On this page
Only use 20 °C (68 °F) resistivity for brief, intermittent loads in cool ambient air or when checking cold-start resistance; using 20 °C figures for continuous DC runs underpredicts both voltage drop and I²R conductor heating. See the DC Power Specs Glossary for related conductor and circuit definitions.
Core Mechanism and Plain-Text Formulas
As copper heats up, lattice vibrations scatter conduction electrons more frequently, increasing resistance linearly across normal DC operating temperatures:
rho_T = rho_20 * [1 + alpha_20 * (T - 20)]
Where:
rho_T= copper resistivity at conductor temperatureT(ohm·mm²/m)rho_20= 0.017241 ohm·mm²/m at 20 °C (68 °F)alpha_20= 0.00393 per °C (temperature coefficient of resistance for annealed copper)T= operating conductor temperature in °C
For any DC circuit using round-trip wire length (2 * L_one_way):
R_T = rho_T * (2 * L_one_way_m) / A_mm2
V_drop = I * R_T
P_heat = I^2 * R_T
Because P_heat scales with I^2 * R_T, a 21.6% rise in copper resistance between 20 °C and 75 °C produces 21.6% more watts of heat in the cable at the exact same current.
Copper Resistivity by Operating Temperature
| Conductor Temp (°C) | Conductor Temp (°F) | Resistivity (ohm·mm²/m) | Multiplier vs. 20 °C | Typical DC System Context |
|---|---|---|---|---|
| 0 °C | 32 °F | 0.01589 | 0.921x (-7.9%) | Cold-weather ambient; lower wire loss, but LiFePO4 charging must be blocked unless self-heated |
| 20 °C | 68 °F | 0.01724 | 1.000x (Baseline) | Reference lab tables only; underestimates loaded DC circuits |
| 60 °C | 140 °F | 0.01995 | 1.157x (+15.7%) | Lightly loaded runs or older 60 °C-rated terminal limits |
| 75 °C | 167 °F | 0.02097 | 1.216x (+21.6%) | Standard DC sizing baseline; matches 75 °C breaker, lug, and inverter terminal ratings |
| 90 °C | 194 °F | 0.02198 | 1.275x (+27.5%) | High-ambient compartments (derate ampacity; still honor 75 °C terminal limits) |
| 105 °C | 221 °F | 0.02300 | 1.334x (+33.4%) | Marine/UL 1426 insulation ceiling in engine spaces (do not run terminations at 105 °C) |
Material and Terminal Constraints
- 75 °C terminal ceiling: Even when a cable jacket is rated for 90 °C (194 °F) or 105 °C (221 °F), the connected fuse holder, DC breaker, shunt, or inverter lug is typically rated for 75 °C (167 °F) on its nameplate. Conductor sizing must keep steady-state conductor temperature at or below the lowest-rated termination in the circuit.
- Copper-clad aluminum (CCA) trap: CCA has roughly 60% higher resistivity than pure annealed copper and a different thermal expansion profile; never apply the 0.02097 ohm·mm²/m copper constant to CCA cable.
- SAE J1128 automotive wire trap: Thin-wall SAE J1128 wire often carries high conductor temperature ratings without marine/UL continuous ampacity derating or thick abrasion insulation; verify actual cross-sectional area (
mm²/ AWG) and continuous thermal limits rather than relying on peak automotive ratings.
Job-Specific Sizing Steps
- Confirm nameplate limits: Check the equipment nameplate or manual for the lowest terminal temperature rating (typically 75 °C / 167 °F) and the circuit's voltage-drop limit (<=3% for critical loads such as inverters, MPPT inputs, and navigation/CPAP DC supplies; <=10% for non-critical loads).
- Calculate round-trip length: Measure one-way cable distance from source to load and double it (
L_total = 2 * L_one_way). - Compute resistance at 75 °C: Use
rho_75 = 0.02097 ohm·mm²/mand the conductor cross-sectional area (mm²) for the candidate AWG size. - Verify both voltage drop and I²R heating: Calculate
V_drop = I * R_75andP_heat = I^2 * R_75. IfV_dropexceeds the circuit limit, step up to the next larger AWG. - Check derated ampacity: Ensure the cable's ambient- and bundle-derated ampacity is at least 1.25x the continuous load (>=3 hours) and that the fuse rating does not exceed the cable ampacity.
Illustrative Example: 12.8V LiFePO4 Circuit (20 °C vs. 75 °C)
Illustrative assumptions: 12.8V nominal LiFePO4 bus, 45A continuous load, 10 ft (3.05 m) one-way run (20 ft / 6.10 m round-trip), 6 AWG annealed copper (13.3 mm²).
- At 20 °C (68 °F):
R_20 = 0.017241 * 6.10 / 13.3 = 0.00791 ohmV_drop_20 = 45A * 0.00791 ohm = 0.356 V(2.78% of 12.8V — appears to pass <=3%)P_heat_20 = 45^2 * 0.00791 = 16.0 W
- At 75 °C (167 °F):
R_75 = 0.02097 * 6.10 / 13.3 = 0.00962 ohmV_drop_75 = 45A * 0.00962 ohm = 0.433 V(3.38% of 12.8V — fails <=3% critical limit)P_heat_75 = 45^2 * 0.00962 = 19.5 W(+3.5 W additional heat)
- Corrective action (4 AWG, 21.15 mm² at 75 °C):
R_75 = 0.02097 * 6.10 / 21.15 = 0.00605 ohmV_drop_75 = 45A * 0.00605 ohm = 0.272 V(2.13% — passes <=3%)P_heat_75 = 45^2 * 0.00605 = 12.3 W
Sign-Off Criteria
- Voltage-drop calculations use 0.02097 ohm·mm²/m (75 °C) and round-trip length (
2 * L_one_way). - Calculated 75 °C voltage drop is <=3% for critical DC circuits or <=10% for non-critical DC circuits at maximum continuous current.
- Selected conductor size meets or exceeds the larger requirement of voltage drop and 1.25x continuous-load (>=3h) derated ampacity.
- Steady-state conductor temperature at full load stays within the lowest connected terminal temperature rating (usually 75 °C / 167 °F).
Real Failure Modes
- I²R thermal runaway in bundled or enclosed runs: Bundled cables dissipate heat poorly. As conductor temperature climbs, resistance rises 0.393% per °C, which increases
I^2 * Rheat output, driving temperature higher until insulation softens or adjacent cables derate. - 20 °C table under-sizing on low-voltage buses: On 12V/12.8V systems, a 21.6% resistance jump at 75 °C pushes borderline 2.7%–2.9% runs past the 3% threshold, triggering premature inverter low-voltage cutoffs under heavy load.
- Terminal overheating behind high-temp insulation: Running 105 °C-rated marine cable at its 105 °C ampacity limit conducts heat directly into 75 °C-rated breaker lugs or plastic fuse blocks, causing lug oxidation, higher contact resistance, and melted housings.
- Hotspot compounding at poor crimps: A loose or corroded crimp adds localized resistance; as
I^2 * Rheats the lug, the adjacent copper strand temperature spikes well above 75 °C, accelerating oxidation and voltage collapse.
Part of DC Power Glossary