On this page

Both architectures operate within the broader charging source comparisons framework and feed the same <=60V DC house bus (12V, 24V, or 48V nominal). In mixed-use RV and marine vessels, solar handles daily base-load offset while an AC-DC shore charger provides deterministic bulk recovery and equalization-free LiFePO4 top-balancing when docked or pitched.

Architectural & Specification Comparison

Parameter Solar (MPPT Photovoltaic) Shore Power (AC-DC Charger / Inverter-Charger)
Input Voltage & Frequency DC array: cold Voc <=150V DC (disconnect/touch-safety required above 60V DC) NA: 120V/60Hz (15A, 20A, 30A, or 50A split-phase 120/240V); UK/AU: 230V/50Hz (16A or 32A)
DC Bus Baselines (<=60V DC) LiFePO4: 12.8V / 25.6V / 51.2V (absorb 14.2–14.6V / 28.4–29.2V / 56.8–58.4V); AGM: 12.0V / 24.0V / 48.0V LiFePO4: 12.8V / 25.6V / 51.2V (absorb 14.2–14.6V / 28.4–29.2V / 56.8–58.4V); AGM: 12.0V / 24.0V / 48.0V
Usable Battery DoD LiFePO4: 80–90% (85% default); AGM/lead-acid: 50% LiFePO4: 80–90% (85% default); AGM/lead-acid: 50%
Recharge Predictability Weather, latitude, tilt, and shading dependent Deterministic; limited only by pedestal breaker and charger rating
Continuous Duty Derating Array derated for temperature (hot Vmp), soiling, and MPPT conversion (~95–98%) Continuous (>=3h) AC draw limited to 80% of pedestal breaker rating unless charger input-current limiting is active
Cold-Charging Limit Flag <=+5°C (41°F) for BMS lockout check; hard block <=0°C (32°F) unless self-heated Flag <=+5°C (41°F) for BMS lockout check; hard block <=0°C (32°F) unless self-heated
Grounding & Shock Protection Array frame bonding + DC-rated isolator/OCPD above 60V DC RCD (30 mA UK/AU) or ELCI/GFCI (30 mA / 5 mA NA), single neutral-to-ground bond, marine galvanic isolation

Shore Power Interface & Grounding Constraints

Shore power introduces AC-side safety and corrosion constraints that do not exist on an isolated DC solar array. All AC interface ratings below describe equipment concepts and nameplate limits only.

  • North American 120V/60Hz Pedestals: Common campsite and marina pedestals supply 15A (1,800W peak / 1,440W continuous at 80%), 20A (2,400W / 1,920W), 30A (3,600W / 2,880W), or 50A 120/240V. On a 15A pedestal, an inverter-charger without programmable AC input-current limiting will trip the pedestal breaker if DC charging plus pass-through AC loads exceed 12A continuous.
  • UK & Australian 230V/50Hz Pedestals: Marina and caravan pitches typically supply 16A (3,680W peak / 2,944W continuous at 80%) or 32A (7,360W / 5,888W) at 230V/50Hz. Higher line voltage cuts AC input current roughly in half for the same DC charge wattage compared to 120V/60Hz, reducing shore-cord voltage drop.
  • RCD / ELCI Protection: UK/Australian pitches and North American marinas enforce 30 mA residual current protection (RCD or ELCI) on the pedestal or vessel inlet. High-frequency switch-mode chargers with damaged EMI suppression or wet shore inlets can leak >15–30 mA to ground and trip the pedestal.
  • Neutral-to-Ground Bonding: A mobile or marine AC system must have exactly one neutral-to-ground bond at any time. When plugged into shore power, the shore pedestal provides the bond; an onboard inverter-charger must open its internal neutral-ground relay during shore pass-through and close it only when inverting off-grid. Two simultaneous bonds create parallel neutral return paths on the safety ground and trip 30 mA RCD/ELCI devices.
  • Marine Galvanic Isolation: Connecting a vessel's DC negative/grounding bus to a marina AC safety ground creates an underwater galvanic cell between the boat's submerged metals (propellers, shafts, through-hulls) and neighboring vessels or steel pilings. Install a galvanic isolator or a marine isolation transformer on the shore inlet to block low-voltage DC galvanic currents while preserving the AC fault-clearing path.

Sizing & Current Calculations (Illustrative Assumptions)

All calculations below use plain-text formulas and illustrative assumptions. Verify exact efficiency, power factor, and temperature coefficients on the equipment nameplate before ordering wire or protection.

Illustrative System Baseline:

  • House bank: 24V LiFePO4 (25.6V nominal, 28.8V absorb, 85% usable DoD).
  • Daily house load: 2,400 Wh/day.
  • Location assumptions: 4.0 peak sun hours (summer) vs. 1.2 peak sun hours (winter); ambient air 25°C (77°F) nominal, winter low -10°C (14°F).

1. Solar Array Sizing vs. Shore Charger Sizing

  • Required Daily PV Harvest (assuming 85% system/MPPT/wire efficiency): Required_PV_Wh = Daily_Load_Wh / 0.85 = 2,400 / 0.85 = 2,824 Wh/day
  • Summer Array Wattage (4.0 peak sun hours): Array_W_summer = 2,824 / 4.0 = 706 W (feasible on most RV roofs or marine arches).
  • Winter Array Wattage (1.2 peak sun hours): Array_W_winter = 2,824 / 1.2 = 2,353 W (typically exceeds mobile/marine mounting area, shifting primary reliance to shore power).
  • Shore Charger AC Draw (for a 60A DC charger at 28.8V absorb, assuming 90% charger efficiency and 0.95 power factor): DC_Charge_W = 60 A * 28.8 V = 1,728 W AC_Apparent_VA = 1,728 / (0.90 * 0.95) = 2,021 VA AC_Current_120V = 2,021 VA / 120 V = 16.8 A (exceeds a 15A NA pedestal's 12A continuous limit; requires a 20A/30A pedestal or input-current limiting). AC_Current_230V = 2,021 VA / 230 V = 8.8 A (fits comfortably within a 16A UK/AU pedestal's 12.8A continuous limit).

2. DC Charging Circuit Wire Sizing & Fusing

Size DC cables between the MPPT controller or shore charger and the <=60V DC bus using the larger cross-section required by voltage drop or derated ampacity.

  • Voltage Drop (<=3% critical/charging circuits, 75°C copper resistivity = 0.02097 ohm·mm²/m): Assume a 60A charger located 2.5 m (8.2 ft) one-way from the 25.6V bus (Round_Trip_L = 2 * 2.5 = 5.0 m). Max_Drop_V = 25.6 V * 0.03 = 0.768 V Min_Area_mm2 = (0.02097 * 5.0 m * 60 A) / 0.768 V = 8.19 mm² (next standard sizes: 10 mm² or 6 AWG at 13.3 mm²).
  • Continuous Ampacity (>=1.25x continuous >=3h): Design_Ampacity = 60 A * 1.25 = 75 A Verify that the selected 6 AWG (13.3 mm²) marine/UL-listed 105°C-insulated copper cable is rated >=75 A when terminated at 75°C equipment lugs (derate if bundled or in engine rooms >30°C / 86°F). Never substitute undersized SAE J1128 automotive wire or copper-clad aluminum (CCA) cable.
  • Overcurrent Protection (OCPD): Select a DC fuse <= cable ampacity and >=75 A (e.g., 80 A fuse). Verify fuse maximum voltage rating >= max charging voltage: for a 51.2V LiFePO4 bank charging at 58.4V, 58V-rated terminal fuses are non-compliant and must be replaced with >=60V DC-rated fuses. Confirm prospective battery fault current <= fuse AIC at operating voltage.

Selection & Commissioning Steps (DC Side)

  1. Audit Daily Energy & Berth Access: Calculate total daily Wh including inverter idle tare draw and DC/AC conversion losses. Confirm whether worst-case seasonal peak sun hours can cover Daily_Load_Wh / 0.85 within available roof/arch area.
  2. Verify Battery Cold-Charge Thresholds: Check the battery BMS datasheet for minimum charge temperature. Flag <=+5°C (41°F) because some commercial LiFePO4 packs lock out charging at +5°C; enforce a hard charge block at <=0°C (32°F) on both MPPT and shore chargers unless the battery is actively self-heated.
  3. Validate MPPT Array Window (Solar Path):
    • Calculate worst-case cold array open-circuit voltage using site minimum ambient temperature and the panel's Voc temperature coefficient: confirm Cold_Voc < MPPT_Vmax and Cold_Voc <= 150V DC.
    • Confirm Hot_Vmp (at maximum cell temperature) remains above the MPPT controller's minimum startup/running voltage window per the device manual.
    • Confirm parallel Array_Isc <= MPPT_Isc_max. For 3 or more parallel strings, install string fuses rated <= panel max series fuse rating to prevent backfeed damage.
  4. Match Shore Charger to Pedestal Limits (Shore Path): Set the charger's AC input-current limit to <=80% of the lowest expected pedestal breaker (e.g., 12A on a 15A 120V pedestal; 12.8A on a 16A 230V pedestal).
  5. Install DC Cabling & Protection: Run 2x round-trip calculations at 75°C copper resistivity (0.02097 ohm·mm²/m), enforce <=3% drop and >=1.25x continuous ampacity, torque 75°C-rated lugs per manual, and place the DC OCPD within 7 inches (180 mm) of the battery/busbar positive source. Install a lockable DC isolator on PV arrays exceeding 60V DC.

Sign-Off Criteria

  • DC Voltage & Polarity: Bus voltage <=60V DC at peak absorb (<=14.6V / <=29.2V / <=58.4V); PV array cold Voc <=150V DC and below MPPT_Vmax.
  • Voltage Drop: Measured drop from charger/MPPT output terminals to battery bus <=3% at full rated charge current.
  • OCPD Compliance: Fuse voltage rating >= max charging voltage (e.g., >=60V DC for 58.4V systems), fuse rating <= derated cable ampacity, and fuse AIC >= battery prospective fault current.
  • Cold-Charge Lockout: Simulated or sensor-tested charge inhibit triggers at <=0°C (32°F) (or <=+5°C / 41°F per BMS spec) on both MPPT and AC charger.
  • Shore Safety (if equipped): Pedestal RCD/ELCI trips cleanly on test; neutral-to-ground continuity confirms open onboard bond while on shore power and closed bond while inverting; marine shore ground passes through a tested galvanic isolator or isolation transformer.

Real Failure Modes

  • Cold-Temperature Lithium Plating or Sudden BMS Disconnect: Charging LiFePO4 below 0°C (32°F) causes permanent metallic lithium plating, while commercial packs with a +5°C (41°F) BMS cutoff will open the charge FET mid-absorb, causing voltage spikes on non-buffered chargers.
  • 58V Terminal Fuse Failure on 48V LiFePO4: Using a standard 58V-rated bolt-on terminal fuse on a 51.2V bank that charges to 58.4V exceeds the fuse's DC arc-quenching voltage rating and risks sustained arcing under fault.
  • Pedestal Breaker & RCD Nuisance Tripping: Running a full-rate shore charger alongside an electric water heater or air conditioner on a 15A/120V or 16A/230V pedestal trips thermal breakers, while a stuck neutral-ground relay trips 30 mA RCD/ELCI breakers immediately upon plug-in.
  • Accelerated Marine Underwater Corrosion: Connecting to marina shore power without a galvanic isolator or isolation transformer dissolves zinc anodes and pits bronze/aluminum underwater gear within weeks.
  • Winter PV Over-Voltage or Summer Brownout: Sizing a PV series string close to MPPT_Vmax at 25°C (77°F) causes freezing morning Voc to exceed controller limits and destroy input MOSFETs; conversely, undersized series voltage drops below the MPPT startup window on hot roofs.