Voltage drop on long roof runs (<=10% non-critical, <=3% if continuous critical ventilation) |
| Standalone Extract Fan | 12V/24V DC or 120V/230V AC | 5–60 W (DC); 20–100 W (AC) | Low: 1.2x–2x for <0.2 s | 10–100% (intermittent galley/bath or 24/7 enclosure exhaust) | Continuous >=3 h ampacity derating if used for battery/equipment compartment ventilation (<=3% drop) |
| Evaporative Cooler | 12V/24V DC or 120V/230V AC (blower + water pump) | 35–150 W (portable/RV DC); 150–400 W (larger AC) | Low to moderate: 1.5x–2.5x for 0.2 s on AC blowers | 50–100% in dry climates | Check DC port current limit on portable stations; do not assume 120 W universal car-socket capability |
| Dehumidifier (Compressor vs. Peltier) | 120V/60Hz AC or 230V/50Hz AC (compressor); 12V DC (Peltier) | 280–650 W (compressor); 40–90 W (Peltier) | Compressor: 2.5x–4x LRA for 0.1–0.4 s; Peltier: none | 35–75% (humidistat-cycled) | Compressor startup surge + overnight inverter tare draw; Peltier units have low power but very low moisture removal |
Regional AC Nameplates: 120V/60Hz (NA) vs. 230V/50Hz (UK/AU)
For mobile AC interfaces (inverter outputs, shore-power transfer switches, and appliance cords), sizing depends on nameplate voltage and frequency ratings:
- AC current vs. DC battery current: A 230V/50Hz UK motorhome or Australian caravan rooftop air conditioner draws roughly half the AC amperage of an equivalent-wattage 120V/60Hz North American unit (for example, ~6.5 A at 230V vs. ~12.5 A at 120V for a 1,500 W real load). However, DC battery current is identical for the same real wattage and inverter efficiency. Moving from 120V AC to 230V AC does not reduce battery bank size or DC cable gauge.
- Frequency compatibility: Fixed-speed AC compressor motors and shaded-pole extract fans designed strictly for
50 Hzor60 Hzwill overheat or draw excessive current if powered at the wrong frequency. Confirm the nameplate states50/60 Hzbefore cross-region use, and match the inverter output frequency to the appliance. - AC receptacles and protection: Verify that the inverter AC output continuous rating, surge rating, and GFCI/RCD receptacle or transfer rating exceed the appliance nameplate FLA and LRA. Keep all practical wiring modifications strictly on the
<=60V DCside.
Step-by-Step Supply Sizing and Plain-Text Formulas
1. Determine Real Running Power, Surge Power, and Daily Energy
Read W (watts), RLA (Rated Load Amps), and LRA (Locked Rotor Amps) from the appliance nameplate. If only AC amps are listed, estimate real power using an illustrative motor power factor (PF = 0.85 to 0.95 for compressors):
P_run_W = V_AC * I_AC * PF
P_surge_W = V_AC * LRA * PF_start (illustrative PF_start = 0.60 to 0.75)
Compute daily energy demand using the expected active hours and thermostat/humidistat duty cycle:
E_daily_Wh = P_run_W * Hours_active * Duty_cycle
2. Calculate Worst-Case DC Current
Size all DC conductors, fuses, and BMS limits at the minimum operating voltage (V_min) of the battery bank under load—not at nominal or charging voltage—and divide by inverter efficiency (Eff_inv, typically 0.85–0.92 for AC loads; 1.0 for native DC loads):
I_DC_max = P_run_W / (V_min * Eff_inv)
I_DC_surge = P_surge_W / (V_min * Eff_inv)
Illustrative comparison (1,500 W continuous / 3,200 W startup rooftop AC):
- 12.8V LiFePO4 bus (
V_min = 11.5 V,Eff_inv = 0.88):I_DC_max = 1500 / (11.5 * 0.88) = 148.2 AI_DC_surge = 3200 / (11.5 * 0.88) = 316.2 A
- 51.2V LiFePO4 bus (
V_min = 46.0 V,Eff_inv = 0.90):I_DC_max = 1500 / (46.0 * 0.90) = 36.2 AI_DC_surge = 3200 / (46.0 * 0.90) = 77.3 A
On a 12V bus, a single 1,500 W rooftop AC pushes continuous current near 150 A and startup current above 315 A, which trips many 100–200 A BMS modules. Stepping up to a 24V (25.6V) or 48V (51.2V) bus cuts DC current by 2x to 4x.
3. Size Usable Battery Capacity
Account for inverter idle tare draw (P_tare_W, typically 15–50 W) during the entire period the inverter remains switched on, plus usable Depth of Discharge (DoD_usable: default 0.85 for LiFePO4 [0.80–0.90 range]; 0.50 for AGM/lead-acid):
E_total_Wh = (E_daily_Wh / Eff_inv) + (P_tare_W * Hours_inverter_on)
Wh_nominal_required = E_total_Wh / DoD_usable
Illustrative example (AC dehumidifier): A 400 W compressor dehumidifier running at a 50% duty cycle for 10 hours (E_daily_Wh = 2,000 Wh) on an inverter with Eff_inv = 0.88 and P_tare_W = 25 W over 10 hours requires:
E_total_Wh = (2000 / 0.88) + (25 * 10) = 2,273 + 250 = 2,523 Wh
On LiFePO4 (DoD_usable = 0.85), minimum nominal bank size is 2,523 / 0.85 = 2,968 Wh (e.g., ~232 Ah at 12.8V). On AGM (DoD_usable = 0.50), it requires 5,046 Wh.
4. Size DC Conductors (Voltage Drop and Continuous Ampacity)
Always calculate using round-trip length (2 x one-way distance) and 75°C copper resistivity (0.02097 ohm·mm²/m):
L_rt_m = 2 * L_one_way_m (1 ft = 0.3048 m)
A_mm2 = (I_DC_max * L_rt_m * 0.02097) / (V_sys * V_drop_limit)
Apply both sizing gates and select the larger conductor (smaller AWG / larger mm²):
- Voltage drop limit (
V_drop_limit):<= 3%(0.03) for critical circuits: inverter DC feeds, compressor-driven DC mini-splits, and continuous enclosure/battery extract fans.<= 10%(0.10) for non-critical circuits: intermittent cabin roof vent fans and portable DC evaporative coolers.
- Continuous ampacity (>=3 hours):
- Cooling and ventilation loads frequently run >=3 hours continuously. Size conductor ampacity to
>= 1.25 * I_DC_maxafter derating for ambient temperature (engine rooms, hot roofs) and conduit/bundle fill. - Honor terminal temperature limits (typically 75°C on breakers, busbars, and inverter lugs—never rely on 105°C wire ratings to downsize wire landed on 75°C terminals).
- Avoid SAE J1128 thin-wall automotive wire traps (often smaller cross-section than marine UL 1426 AWG) and never use Copper-Clad Aluminum (CCA) cable on high-current cooling or inverter feeds.
- Cooling and ventilation loads frequently run >=3 hours continuously. Size conductor ampacity to
5. Select DC Fuses and Verify BMS Peak Limits
- Continuous & cable protection:
1.25 * I_DC_max <= Fuse_rating_A <= Derated_cable_ampacity_A - Voltage rating (
Fuse_Vmax >= V_charge_max):- 12.8V LiFePO4 (14.2–14.6V absorb): >=32V DC fuse.
- 25.6V LiFePO4 (28.4–29.2V absorb): >=32V DC fuse.
- 51.2V LiFePO4 (56.8–58.4V absorb): >=60V DC (typically 70V–80V+ DC) fuse. Do not use 58V-rated terminal fuses on 48V LiFePO4 banks charging to 58.4V.
- Interrupt rating (AIC): Verify prospective battery short-circuit fault current is
<= Fuse_AICat operating voltage (LiFePO4 banks require high-AIC fuses such as Class T near the main bus). - Surge coordination: Confirm
I_DC_surgestays within the inverter surge window, the BMS peak current duration (often 1–5 seconds), and the fuse time-current melting curve for the 0.1–0.5 s compressor start.
6. Check Portable Power Station Feasibility
Do not rely on advertised peak watts alone. Verify all three constraints:
- AC/DC output limits:
Station_continuous_W >= P_run_WandStation_surge_W >= P_surge_W. For DC-powered fans or evaporative coolers, check the specific DC port current limit in the manual—do not assume a universal 120 W (10 A at 12V) limit or assume a cigarette-lighter socket can sustain high continuous draw without overheating. - Usable Wh runtime:
(UseRuntime_h = (Wh_station * Eff_conv) / ((P_run_W * Duty_cycle) + P_tare_W)Eff_conv~0.85 for AC inverter output or ~0.92 for regulated DC output if not specified by the manufacturer.)
Sign-Off Criteria
Before placing a cooling or ventilation circuit into service, verify every item below:
- Bus voltage boundary: Battery and DC distribution bus remains strictly
<=60V DCat peak absorb voltage (14.6V / 29.2V / 58.4V for LiFePO4). - Startup surge verified:
I_DC_surgeatV_minis below the inverter surge cutoff, BMS peak-current duration limit, and fuse time-current trip threshold. - Conductor sizing: Selected AWG / mm² meets both
<=3%(critical) or<=10%(non-critical) round-trip voltage drop and>=1.25xcontinuous (>=3 h) derated ampacity at 75°C terminal limits. - Fuse ratings:
Fuse_Vmax >= V_charge_max(no 58V fuses on 48V LiFePO4),Fuse_AIC >= prospective fault current, andFuse_A <= Cable_ampacity_A. - Cold-charging boundary: If the battery bank is installed in an unconditioned compartment, verify BMS minimum charge temperature at
<=+5°C(41°F) and confirm hard charge lockout at<=0°C(32°F) unless self-heating is active.
Real Failure Modes
- Hot-restart locked-rotor trips: Turning an AC rooftop unit or compressor dehumidifier off and immediately back on traps high refrigerant head pressure, driving LRA surge to the upper end of its range and tripping the inverter overload or BMS short-circuit protection.
- Voltage sag cutoff on undersized 12V runs: A 12V inverter or DC mini-split fed by undersized cable, long uncompensated round-trip runs, or CCA wire experiences >5–10% voltage drop during compressor ramp-up, triggering a false low-voltage shutdown while the battery still has >50% state of charge.
- 58V terminal fuse over-voltage on 48V LiFePO4: Charging a 51.2V LiFePO4 bank to 56.8–58.4V exceeds the 58V DC rating of standard automotive/marine terminal fuses, risking arc-sustained failure during a fault.
- Overnight tare drain: Leaving a 2,000–3,000 W inverter powered on overnight to cycle a 350 W dehumidifier or mini-split wastes 300–600 Wh in idle tare draw alone, depleting small banks before morning solar generation begins.
- Unnoticed 50Hz / 60Hz mismatch: Running a 60Hz-only North American rooftop AC on a 50Hz UK/AU inverter (or a 50Hz-only fan on 60Hz) alters motor synchronous speed and reactance, causing excessive winding heat and premature thermal cutout.
In this section
- AC Dehumidifier Load Specs AC compressor dehumidifiers draw 180-450 W (3x-5x surge), while 230 V/50 Hz desiccant models pull 300-700 W steadily and drain batteries overnight.
- AC Evaporative Cooler Load Specs An AC evaporative cooler draws 80-350 W (2x-4x motor surge), making inverter idle loss and pure-sine output the main limits on 120 V or 230 V systems.
- AC Extract Fan Load Specs An AC extract fan draws 25-150 W with a 2x-4x inductive startup surge, and inverter standby losses often use more battery energy than the fan itself.
- AC Mini-Split Load Specs Inverter-driven AC mini-splits ramp smoothly without locked-rotor surge, so off-grid sizing hinges on cooling watts, idle loss, and 120 V/230 V input.
- Native DC Dehumidifier Load Specs A 12 V or 24 V DC dehumidifier draws 25-80 W continuously with minimal startup surge, accumulating high 24-hour energy use for modest moisture removal.
- Native DC Evaporative Cooler Load Specs A 12 V or 24 V DC evaporative cooler draws 30-120 W without compressor surge, enabling all-day dry-climate cooling when sized for a 1.25 duty factor.
- Native DC Extract Fan Load Specs A 12 V, 24 V, or 48 V DC extract fan draws steady low current under duct pressure, making 1.25 continuous-duty sizing and low voltage drop key.
- Native DC Mini-Split Load Specs A 12 V, 24 V, or 48 V DC mini-split avoids inverter standby loss and startup spikes by modulating directly from the battery within voltage limits.
- Native DC Roof Vent Fan Load Specs A 12 V or 24 V DC roof vent fan draws 0.2-5 A across speeds, requiring a 1.25 continuous-duty factor and clean voltage regulation for PWM boards.
- Native DC Rooftop Air Conditioner Load Specs A 12 V, 24 V, or 48 V DC rooftop AC eliminates inverter losses and surges, but pulls 40-80 A at 12 V and trips if circuit voltage drop exceeds 3%.
- AC RV Rooftop Air Conditioner Load Specs An AC RV rooftop AC needs pure-sine power for a 1,100-1,800 W running load and a 2,500-4,500 W startup surge on 120 V/60 Hz or 230 V/50 Hz.
Part of Electrical Loads