On this page
Four operating conditions change how severely LRA stresses the DC bus:
- Motor and drive topology: Direct-on-line AC induction motors and brushed DC motors draw full LRA; soft-start kits, variable-frequency drives (VFDs), and brushless DC (BLDC) controllers ramp current to avoid the full locked-rotor spike.
- Mechanical load and head pressure: High refrigerant head pressure (such as restarting an air conditioner before pressure equalizes) or heavy mechanical torque extends the time required to reach operating speed.
- Battery bank state of charge and temperature: Low state of charge or cold electrolyte increases internal voltage sag, pushing DC current higher at the inverter input as it tries to maintain AC output.
- System nominal voltage: Moving from a 12V to a 24V or 48V DC bus cuts the DC-side surge current proportionally for the same AC LRA load.
This reference is part of the Glossary for DC engineering mechanisms.
Physics and Electrical Behavior
When power is first applied to a stationary motor, rotor speed is zero and magnetic flux cutting the armature or rotor bars produces zero opposing voltage:
At t = 0 (rotor stationary):
Back-EMF = 0 V
I_LRA = V_supply / Z_winding (AC motor, where Z_winding is locked-rotor impedance)
I_LRA = V_DC / R_armature (DC motor, where R_armature is DC winding resistance)
As the rotor accelerates, rotation induces back-EMF that opposes the supply voltage, dropping current down to running levels:
At operating speed:
I_run = (V_supply - Back-EMF) / Z_winding
For an AC motor powered by a DC-to-AC inverter, the AC-side LRA translates into a much larger DC-side current surge because of the voltage step-up ratio, inverter efficiency (eta), and low-voltage bus sag (V_DC_min):
VA_LRA = V_AC * I_LRA
I_DC_surge = VA_LRA / (V_DC_min * eta)
Locked-rotor power factor is typically low (inductive), meaning apparent power (VA_LRA) governs the peak current the inverter switches and DC bus must supply, even if real power in watts is lower than VA_LRA.
Illustrative example (assumed nameplate and operating parameters):
Assume a 120V/60Hz RV air conditioner compressor with a nameplate LRA = 45 A, an inverter efficiency of eta = 0.85, and a battery bank sagging to V_DC_min during the surge:
VA_LRA = 120 V * 45 A = 5,400 VA- On a 12.8V LiFePO4 bank sagging to
11.5 V:I_DC_surge = 5,400 / (11.5 * 0.85) = 552 A - On a 25.6V LiFePO4 bank sagging to
23.0 V:I_DC_surge = 5,400 / (23.0 * 0.85) = 276 A - On a 51.2V LiFePO4 bank sagging to
46.0 V:I_DC_surge = 5,400 / (46.0 * 0.85) = 138 A
On a 230V/50Hz UK/AU appliance with the same 5,400 VA locked-rotor demand, the AC nameplate LRA would read 23.5 A (5,400 VA / 230 V), yet the DC-side surge current on the 12V, 24V, or 48V battery bus remains identical.
Specifications and Duration Behavior
| Motor / Load Type | Typical LRA Multiplier (vs. RLA/FLA) | Typical Surge Duration | Primary DC-Side Bottleneck |
|---|---|---|---|
| Direct-on-line AC induction compressor (120V/60Hz or 230V/50Hz) | 4x to 7x RLA | 100 ms to 2,000 ms | Inverter surge VA limit, BMS peak cutoff, DC voltage sag |
| AC induction compressor with soft-start / VFD | 1.2x to 2x RLA | Ramped over 500 ms to 3,000 ms | Continuous inverter rating and thermal headroom |
| Brushed DC motor (12V/24V/48V pump, winch, windlass) | 3x to 6x continuous rating | 50 ms to 500 ms (longer if stalled) | DC fuse time-current curve, cable voltage drop, BMS peak |
| BLDC / variable-speed DC compressor (12V/24V fridge) | 1.1x to 1.5x running current | Ramped over 1,000 ms to 3,000 ms | Minimum startup voltage threshold at compressor controller |
Always verify exact LRA, RLA/FLA, rated voltage, and frequency (60 Hz or 50 Hz) on the equipment nameplate rather than relying on generic multipliers.
Verification Steps (DC Side)
- Read the equipment nameplate: Record
LRA(in amps), rated supply voltage (120V/60Hz,230V/50Hz, or12V/24V/48VDC), and continuousRLA/FLA. If an AC motor uses an aftermarket soft-start module, use the reduced starting current specified by the soft-start datasheet. - Compute worst-case DC surge current: For AC loads on an inverter, calculate
I_DC_surge = (V_AC * I_LRA) / (V_DC_min * eta)using the inverter's low-voltage cutoff (V_min) and surge efficiency. For direct DC motors, use the nameplate stall/inrush current directly. - Check inverter and BMS peak duration limits: Confirm the inverter's surge rating (in VA and milliseconds/seconds) exceeds
VA_LRAfor at least 1–2 seconds, and confirm the battery BMS peak discharge rating exceedsI_DC_surgefor the same window without triggering instantaneous overcurrent protection. - Verify DC fuse time-current curve and ratings: Check the fuse manufacturer's time-current curve at
I_DC_surgeto verify it does not melt within the expected startup duration (typically 0.5–2 s). Ensure fuse ampacity does not exceed cable ampacity (sized at>= 1.25xcontinuous>= 3 hload), fuse voltage rating is>=maximum charging voltage (for example,58.4 Vabsorb on a 48V LiFePO4 bank exceeds 58V-rated terminal fuses), and fuse Ampere Interrupting Capacity (AIC) exceeds battery bank prospective fault current. - Check transient voltage drop on DC cabling: Using round-trip cable length (
2 * one-waydistance in meters or feet) and 75°C copper resistivity (0.02097 ohm·mm²/m), calculate voltage drop atI_DC_surgealongside continuous critical-circuit limits (<= 3%drop). Confirm that battery voltage minus cable drop underI_DC_surgestays above the inverter or DC motor low-voltage disconnect (V_min).
Sign-Off Criteria
- Nameplate
LRA(or soft-started inrush current) and supply voltage/frequency are documented. - Calculated
I_DC_surgeatV_minis below both the inverter surge limit and the battery BMS peak discharge trip threshold for at least 2 seconds. - Selected DC overcurrent device holds
I_DC_surgewithout opening on the time-current curve for the full motor acceleration period, while remaining<=derated cable ampacity,>=max system charge voltage, and>=prospective fault current AIC. - DC terminal voltage at the inverter or motor during LRA remains above
V_minafter accounting for round-trip copper resistance and battery internal sag.
Failure Modes
- Inverter Low-Voltage Disconnect (LVD) on startup: Undersized DC cables, loose lugs, or cold/depleted batteries cause terminal voltage to drop below
V_minduring the first 100–500 ms of LRA, shutting down the inverter before the rotor accelerates. - BMS instantaneous overcurrent lockout: High
I_DC_surgefrom an AC compressor on a single LiFePO4 battery triggers the BMS short-circuit or peak discharge MOSFET trip, cutting power to the entire DC bus until the BMS resets. - Nuisance fuse clearing or thermal fatigue: Sizing a fast-acting fuse solely to continuous RLA causes it to open during repeated motor starts, or heats the fuse element near its melting threshold across multiple cycles.
- Extended LRA from mechanical stall or un-equalized head pressure: Restarting an AC compressor immediately after shutdown forces the motor to push against high refrigerant head pressure, holding LRA longer than 2 seconds until the motor thermal overload opens, the inverter faults, or the DC fuse clears.
Part of DC Power Glossary