Required Array Wattage (W) = Daily_Recharge_Wh / (Worst_Month_PSH * Derating_Factor)
Use 0.75 to 0.80 for MPPT charge controllers with unshaded arrays and LiFePO4 batteries, and drop to 0.70 (or lower) for partial horizon shading, high ambient module temperatures, flat-mounted RV/marine panels, or lead-acid/AGM banks with high absorption-stage taper losses. For full array topology, combiner protection, and disconnect rules once your wattage is set, see the parent Solar Arrays reference.
Conditions That Shift the Calculation
| Parameter | Baseline Value | When to Adjust |
|---|---|---|
| Overall charging derating factor | 0.70 – 0.80 (MPPT default: 0.75) | Use 0.70 for flat-mounted panels, high heat, or AGM absorption taper; 0.55–0.65 if using a PWM controller on mismatched module voltage |
| Peak sun hours (PSH) | Worst-month daily average (1.5–4.5 h typical) | Use annual or summer PSH only for fair-weather seasonal RVs/cabins; year-round systems must size to the lowest-sun month |
| LiFePO4 bank baseline | 12.8V / 25.6V / 51.2V nominal (absorb 14.2–14.6V / 28.4–29.2V / 56.8–58.4V) | Usable DoD 80–90% (default 85%); high coulombic efficiency (~95–98%) supports 0.75–0.80 array derating |
| AGM / lead-acid bank baseline | 12.0V / 24.0V / 48.0V nominal | Usable DoD 50%; slower absorption current acceptance increases effective array size needed to reach full charge before sunset |
| System voltage boundaries | Battery bus <=60V DC; PV array cold Voc <=150V DC | Above 60V DC on the PV side requires touch-safe PV disconnects and rated isolation; never exceed 60V DC on the battery bus |
| Cold-charging temperature floor | Flag at <=+5°C (41°F); hard block at <=0°C (32°F) | Some commercial LiFePO4 BMS units lock out charging at +5°C (41°F); block charging at <=0°C (32°F) unless the pack is self-heated |
Step-by-Step Array Sizing
- Determine daily battery recharge watt-hours (
Daily_Recharge_Wh). Sum all daily DC loads plus any 120V/60Hz AC inverter loads (or 230V/50Hz AC loads in UK/AU systems). Include inverter conversion losses (typically 10–15%) and 24-hour inverter idle tare draw in the daily total so the solar array replaces what the battery actually loses. - Select worst-month PSH for the installation tilt. Pull the site's worst-month solar insolation in kWh/m²/day (numerically equal to PSH) at the planned panel tilt angle. Flat-mounted roof panels on an RV or boat receive significantly fewer winter PSH than latitude-tilted cabin mounts.
- Compute minimum STC array wattage.
Divide
Daily_Recharge_Whby(Worst_Month_PSH * Derating_Factor). Round up to the nearest practical module combination. - Check charge controller output current against battery voltage.
Verify that the MPPT controller's continuous output rating meets or exceeds this value, or step the battery bank from 12.8V to 25.6V or 51.2V to cut charge current in half or a quarter.Controller_Output_A = Array_STC_W / Battery_Nominal_V - Verify string voltage and current limits against the controller nameplate.
- Cold
Voc: Calculate stringVocat the site's record low ambient temperature using the panel nameplateVoctemperature coefficient. ConfirmCold_String_Voc < MPPT_Vmaxand<=150V DC. - Hot
Vmp: Calculate stringVmpat high cell temperature (typically ambient + 25–35°C / 45–63°F on a roof). ConfirmHot_String_Vmpstays above the controller's startup and running voltage window (per device manual) over the battery's maximum absorb voltage (14.6V / 29.2V / 58.4V). - Parallel
Iscand backfeed: Sum parallel stringIscvalues and confirmTotal_Array_Isc <= MPPT_Isc_max. If wiring 3 or more parallel strings, verify that combined backfeed current does not exceed the panel nameplate maximum series fuse rating, or install per-string fuses/breakers.
- Cold
Worked Illustrative Example (24V Cabin System)
Illustrative assumptions: Daily DC + 120V/60Hz AC inverter demand (after conversion losses and tare) = 1,500 Wh/day; worst-month flat/low-tilt PSH = 3.0 h/day; MPPT derating factor = 0.75; 25.6V nominal LiFePO4 bank (29.2V max absorb); illustrative 200W modules with nameplate Voc = 24.0V, Vmp = 20.0V, Isc = 10.6A, Voc coeff = -0.28%/°C, Vmp coeff = -0.35%/°C; site record low = -20°C (-4°F); peak cell temp = +65°C (149°F).
- Required array wattage:
1,500 Wh / (3.0 PSH * 0.75) = 667 Wminimum -> select 4 x 200W = 800W STC. - Controller output current:
800W / 25.6V = 31.3A-> select at least a 35A–40A MPPT controller (or check manual for safe over-paneling behavior if using a 30A unit). - Cold
Voccheck (4S string):delta_T = -20°C - 25°C = -45°C. Rise =-45 * -0.28% = +12.6%.Cold_Voc = 4 * 24.0V * 1.126 = 108.1V. Safe for a 150V MPPT (< 150V DC), but exceeds 60V DC so a rated PV disconnect is required. - Hot
Vmpcheck (4S string):delta_T = +65°C - 25°C = +40°C. Drop =40 * -0.35% = -14.0%.Hot_Vmp = 4 * 20.0V * 0.86 = 68.8V. Stays well above 29.2V absorb plus controller headroom. - Parallel
Isccheck (4S1P): Single stringIsc = 10.6A(<= MPPT_Isc_max); no 3+ parallel string backfeed fuse needed.
Commissioning Sign-Off Criteria
Daily_Recharge_Whincludes AC inverter efficiency losses and 24-hour idle tare draw.- Array STC wattage meets or exceeds
Daily_Recharge_Wh / (Worst_Month_PSH * Derating_Factor)using worst-month PSH for the actual mounting tilt. Cold_String_Vocat record site low temperature is strictly belowMPPT_Vmaxand<=150V DC(with a touch-safe disconnect installed if above 60V DC).Hot_String_Vmpstays within the MPPT controller's running voltage window above maximum battery absorb voltage (14.6V / 29.2V / 58.4V).Total_Array_Isc <= MPPT_Isc_max, and strings of 3+ in parallel have series overcurrent protection matching the panel nameplate maximum series fuse rating.- Charge controller low-temperature cutoff is set to block charging at
<=0°C (32°F)(or<=+5°C / 41°Fif required by the battery BMS datasheet) unless a self-heated battery is verified.
Real-World Failure Modes
- Sizing to annual average PSH: Using yearly average sun hours instead of worst-month PSH leaves the battery chronically undercharged in winter, walking LiFePO4 banks down to low-voltage cutoff and sulfating lead-acid banks.
- Ignoring inverter idle tare and conversion loss: Counting only AC appliance nameplate watt-hours omits the 10–15% conversion loss and continuous inverter standby draw (often 10–40W on 120V/60Hz or 230V/50Hz units), understating daily recharge needs by 250–1,000 Wh/day.
- Cold-morning
Vocovervoltage: Sizing strings at 25°C (77°F) STCVocnear a 100V or 150V MPPT limit causes morning open-circuit voltage spikes in freezing weather to permanently damage the controller input stage. - Hot-roof
Vmpsag below startup threshold: Single 12V-class panels or 2S strings on a 48V bank can sag below the controller'sV_batt + headroomrunning window on hot summer roofs, stalling harvest during peak midday sun. - Sub-freezing LiFePO4 charging: Allowing an active solar array to push current into non-heated LiFePO4 cells at
<=0°C (32°F)(or below a+5°C / 41°FBMS limit) causes lithium plating or sudden BMS charge-FET disconnect that can spike controller output voltage if no load is present.