Thermostatic and intermittent appliances (such as DC compressor refrigerators, diesel heaters, and water pumps) consume far less daily energy than their continuous wattage rating implies because their motors or heating elements turn off between active cycles. However, the actual duty cycle shifts significantly with ambient temperature, thermal insulation, thermostat setpoint, door-opening frequency, supply voltage, and mechanical demand.

For related system-level definitions, see the DC Power Glossary.


Core Formulas (Plain Text)

Use these equations to convert between active power, cycle timing, and daily battery demand on 12V, 24V, and 48V DC systems (strictly <=60V DC bus):

Duty_Cycle (%) = (Active_On_Time / Total_Cycle_Period) x 100

Effective_Hours_Per_Day = 24 x (Duty_Cycle_% / 100)

Daily_DC_Wh = Active_DC_Watts x Effective_Hours_Per_Day

Daily_DC_Ah = Daily_DC_Wh / V_nominal

Note on V_nominal: Use 12.8V, 25.6V, or 51.2V for LiFePO4 banks (default 85% usable DoD, range 80–90%), and 12.0V, 24.0V, or 48.0V for AGM/lead-acid banks (50% usable DoD).

Cycling AC Loads on an Inverter

When a cycling AC appliance (120V/60Hz North America; 230V/50Hz UK/AU) runs off an inverter that stays powered on continuously, you must add the inverter's off-cycle idle tare draw to the active energy:

Off_Hours_Per_Day = 24 - Effective_Hours_Per_Day

Daily_DC_Wh_With_Inverter = (Active_AC_Watts x Effective_Hours_Per_Day / Inverter_Efficiency)
                          + (Inverter_Idle_Watts x Off_Hours_Per_Day)

Typical Duty Cycle Ranges by Load Class

The values below are illustrative engineering assumptions for preliminary budgeting. Always verify active watts, startup surge, and cycle limits on the equipment nameplate and manual.

Load Type Control Mechanism Typical 24h Duty Cycle (Illustrative) Primary Variable That Shifts Duty Cycle Sizing Rule (Wire & Fuse vs. Energy)
DC Compressor Fridge / Freezer Thermostatic 25%–50% at 70–75°F (21–24°C); 60%–85% at 95–105°F (35–41°C) Ambient air temperature, cabinet ventilation, door openings Energy uses duty cycle; wire/fuse uses full running + compressor startup surge
Diesel Air / Hydronic Heater Thermostatic + Glow-plug start 100% for 2–5 min startup surge; 20%–60% steady fan/pump Cabin heat loss, outdoor temperature, setpoint Wire/fuse sized for 100% glow-plug surge (<=3% voltage drop)
Pressurized Water Pump Pressure-switch intermittent 1%–5% (15–70 min/day) Faucet/shower flow duration Energy is minimal; wire/fuse sized for full active pump + locked-rotor amps
Bilge / Transfer Pump Float-switch intermittent <1% dry bilge; up to 100% in heavy leak Water ingress rate Must be wired and fused for 100% continuous duty (>=1.25x ampacity)
AC Microwave / Induction (120V/60Hz or 230V/50Hz) Manual intermittent 1%–4% (15–60 min/day) Cooking duration Energy is modest; inverter, DC cable, and fuse sized for 100% peak + surge
CPAP / 24-7 Telemetry Fixed block or continuous 33% (8h/day CPAP); 100% (24h/day router/BMS) Scheduled runtime window Any load running >=3 hours continuously requires >=1.25x conductor derating

Step-by-Step Duty Cycle Sizing & Energy Calculation

  1. Read the nameplate and manual ratings: Record active running watts (W) or amps (A) at nominal voltage, startup/locked-rotor surge amps, and any manufacturer-mandated maximum on-time (common on intermittent-duty winches, thrusters, and macerator pumps).
  2. Determine the active runtime fraction: Measure a full 24-hour period with a DC shunt or clamp-on energy meter at your expected operating temperature, or time multiple consecutive on/off cycles (Active_On_Time / Total_Cycle_Period).
  3. Compute daily Wh and Ah: Multiply active watts by Effective_Hours_Per_Day. For AC loads on an always-on inverter, divide active AC Wh by inverter efficiency (typically 0.85–0.92) and add Inverter_Idle_Watts x Off_Hours_Per_Day.
  4. Size conductors and protection for 100% peak, not the average: Calculate round-trip wire length (2 x one-way feet or meters) and size AWG (mm²) for the larger of <=3% voltage drop (critical DC circuits such as compressor fridges and heaters) or <=10% (non-critical), and derated ampacity (>=1.25x continuous current if any single active cycle lasts >=3 hours). Verify terminal temperature ratings (typically 75°C / 167°F).

Worked Example: 12V DC Compressor Fridge (Illustrative)

  • Assumptions: 12.8V LiFePO4 system; fridge nameplate draws 48W (3.75A at 12.8V) while running, with an 8–12A compressor startup surge.
  • Moderate ambient (77°F / 25°C) at 35% duty cycle:
    • Effective_Hours_Per_Day = 24 x 0.35 = 8.4 hours
    • Daily_DC_Wh = 48W x 8.4h = 403.2 Wh/day
    • Daily_DC_Ah = 403.2 Wh / 12.8V = 31.5 Ah/day
    • Comparison: Assuming 100% continuous runtime (48W x 24h) yields 1,152 Wh/day (90 Ah/day)—a 2.86x overestimate of battery demand.
  • Hot cabin ambient (100°F / 38°C) at 70% duty cycle:
    • Effective_Hours_Per_Day = 24 x 0.70 = 16.8 hours
    • Daily_DC_Wh = 48W x 16.8h = 806.4 Wh/day (63.0 Ah/day)
  • Circuit sizing: Regardless of whether the fridge runs 35% or 70% of the day, size the DC branch cable (e.g., 12 AWG / 3.31 mm² or larger depending on round-trip distance) and fuse for the full 3.75A active draw and 8–12A startup surge at <=3% voltage drop.

Sign-Off Criteria

  • Worst-case ambient accounted for: Daily Wh and Ah calculations reflect peak seasonal cabin/ambient temperature, not 70°F (21°C) bench conditions alone.
  • Inverter tare included for AC loads: Any cycling 120V/60Hz or 230V/50Hz load powered by an inverter includes off-cycle idle draw across Off_Hours_Per_Day, or uses a verified load-sensing sleep mode compatible with the appliance thermostat.
  • Zero average-current downsizing: All conductors, 75°C-rated terminals, fuses, and BMS discharge limits are sized for 100% active running current and startup surge.
  • Battery DoD margin verified: Total daily duty-cycled Wh fits within usable battery capacity (85% default DoD for LiFePO4; 50% DoD for AGM/lead-acid) without triggering low-voltage disconnect during motor startup surges.

Common Failure Modes

  • Sizing wire and fuses to duty-cycled average current: Sizing a water pump or compressor fridge circuit for its 2–30 Ah/day average instead of its 10–20A active/surge draw causes >3% round-trip voltage drop, low-voltage compressor lockouts on startup, and nuisance fuse trips.
  • Ignoring inverter idle tare on cycling AC loads: Running a small 120V/60Hz (or 230V/50Hz) AC dorm fridge on a 1,500W–2,000W inverter that draws 20W at idle consumes 20W x 16h = 320 Wh/day in tare losses alone during off-cycles—often matching or exceeding the fridge's actual cooling energy.
  • Using mild-weather duty cycles for summer sizing: An unventilated RV or boat cabin reaching 95–105°F (35–41°C) can double or triple refrigerator duty cycle, exhausting a battery bank sized for 70°F (21°C) room-temperature estimates.
  • Exceeding intermittent motor thermal limits: Operating an intermittent-duty motor (such as a windlass, thruster, or high-pressure washdown pump) beyond its nameplate on/off cycle (for example, 2 min on / 10 min off) overheats windings and trips thermal breakers even when the battery bank has ample state of charge.