Usable energy also depends on chemistry depth of discharge (DoD), operating temperature, and conversion losses. LiFePO4 packs typically allow 80–90% usable DoD (85% default), whereas AGM and sealed lead-acid banks are limited to 50% usable DoD. All battery and DC bus voltages covered in this glossary reference remain strictly <=60V DC across 12V, 24V, and 48V nominal systems.
Core Formulas and Voltage Baselines
Use plain-text energy conversions anchored to the battery nameplate nominal voltage (V_nominal), not rounded marketing labels:
Wh = Ah x V_nominal
Ah = Wh / V_nominal
kWh = Wh / 1000
Usable_Wh = Ah x V_nominal x DoD
AC_Runtime_h = Usable_Wh / ((AC_Load_W / Inverter_Efficiency) + Inverter_Tare_W)
| Nominal Class | Chemistry | Nameplate V_nominal | Typical Absorb Voltage | Usable DoD |
|---|---|---|---|---|
| 12V | LiFePO4 | 12.8V | 14.2–14.6V | 80–90% (85% default) |
| 12V | AGM / Lead-Acid | 12.0V | Per battery datasheet | 50% |
| 24V | LiFePO4 | 25.6V | 28.4–29.2V | 80–90% (85% default) |
| 24V | AGM / Lead-Acid | 24.0V | Per battery datasheet | 50% |
| 48V | LiFePO4 | 51.2V | 56.8–58.4V | 80–90% (85% default) |
| 48V | AGM / Lead-Acid | 48.0V | <=60.0V DC max | 50% |
Comparing a 100Ah 12.8V Battery With a 1,000Wh Power Station
Compare at the Same Output Point and Count Losses Once
To compare a 100 Ah, 12.8 V LiFePO₄ battery against a 1,000 Wh portable power station running the same laptop without mixing up Ah, Wh, and inverter losses:
- Convert both to nominal Wh first:
100 Ah × 12.8 V = 1,280 Whnominal (28% more stored nominal energy than1,000 Wh).
- Compare at the exact same output measurement point:
- Suppose both setups deliver an illustrative 80% of nameplate Wh to the AC outlet (accounting for usable DoD, inverter efficiency, and inverter standby draw), and the same laptop charger draws 50 W measured at the AC outlet:
- 100 Ah 12.8 V battery + inverter:
(1,280 Wh × 0.80) = 1,024 Whdelivered →1,024 Wh / 50 W = 20.5 hours. - 1,000 Wh portable power station:
(1,000 Wh × 0.80) = 800 Whdelivered →800 Wh / 50 W = 16.0 hours.
- 100 Ah 12.8 V battery + inverter:
- Suppose both setups deliver an illustrative 80% of nameplate Wh to the AC outlet (accounting for usable DoD, inverter efficiency, and inverter standby draw), and the same laptop charger draws 50 W measured at the AC outlet:
- Never subtract efficiency twice:
- If you measure delivered Wh directly at the AC outlet (or USB-C input to the laptop) with an inline wattmeter from full to shutoff, divide that measured Wh directly by the load's average watts at the same measurement point—do not multiply by inverter efficiency a second time. When comparing an AC laptop brick vs. USB-C PD output, measure both paths at the laptop's input so AC conversion loss and inverter idle draw are captured fairly.
- Compare existing battery runtime vs. portable station runtime in the calculator
- Review portable power station usable capacity and conversion efficiency
100 Ah Bank Comparison Across 12V, 24V, and 48V
The table below uses an illustrative 100 Ah battery rating per nominal class to show how nameplate Wh, kWh, and usable Wh scale with voltage and chemistry:
| Bank Configuration (Illustrative 100 Ah) | V_nominal | Nameplate Wh | Nameplate kWh | Default Usable DoD | Usable Wh |
|---|---|---|---|---|---|
| 12V 100 Ah LiFePO4 | 12.8V | 1,280 Wh | 1.28 kWh | 85% | 1,088 Wh |
| 12V 100 Ah AGM / Lead-Acid | 12.0V | 1,200 Wh | 1.20 kWh | 50% | 600 Wh |
| 24V 100 Ah LiFePO4 | 25.6V | 2,560 Wh | 2.56 kWh | 85% | 2,176 Wh |
| 24V 100 Ah AGM / Lead-Acid | 24.0V | 2,400 Wh | 2.40 kWh | 50% | 1,200 Wh |
| 48V 100 Ah LiFePO4 | 51.2V | 5,120 Wh | 5.12 kWh | 85% | 4,352 Wh |
| 48V 100 Ah AGM / Lead-Acid | 48.0V | 4,800 Wh | 4.80 kWh | 50% | 2,400 Wh |
Step-by-Step Conversion and Sizing Procedure
- Verify nameplate ratings. Read
AhandV_nominaldirectly from the battery datasheet or case label (12.8V, 25.6V, or 51.2V for LiFePO4; 12.0V, 24.0V, or 48.0V for AGM/lead-acid). Confirm that peak charging voltage stays <=60V DC. - Convert Ah to Wh and kWh. Multiply
Ah x V_nominalto get nameplate Wh, then divide by 1,000 for kWh. If a datasheet lists Wh directly, verify it againstAh x V_nominalto confirm the cell count and nominal voltage. - Apply usable DoD. Multiply nameplate Wh by
0.85(or the manufacturer's rated 0.80–0.90 window) for LiFePO4, or0.50for AGM/lead-acid. - Account for series and parallel wiring.
- Series strings: Add
V_nominalacross batteries while keepingAhequal to a single battery (e.g., two 12.8V 100 Ah batteries in series = 25.6V 100 Ah = 2,560 Wh). - Parallel banks: Add
Ahacross batteries while keepingV_nominalconstant (e.g., two 12.8V 100 Ah batteries in parallel = 12.8V 200 Ah = 2,560 Wh).
- Series strings: Add
- Apply load conversion and temperature limits. For AC loads—whether 120V/60Hz (North America) or 230V/50Hz (UK/AU)—divide AC watts by inverter efficiency and add inverter idle tare draw before dividing into
Usable_Wh. When ambient battery temperature drops to <=5°C (41°F), verify the BMS minimum charge temperature (some commercial packs lock out charging at +5°C); hard-block charging at <=0°C (32°F) unless the pack has active self-heating.
Sign-Off Criteria
- Total stored energy is expressed in Wh or kWh using exact
V_nominal(12.8V / 25.6V / 51.2Vor12.0V / 24.0V / 48.0V). - Usable energy reflects chemistry DoD (
85%default LiFePO4;50%AGM/lead-acid) rather than 100% nameplate Wh. - Series/parallel bank totals match the single-battery Wh multiplied by the total number of identical batteries.
- All DC bus and charging voltages remain strictly <=60V DC, and cold-charge thresholds (
<=5°C / 41°Fcheck,<=0°C / 32°Fblock) are documented for the installation environment.
Failure Modes
- Comparing Ah across different bank voltages: Treating a 200 Ah 12.8V bank (2,560 Wh) as larger than a 100 Ah 51.2V bank (5,120 Wh) results in a 50% energy shortfall.
- Double-counting series-parallel capacity: Adding both voltage and Ah when wiring batteries in series produces an imaginary 2x or 4x energy figure that collapses under load.
- Dividing AC appliance amps directly into DC battery Ah: A 10 A load at 120V/60Hz AC (1,200 W) or 5.2 A at 230V/50Hz AC (1,200 W) draws roughly 100 A+ from a 12.8V DC bus after inverter losses, exhausting a 100 Ah 12.8V bank in under an hour rather than 10 hours.
- Ignoring DoD and inverter tare draw: Sizing runtime from 100% nameplate Wh on an AGM bank or omitting continuous inverter standby draw causes premature low-voltage cutoff on overnight loads.
Sources and Verification
- Victron Energy — Wiring Unlimited — Battery capacity (Ah/Wh), usable depth of discharge, and inverter loss budgeting.
- Measurement note: Nominal Wh equals
Ah × V_nominal; delivered Wh at an AC or USB-C port depends on actual load level, standby draw, and cutoff thresholds and is best verified with an inline wattmeter under the same load and start/stop conditions.