Four operating conditions change the required converter rating:
- Enclosure ambient temperature above the datasheet knee (commonly 104°F / 40°C), which forces linear output current derating or triggers thermal foldback.
- Inductive or capacitive startup surges (compressors, pumps, fans, or downstream DC power supplies), which trip constant-current or hiccup protection if peak demand exceeds the converter's transient envelope.
- Minimum battery bus cutoff voltage (
V_in_min), which drives worst-case primary input current (I_in_max) higher as the bank discharges. - Continuous duty (>= 3 hours), which requires 1.25x conductor and overcurrent sizing on both the primary input and regulated output circuits.
Sizing Formulas and Bus Specifications
Use the following plain-text equations with values from the converter datasheet and load schedule:
I_out_cont = Sum(I_load_i) [or Sum(P_load_i / V_out_nom) for all concurrent continuous loads]
I_out_peak = I_out_running + I_inrush_max
I_out_rated_min = I_out_cont / K_temp
I_in_max = (V_out_nom * I_out_cont) / (V_in_min * eff_min)
I_in_peak = (V_out_nom * I_out_peak) / (V_in_min * eff_min)
Where:
K_tempis the ambient thermal derating factor (<= 1.00) read from the converter's datasheet curve at maximum expected enclosure temperature (T_amb_max).V_in_minis the battery bank low-voltage disconnect (LVD) or BMS cutoff voltage minus primary cable voltage drop.eff_minis the converter's minimum full-load efficiency atV_in_min(expressed as a decimal, typically0.85to0.94depending on topology and load).
DC Bus Voltage Baselines (<= 60V DC)
| Nominal Bus | Chemistry | Typical Operating & Absorb Range | Illustrative V_in_min (LVD) |
Input Fuse Voltage Floor |
|---|---|---|---|---|
| 12V | LiFePO4 (12.8V) | 12.0V – 14.6V | 10.5V – 11.5V | >= 32V DC |
| 12V | AGM / Lead-Acid (12.0V) | 11.5V – 14.8V | 10.5V – 11.0V | >= 32V DC |
| 24V | LiFePO4 (25.6V) | 24.0V – 29.2V | 21.0V – 23.0V | >= 32V – 58V DC |
| 24V | AGM / Lead-Acid (24.0V) | 23.0V – 29.6V | 21.0V – 22.0V | >= 32V – 58V DC |
| 48V | LiFePO4 (51.2V) | 48.0V – 58.4V | 43.0V – 46.0V | >= 60V – 80V DC |
| 48V | AGM / Lead-Acid (48.0V) | 46.0V – 58.8V | 42.0V – 44.0V | >= 60V – 80V DC |
Note on 48V buses: A 58.4V LiFePO4 absorb voltage (and 58.8V AGM charging voltage) exceeds standard 58V-rated automotive/marine terminal fuses. Select overcurrent devices rated at >= 60V–80V DC for any 48V nominal input circuit.
Typical Ambient Enclosure Derating Profile
Exact knee temperatures and slopes vary by heatsink mass, potting, and airflow; verify the specific curve on the equipment datasheet before finalizing K_temp.
Enclosure Ambient (T_amb_max) |
Typical Thermal Region | Typical K_temp Range |
Engineering Action |
|---|---|---|---|
| <= 77°F to 104°F (25°C to 40°C) | Full-rated plateau | 1.00 |
No thermal derating required; verify vertical heatsink clearance. |
| 105°F to 122°F (41°C to 50°C) | Linear derating zone | 0.75 – 0.85 |
Upsize converter nominal rating using I_out_cont / K_temp. |
| 123°F to 140°F (51°C to 60°C) | Severe derating / foldback | 0.50 – 0.75 |
Add forced ventilation, relocate converter, or step up two frame sizes. |
| > 140°F (60°C) | Thermal shutdown threshold | < 0.50 or 0.00 |
Do not install without active cooling or relocation to a cooler zone. |
Step-by-Step Sizing Procedure
- Tally concurrent continuous output current (
I_out_cont). Sum the steady-state currents of all loads that can run simultaneously for 3 hours or more. Convert wattage-rated loads using the converter's regulated output voltage (I = P / V_out_nom). Separate non-concurrent intermittent loads unless they overlap during normal operation. - Determine peak transient startup demand (
I_out_peak). Add the locked-rotor or startup inrush current of the largest motor, compressor, or pump to the running current of all other active loads. Record the surge duration in milliseconds or seconds. - Apply ambient enclosure thermal derating (
K_temp). Measure or estimate the peak compartment temperature (T_amb_max), including heat rejected by adjacent inverters, chargers, or battery enclosures. ReadK_tempfrom the datasheet for your mounting orientation (horizontal mounting often derates earlier than vertical heatsink fins). CalculateI_out_rated_min = I_out_cont / K_tempand select the next standard converter frame at or aboveI_out_rated_min. - Verify transient overload behavior against the datasheet.
Confirm that
I_out_peakand its duration fit inside the selected converter's overload envelope. Check whether the unit uses constant-current limiting (voltage sags smoothly during surge) or hiccup protection (output cuts off and retries cyclically, which can lock out compressors or reset sensitive electronics). - Calculate worst-case input current (
I_in_max) atV_in_min. Use the battery bank's low-voltage cutoff (V_in_min) and the converter's minimum full-load efficiency (eff_min)—never nominal bus voltage—to computeI_in_max. If the converter will be loaded up to its full derated capacity, computeI_in_maxusing the converter's rated output power rather than the initial load tally. - Size input/output conductors and overcurrent protection.
- Continuous ampacity: Multiply continuous (>= 3h) input and output currents by
1.25when selecting conductor ampacity and fuse ratings. - Voltage drop: Calculate round-trip length (
2 * one_way_length) using 75°C copper resistivity (0.02097 ohm*mm^2/m). Keep critical load and primary converter feed circuits at<= 3%voltage drop (non-critical<= 10%), sizing by the larger of voltage drop or derated ampacity. - Terminal and cable limits: Honor 75°C terminal temperature ratings on converter lugs and breakers, and avoid undersized SAE J1128 automotive wire or copper-clad aluminum (CCA) cable.
- Fuse verification: Confirm fuse voltage rating
>=max charging voltage, interrupting rating (AIC)>=prospective battery fault current, and fuse amp rating<=conductor ampacity.
- Continuous ampacity: Multiply continuous (>= 3h) input and output currents by
Illustrative Worked Example (48V Bus to 12.5V Regulated Load)
Illustrative assumptions: A 48V nominal LiFePO4 system (V_in_min = 44.0V at LVD, V_in_max = 58.4V absorb) powers a regulated 12.5V load bus in an enclosed utility bay reaching 122°F (50°C). Continuous loads draw 20A (250W), and a water pump adds a 15A startup transient for 2 seconds (35A peak). The candidate converter datasheet specifies full output to 104°F (40°C), linear derating at 2.0% per °C (1.11% per °F) above 40°C, and eff_min = 0.90 at 44.0V.
- Thermal derating factor:
K_temp = 1.00 - (0.02 * (50°C - 40°C)) = 0.80 - Minimum nominal converter rating:
I_out_rated_min = 20A / 0.80 = 25.0A-> Select a30Anominal converter (30A * 0.80 = 24.0Acontinuous at50°C, leaving4.0Acontinuous margin). - Transient check:
35Apeak for2 secondsis117%of the30Anominal rating. Verify on the datasheet that the30Aunit sustains>= 35Afor>= 2 secondsat50°Cwithout entering hiccup shutdown. - Worst-case input current (at
20Acontinuous load and44.0Vcutoff):I_in_max = (12.5V * 20A) / (44.0V * 0.90) = 250W / 39.6V = 6.31A(If sizing the primary feed for the converter's full30Anameplate output at44.0V:(12.5V * 30A) / (44.0V * 0.90) = 9.47A.) - Primary wire and fuse sizing (for full
9.47Aconverter capability):- Minimum continuous fuse/conductor rating:
9.47A * 1.25 = 11.84A-> Select a15ADC fuse or breaker rated>= 60V DC(such as an80V DCrated fuse) with AIC exceeding battery short-circuit current. - For a
10 ft (3.05 m)one-way run (20 ft / 6.10 mround-trip),14 AWG (2.08 mm^2)copper at0.02097 ohm*mm^2/mhas0.0615 ohmround-trip resistance, yielding9.47A * 0.0615 ohm = 0.58Vdrop (1.32%of44.0V, well under the3%limit) and exceeds the15Afuse ampacity.
- Minimum continuous fuse/conductor rating:
Sign-Off Criteria
Verify every item below against the installed converter nameplate, datasheet, and measured circuit parameters before commissioning:
- Continuous & derated margin: Selected converter nominal current multiplied by datasheet
K_tempatT_amb_maxis>= I_out_cont. - Transient compatibility: Peak startup current (
I_out_peak) and duration fall within the converter's published surge/overload curve without triggering hiccup lockout. - Worst-case input sizing: Primary wire ampacity (
>= 1.25xcontinuousI_in_max) and overcurrent protection are calculated atV_in_minandeff_min, not nominal bus voltage. - Voltage drop: Round-trip primary and secondary voltage drops are
<= 3%for critical loads at worst-case current, using 75°C copper resistivity. - Overcurrent & terminal ratings: Input fuse voltage rating is
>=maximum bus charging voltage (e.g.,>= 60V–80V DCfor 48V LiFePO4 absorb at58.4V), AIC>=prospective fault current, fuse<=cable ampacity, and all terminations honor 75°C temperature limits. - Thermal clearance: Mounting orientation matches the datasheet derating curve and maintains required airflow clearance around heatsink fins.
Failure Modes
- Thermal foldback or cyclic shutdown in unventilated bays: Sizing a converter to its 77°F (25°C) nameplate rating inside a 115°F–130°F (46°C–54°C) locker causes output voltage to droop or shut off after 20–45 minutes of continuous load.
- Hiccup-mode lockouts on motor startup: Converters with aggressive hiccup current limiting shut down when compressor or pump inrush exceeds 105%–115% of nominal rating, causing rapid relay chatter and repeated brownouts.
- Input UVLO tripping under battery sag: Undersized primary cables add >3% voltage drop on top of battery sag at
V_in_min, pushing the converter's input terminals below its undervoltage lockout threshold even though battery resting voltage appears adequate. - Sustained DC arcing on under-rated fuses: Installing 58V-rated fuses on a 48V nominal LiFePO4 bus exposes the fuse to 58.4V absorb voltage, risking failure to extinguish an arc during a fault.
Part of Load-Side DC-DC Converters