On this page

Conditions that change this procedure:

  • Active heated storage: If the bank remains in a climate-controlled space above +5°C (41°F) or relies on internal self-heating pads to stay above freezing, it requires continuous power rather than unpowered lay-up; see the parent Winter Lay-Up guide for active-system vs. unpowered storage trade-offs.
  • BMS without storage mode: If the battery lacks a sleep/storage switch or draws more than 1–2 mA quiescent current for Bluetooth, CANbus, or displays, physically unbolt the main negative cable at the bank terminal after isolating external circuits.
  • Extreme cold (< -20°C / -4°F): Verify the battery nameplate's minimum unpowered storage temperature; if ambient temperatures drop below the pack's storage rating, remove the batteries to a dry space within the rated temperature window.

Storage Parameters and Voltage Targets

LiFePO4 cells have a flat open-circuit voltage curve between 20% and 80% SoC, so use a calibrated coulomb-counting shunt to set 50% SoC rather than relying on voltage alone. Unlike AGM/lead-acid banks (12.0V / 24.0V / 48.0V nominal, 50% usable DoD, stored at 100% SoC on a float charger), LiFePO4 banks suffer accelerated calendar aging when held at 100% SoC and must never be left on a continuous float charger during freezing lay-up.

Parameter 12V System (12.8V Nominal) 24V System (25.6V Nominal) 48V System (51.2V Nominal)
Typical Absorb Voltage 14.2–14.6V 28.4–29.2V 56.8–58.4V
Target Lay-Up SoC 45–55% (Default 50%) 45–55% (Default 50%) 45–55% (Default 50%)
Approx. Resting Voltage at 50% SoC (1–2 h zero load/charge) 13.0–13.1V 26.0–26.2V 52.0–52.4V
Verify BMS Low-Temp Charge Lockout <= +5°C (41°F) <= +5°C (41°F) <= +5°C (41°F)
Hard Charge Block (Unless Self-Heated) <= 0°C (32°F) <= 0°C (32°F) <= 0°C (32°F)
Typical Unpowered Self-Discharge 1–3% per month 1–3% per month 1–3% per month

Step-by-Step Lay-Up Procedure

1. Set State of Charge to ~50% Before Freezing Temperatures Arrive

  1. Check cell temperature via the BMS or an infrared thermometer on the battery case.
  2. Flag any temperature at or below +5°C (41°F) and verify the battery nameplate's minimum charge temperature (some commercial BMS units lock out charging at +5°C). Hard-block all charging at or below 0°C (32°F).
  3. Charge or discharge the bank under normal temperatures until the battery monitor reads 45–55% SoC. If the bank is at 100% SoC, run a DC load or inverter briefly to bring it down to ~50% SoC, then let it rest for 1–2 hours.

2. Isolate All Charging Sources

  1. Solar (MPPT / PV): Open the PV array DC isolator/breaker first to drop array voltage off the controller, then open the breaker between the MPPT output and the battery bus. For PV arrays with cold open-circuit voltage (Voc) above 60V DC (up to the 150V DC system ceiling), use a touch-safe, rated DC disconnect. Never leave solar connected to "top off" the bank over winter.
  2. Alternator / DC-DC Charger: Open the DC-DC charger's input and output breakers or fuses, and disconnect the ignition/D+ trigger wire so engine starts or vehicle movement cannot energize the charging bus.
  3. AC-to-DC Shore Charger / Inverter-Charger: Disconnect the 120V/60Hz (North America) or 230V/50Hz (UK/AU) AC shore supply to the charger, then open the DC breaker between the charger and the battery bank.

3. Eliminate All Parasitic DC Loads

  1. Power off the inverter at its main switch (inverters draw continuous idle tare current even with zero AC load connected) and open the main DC battery disconnect switch.
  2. Locate and isolate unswitched circuits that commonly bypass the main house switch: bilge pumps, LP gas and CO detectors, cellular/Wi-Fi routers, shunt displays, USB outlets, and stereo memory feeds. Pull their inline fuses or open their branch breakers.
  3. Verify zero bus current using a DC clamp meter on the main battery cable or by checking the inline shunt readout.

Illustrative parasitic drain calculation: Assume a 12.8V 100Ah LiFePO4 bank (1,280Wh nominal) stored at 50% SoC holds 50Ah (640Wh) of reserve. A small unswitched parasitic load of 25 mA (0.025 A) draws: 0.025 A x 24 h x 30 days = 18 Ah/month At 18 Ah/month, the 50Ah reserve reaches 0% SoC in: 50 Ah / 18 Ah/month = 2.78 months Once depleted, the BMS trips under-voltage lockout and continued self-discharge can drop cells below recoverable voltage before spring.

4. Engage BMS Storage Mode or Physically Disconnect

  1. If the battery pack has a physical power button, Bluetooth app storage command, or CANbus sleep function, activate storage/ship mode after all external chargers and loads are open.
  2. If the BMS has no storage mode or retains active comms/LED draw, unbolt the main negative cable from the bank's negative terminal (or open a battery-side isolation switch rated for the bank's operating voltage, <=60V DC) and insulate the exposed lug.
  3. For multi-battery parallel banks, confirm every battery in the bank is in the exact same off/storage or disconnected state so individual packs do not drift apart unevenly.

Sign-Off Criteria

  • SoC verified: Shunt reads 45–55% SoC (or resting OCV is ~13.0–13.1V / ~26.0–26.2V / ~52.0–52.4V after 1–2 hours at zero load).
  • Chargers isolated: PV array isolator, MPPT-to-battery breaker, DC-DC charger, and AC shore charger (120V/60Hz NA or 230V/50Hz UK/AU) are physically open/disconnected.
  • Zero bus current: Main DC disconnect is open, bypass loads are pulled, and a DC clamp meter or shunt reads 0.0 A on the external bus.
  • BMS asleep or cable lifted: Storage/sleep mode is active (LEDs and comms off) or the main negative terminal cable is unbolted and insulated.
  • Storage temperature checked: Expected winter ambient minimum stays within the battery nameplate's unpowered storage rating (typically -20°C / -4°F or higher).

Failure Modes During Winter Lay-Up

  • Parasitic drain into BMS under-voltage lockout: Leaving a shunt, gas detector, or active BMS Bluetooth radio connected drains the 50% reserve over 2–4 months. After BMS cutoff, internal self-discharge can pull cells below 2.0–2.5V/cell, preventing standard chargers from waking the pack in spring.
  • Sub-zero charging and lithium plating: Leaving solar or a shore maintainer connected allows charging on sunny or mild-seeming days when cell cores are still at or below 0°C (32°F) (or <=+5°C / 41°F on packs with +5°C lockouts). If the BMS lacks low-temp protection or a thermistor fails, charging below freezing plates metallic lithium onto the anode, permanently cutting capacity and creating an internal short-circuit hazard.
  • Holding 100% SoC on float: Applying lead-acid winter habits (leaving the bank at 100% SoC on a continuous float voltage) accelerates electrolyte oxidation and calendar degradation in LiFePO4 cells.
  • Parallel bank imbalance at spring wake-up: Leaving one battery in a parallel bank active while another is in storage mode creates an SoC mismatch. Closing the parallel bus in spring without equalizing individual pack voltages causes high inrush currents between batteries; verify bank-to-bank voltage difference is under 0.2V (12.8V), 0.4V (25.6V), or 0.8V (51.2V) before re-paralleling.