On this page

For sizing solar arrays, alternators, or AC chargers, do not use cell-level coulombic efficiency (98%–99% for LiFePO4) as your system number. Choose battery-only RTE (typically 92%–96% for LiFePO4; 75%–85% for AGM/lead-acid) only when measuring directly at the DC battery terminals, and use end-to-end system RTE (65%–88% depending on topology, inverter tare draw, and wire drop) when sizing input energy from PV, vehicle charging, or AC shore power.

This Glossary reference covers the cumulative electrochemical, resistive, and conversion losses across 12V, 24V, and 48V DC systems (strictly <=60V DC on the battery bus) and portable power stations.


Conditions That Change Round-Trip Efficiency

  • Battery chemistry and charge stage: LiFePO4 (12.8V / 25.6V / 51.2V nominal, factory-integrated BMS) maintains low internal resistance and flat voltage across its 80%–90% usable depth of discharge (85% default), keeping electrochemical RTE at 92%–96%. AGM/lead-acid (12.0V / 24.0V / 48.0V nominal, 50% usable DoD) loses 15%–25% of input Wh to higher internal resistance, Peukert losses under load, and prolonged absorption/tail-current heating.
  • Inverter conversion and idle tare draw: Enabling a 120V/60Hz (North America) or 230V/50Hz (UK/AU) AC inverter introduces both load-dependent conversion loss (typically 7%–15% at rated mid-load) and continuous no-load tare draw (typically 10W–40W). Light, continuous AC loads suffer the steepest RTE penalty because tare Wh rivals or exceeds useful load Wh.
  • System voltage and DC conductor loss (I^2 * R): Power loss in DC cabling scales with the square of current over the round-trip length (2 * one-way length). At 12.8V nominal, a 1,000W load draws ~4x the current of a 51.2V bank, generating ~16x the resistive heat loss in identical wire gauge and length.
  • C-rate and component resistance: High charge or discharge rates increase I^2 * R heating across internal cell impedance, BMS MOSFETs, shunts, fuses, and terminal lugs.
  • Cold-weather charging and self-heating: Low temperatures raise internal resistance, depressing discharge voltage. At <=+5°C (41°F), verify the battery BMS minimum charge temperature (some commercial packs lock out charging at +5°C). Charging is hard-blocked at <=0°C (32°F) unless the pack is self-heated; internal heating elements consume incoming or stored Wh before net charge accumulates, lowering effective system RTE.

Reference Specifications and Loss Stages

The table below separates electrochemical battery RTE from conversion and distribution stage efficiencies for <=60V DC systems.

Stage / Parameter LiFePO4 (BMS-Protected) AGM / Sealed Lead-Acid Notes / Nameplate Check
Nominal / Absorb Voltage (12V class) 12.8V / 14.2–14.6V 12.0V / 14.4–14.7V Verify charger absorb/float profile on battery datasheet
Nominal / Absorb Voltage (24V class) 25.6V / 28.4–29.2V 24.0V / 28.8–29.4V Verify charger absorb/float profile on battery datasheet
Nominal / Absorb Voltage (48V class) 51.2V / 56.8–58.4V 48.0V / <=60.0V max Keep all DC bus voltages <=60V DC
Usable Depth of Discharge (DoD) 80%–90% (85% default) 50% Governs usable Wh, not RTE directly
Battery-Only Wh RTE (eta_batt) 92%–96% 75%–85% Measured at battery terminals at moderate C-rate (<=0.2C)
MPPT Charge Controller (eta_mppt) 94%–98% 94%–98% Check controller efficiency curve; cold PV Voc must stay <=150V DC
AC-to-DC Charger (eta_chg) 85%–92% 85%–92% Applies to 120V/60Hz (NA) or 230V/50Hz (UK/AU) shore chargers
DC-to-AC Inverter (eta_inv) 85%–93% (excl. tare) 85%–93% (excl. tare) Check nameplate continuous W, efficiency curve, and no-load W
DC Wiring Drop (eta_wire) 97%–99% (critical <=3%) 97%–99% (critical <=3%) Use round-trip length; 75°C Cu resistivity 0.02097 ohm*mm^2/m

Typical System RTE by Topology (Illustrative Ranges)

System Topology Formula Typical LiFePO4 System RTE Typical AGM System RTE
Solar -> MPPT -> Battery -> DC Load eta_mppt * eta_batt * eta_wire_in * eta_wire_out 82%–90% 67%–79%
Solar -> MPPT -> Battery -> AC Inverter -> Load eta_mppt * eta_batt * eta_wire * eta_inv_net 70%–82% 57%–72%
AC Charger -> Battery -> AC Inverter -> Load eta_chg * eta_batt * eta_wire * eta_inv_net 64%–78% 52%–68%
Portable Power Station (AC in -> AC out) E_ac_out / E_ac_in (includes tare + cooling fans) 72%–84% N/A

Note: eta_inv_net drops below the table ranges whenever inverter idle tare draw exceeds ~10% of the active load.


Step-by-Step System RTE Calculation

Use these steps to calculate required charging energy (E_in) from a known daily load (E_load), or to verify measured system RTE.

1. Gather Nameplate and Circuit Inputs

  1. Read battery nominal voltage and capacity (V_nom, Ah, or Wh), BMS temperature limits, and chemistry from the battery nameplate.
  2. Read MPPT or AC charger efficiency (eta_chg or eta_mppt) and inverter efficiency (eta_inv) plus no-load tare power (P_tare, in W) from each device manual.
  3. Measure one-way DC cable runs in feet (or meters) and double them for round-trip length: L_rt_m = 2 * L_oneway_ft * 0.3048

2. Compute DC Wiring Efficiency (eta_wire)

Calculate DC round-trip resistance using 75°C copper resistivity (0.02097 ohm*mm^2/m):

  • R_rt (ohm) = (0.02097 * L_rt_m) / Area_mm2
  • V_drop (V) = I_dc * R_rt
  • eta_wire = 1 - (V_drop / V_nom) (keep critical DC circuits <=3% drop, i.e., eta_wire >= 0.97).

3. Account for Inverter Tare Draw (E_tare)

If an AC inverter (120V/60Hz NA or 230V/50Hz UK/AU) stays powered on for H_on hours per day:

  • E_tare (Wh/day) = P_tare (W) * H_on (h/day)
  • E_batt_out (Wh/day) = (E_ac_load / eta_inv) + E_tare

4. Compute Total Required Charging Energy (E_in) and System RTE

  • E_in (Wh/day) = E_batt_out / (eta_batt * eta_chg_or_mppt * eta_wire_total)
  • System RTE (%) = (E_ac_load / E_in) * 100 (or (E_dc_load / E_in) * 100 for DC-only loads).

Worked Example (Illustrative Assumptions)

Assume a 25.6V nominal LiFePO4 bank (eta_batt = 0.94) feeding a 120V/60Hz AC load of E_ac_load = 1,200 Wh/day (e.g., 100W average for 12h, inverter left on 24h).

  • Assumed hardware specs: MPPT efficiency eta_mppt = 0.96; inverter conversion efficiency eta_inv = 0.90; inverter idle tare P_tare = 18W for 24h; combined charge + discharge DC wiring efficiency eta_wire_total = 0.98 (6 AWG / 13.3 mm² copper, short bus run).
  • Step 1 (Tare energy): E_tare = 18W * 24h = 432 Wh/day.
  • Step 2 (Battery DC output needed): E_batt_out = (1,200 / 0.90) + 432 = 1,333 + 432 = 1,765 Wh/day.
  • Step 3 (Total MPPT input needed): E_in = 1,765 / (0.94 * 0.96 * 0.98) = 1,765 / 0.884 = 1,997 Wh/day.
  • Step 4 (System RTE): System RTE = (1,200 / 1,997) * 100 = 60.1%.

Notice that even with a 94% efficient LiFePO4 battery and 90% efficient inverter, 24-hour idle tare draw pulls end-to-end system RTE down to 60.1%. Turning the inverter off when not needed (e.g., H_on = 12h, E_tare = 216 Wh/day) reduces E_in to 1,752 Wh/day and raises system RTE to 68.5%.


Sign-Off Criteria

Before signing off on an energy budget or commissioning measurement:

  • Same-SoC test boundaries: Measure field RTE only across a full cycle starting and ending at the exact same resting open-circuit state of charge (or full-charge float/absorb termination) at stable ambient temperature (20°C–25°C / 68°F–77°F).
  • Meter placement: Log E_in at the charger/MPPT input (or AC wall meter for portable power stations) and E_out at the load output terminals; do not mix coulomb-counter Ah with Wh without accounting for charge/discharge voltage difference.
  • Thermal and drop compliance: Confirm DC voltage drop is <=3% on critical inverter/charger circuits (<=10% on non-critical DC loads) and verify battery cell temperature stays above the BMS charge threshold (>+5°C / 41°F check; >0°C / 32°F hard floor unless self-heating).
  • Portable power station sizing: Verify usable Wh after DC/AC conversion losses and tare draw against nameplate continuous W, surge W, and DC port current limits (do not assume a universal 120W car-socket limit).

Common Failure Modes

  • Sizing solar/charging from Ah instead of Wh: Assuming 100 Ah in = 100 Ah out ignores the voltage gap between charging (e.g., 14.4V–29.2V–58.4V absorb) and discharging (12.8V–25.6V–51.2V nominal or lower under load), overestimating usable Wh by 10%–25%.
  • Ignoring inverter tare on small continuous loads: Leaving a large 120V/60Hz or 230V/50Hz inverter idling overnight to power a 15W–30W router or DC-capable appliance can consume more energy in tare heat than the load itself, cutting effective RTE below 50%.
  • Counting AGM absorption tail as usable storage: During the final 15%–20% of an AGM charge cycle, charge acceptance drops sharply; most charger Wh goes into heat and internal gas recombination rather than recoverable capacity.
  • Hidden I^2 * R losses in undersized or CCA cables: Copper-clad aluminum (CCA) or undersized SAE J1128 conductors on high-current 12V/24V runs create excessive voltage drop, tripping inverter low-voltage cutoffs early and converting stored battery Wh into cable heat.
  • Unaccounted self-heating draw in cold climates: In sub-freezing installations (<=0°C / 32°F), self-heated LiFePO4 packs divert incoming solar or alternator energy to internal heater pads before cell charging begins, causing actual harvested Wh to fall well below warm-weather RTE estimates.