On this page

In the DC Power Specs Glossary, SoH is tracked alongside State of Charge (SoC): SoC tells you how much energy is left in the current cycle, while SoH tells you how much total capacity the battery can still hold and how stiffly it holds voltage under load.


Core SoH Formulas & Indicators

Use plain-text ratios against the battery nameplate or commissioning baseline:

  • Capacity-Based SoH (SoH_C): SoH_C (%) = (C_measured_Ah / C_rated_Ah) x 100
  • Voltage Sag from Internal Resistance (R_internal): V_terminal = V_ocv - (I_load x R_internal) R_internal (ohms) = (V_1 - V_2) / (I_2 - I_1)
  • SoH-Adjusted Usable Energy (Wh_usable): Wh_usable = V_nominal x C_rated_Ah x (SoH_C / 100) x DoD_usable

Reference Thresholds by Chemistry (<=60V DC)

Parameter LiFePO4 (12.8V / 25.6V / 51.2V) AGM / Sealed Lead-Acid (12.0V / 24.0V / 48.0V)
New Baseline (100% SoH) 100% rated Ah; absorb 14.2–14.6V / 28.4–29.2V / 56.8–58.4V 100% rated Ah (typically C20 rate); absorb per nameplate
Usable DoD Window 80–90% (default 85% design baseline) 50% (exceeding 50% accelerates capacity fade)
Serviceable Aging (81–99% SoH) Minimal voltage sag; derate runtime by SoH_C Rising R_internal; monitor voltage sag under inverter loads
End-of-Life Threshold (<=80% SoH) Capacity fade accelerates; replace for primary cyclic duty Rapid sulfation and high sag; replace before deep-cycle failure
Temperature Caveat Flag charging at <=+5°C (41°F) for BMS limits; hard block <=0°C (32°F) unless self-heated Cold reduces temporary deliverable Ah; does not equal permanent SoH loss unless frozen

Illustrative Runtime Derating Example

  • Illustrative assumptions: A 12.8V nominal, 100Ah LiFePO4 battery (85% usable DoD) has aged to 80% SoH_C.
  • New usable energy: 12.8V x 100Ah x 0.85 = 1,088 Wh (85Ah).
  • Aged usable energy at 80% SoH: 12.8V x 100Ah x 0.80 x 0.85 = 870.4 Wh (68Ah).
  • Impedance impact: If R_internal doubles from 5 mOhm (0.005 ohm) to 10 mOhm (0.010 ohm), a 100A DC draw (typical of a ~1,000–1,100W AC inverter load on North America 120V/60Hz or UK/AU 230V/50Hz outputs) increases terminal voltage sag from 0.5V to 1.0V, tripping V_min earlier during high-wattage surges.

Job-Specific Steps to Measure SoH

  1. Record Nameplate & Baseline Limits Check the battery nameplate for rated capacity (Ah and C-rate, such as C20 for AGM or C5/C1 for LiFePO4), nominal voltage, absorb/float voltages, maximum continuous discharge current, and BMS low-temperature charge cutoff (verify if the BMS locks out charging at <=+5°C / 41°F or <=0°C / 32°F).
  2. Stabilize Temperature & Full-Charge State Perform capacity testing at ambient 20–25°C (68–77°F) so cold-induced resistance does not skew the reading. Charge to the nameplate absorb voltage (14.2–14.6V / 28.4–29.2V / 56.8–58.4V for LiFePO4) until tail current drops per manufacturer spec, allowing passive cell balancing to complete. Rest 30–60 minutes.
  3. Run a Controlled Capacity Discharge (SoH_C) Using a calibrated DC shunt or battery analyzer, discharge at a steady current matching the nameplate test rate down to the rated discharge cutoff voltage (or BMS cutoff). Record total Ah delivered and compute SoH_C = (C_measured_Ah / C_rated_Ah) x 100.
  4. Measure Load-Step Internal Resistance (R_internal) Apply two steady DC load steps (I_1, then I_2) for 10–15 seconds each and record stabilized terminal voltages (V_1, V_2) directly at the battery posts (excluding cable and fuse drop). Calculate R_internal = (V_1 - V_2) / (I_2 - I_1) and compare against the new baseline or parallel sibling batteries.

Sign-Off Criteria

A battery or <=60V DC bank passes an SoH inspection for continued service only when all of the following hold:

  • Capacity: Measured SoH_C is >80% of nameplate Ah, and the adjusted Wh_usable meets the system's required autonomy.
  • Voltage Stability: Under worst-case continuous DC current plus inverter surge at low SoC, V_terminal remains above the inverter and BMS V_min cutoff.
  • Parallel Bank Matching: In multi-battery parallel banks, measured SoH_C and R_internal are matched across all strings so current sharing stays balanced within manufacturer tolerances.
  • Physical & BMS Integrity: No swollen cases, vented electrolyte, terminal overheating, or unexplained BMS cell-imbalance/over-voltage/under-voltage trips.

Real Failure Modes

  • Coulomb Counter Drift (False 100% SoC): Battery monitors programmed with the original 100% nameplate Ah continue reporting 100% SoC on a faded 75% SoH battery. The system unexpectedly hits V_min and drops the 120V/60Hz (or 230V/50Hz) inverter load while the display still shows 20–25% SoC remaining.
  • Impedance-Induced Premature Cutoff: Sulfated AGM packs or aged LiFePO4 cells can still hold >80% capacity at low C20 discharge rates, yet exhibit high R_internal. Heavy DC draws cause steep I x R sag that trips inverter low-voltage alarms immediately upon load start.
  • Parallel String Imbalance: Connecting a new 100% SoH battery in parallel with an aged 75% SoH battery forces the lower-resistance new unit to supply and absorb most of the current, accelerating its wear while the high-resistance old unit sits underutilized.
  • Cold-Charge Lithium Plating: Charging a LiFePO4 battery at <=0°C (32°F) without an active self-heating system—or ignoring a <=+5°C (41°F) BMS warning threshold—plates metallic lithium onto the anode, causing permanent, irreversible SoH_C loss and internal short risk.