This partitioning applies to 12V, 24V, and 48V nominal DC systems strictly at or below 60V DC on the battery and DC bus side. For bank chemistry, case sizing, and cranking specifications on the starting side, see starter batteries.
Load Partitioning Specifications
| Load Category | Assigned Bank | Duty & Voltage | Assignment Condition & Protection Check |
|---|---|---|---|
| Engine ignition & starter motor | Starter | High-current intermittent (12V/24V) | Keep cable runs short; never route through a house BMS unless the battery is explicitly cranking-rated. |
| OEM chassis electronics & ECU/ECM | Starter | Continuous while running; low-mA sleep | Preserve OEM factory fusing and voltage stability during cranking; critical <=3% voltage drop. |
| Navigation & road lighting | Starter | Continuous during operation | Legally required while underway; keep independent of house low-voltage disconnects (LVD). |
| Refrigeration & galley appliances | House / Leisure / Auxiliary | Cycling 24/7 | Size house bank usable Ah for multi-day autonomy; verify compressor startup surge against wire drop (<=3% critical). |
| Cabin & utility lighting | House / Leisure / Auxiliary | Intermittent to continuous | Non-critical circuits <=10% voltage drop; isolate from starter bank to protect cranking reserve. |
| DC-to-AC inverters (120V/60Hz NA; 230V/50Hz UK/AU) | House / Leisure / Auxiliary | High continuous + surge | Check worst-case DC current at V_min, BMS peak duration, and fuse time-current curve. |
| Communications & instrumentation | House / Leisure / Auxiliary | Continuous low draw | Wire critical VHF/telemetry at <=3% drop; verify clean ground and stable DC input window. |
| High-inrush winches & windlasses | Starter (alternator running) or House | Short high-inrush | Assign to starter only if alternator supports load and cranking reserve holds; assign to house only if BMS peak rating exceeds stall current. |
| Unattended bilge pumps & safety circuits | Starter or Direct House | Standby + intermittent | Bypass main house switch and LVD; if on starter, verify float-switch parasitic draw does not deplete cranking reserve. |
Bank Chemistry and Operating Baselines
Starter banks prioritize high cold-cranking amps (CCA) and mechanical vibration resistance over deep-cycle life, whereas house banks prioritize usable energy capacity (Wh) and cycle life.
| Parameter | AGM / Lead-Acid Baseline | LiFePO4 Baseline | Engineering Constraint |
|---|---|---|---|
| Nominal bank voltage | 12.0V / 24.0V / 48.0V | 12.8V / 25.6V / 51.2V | Keep entire DC bus <=60V DC. |
| Typical absorption voltage | Per battery nameplate (typically 14.2–14.8V / 28.4–29.6V / 56.8–59.2V) | 14.2–14.6V / 28.4–29.2V / 56.8–58.4V | Fuse max voltage rating must be >= max charging voltage (e.g., 58.4V exceeds 58V-rated terminal fuses). |
| Usable depth of discharge (DoD) | 50% | 80–90% (default 85%) | Size house bank capacity using usable Wh, not nameplate Wh. |
| Cold-charging limit | Temperature-compensated voltage per nameplate | Flag <=+5°C (41°F); hard block <=0°C (32°F) unless self-heated | Verify BMS minimum charge temperature on the pack datasheet (some commercial packs lock out at +5°C / 41°F). |
Step-by-Step Load Assignment
Lock OEM and underway safety loads to the starter bank. Confirm engine starter motor, ignition, ECU/ECM, alternator excitation, and road or navigation lights remain on the starter bus. Check the engine manual for minimum cranking CCA/MCA at the lowest expected ambient temperature (
°F/°C).Move hotel and continuous DC/AC loads to the house bank. Transfer refrigeration, cabin lighting, communications, USB/12V outlets, and DC-to-AC inverters (120V/60Hz output in North America; 230V/50Hz output in the UK and Australia) to the house, leisure, or auxiliary bus. For inverters, compute worst-case DC current at the inverter's low-voltage cutoff (
V_min) and conversion efficiency from the nameplate:I_dc_max = P_ac_continuous / (V_min * efficiency)Illustrative example: A 2,000W 120V/60Hz inverter on a 12.8V LiFePO4 house bank with
V_min = 11.0Vand0.88efficiency draws2000 / (11.0 * 0.88) = 206.6Acontinuous DC, requiring>= 206.6 * 1.25 = 258.3Aderated cable ampacity for runs operating >=3 hours.Assign high-inrush winches and windlasses by surge capability. Check the winch nameplate for maximum loaded and stall current.
- Assign to the starter bank if the winch is operated exclusively with the engine running, the alternator supplies part of the demand, and the starter battery is an AGM or lead-acid cranking bank without an electronic over-current cutoff.
- Assign to the house bank only if the house bank's continuous and peak BMS discharge ratings (and peak duration in seconds) exceed the winch's maximum inrush current, and the main fuse time-current curve clears normal winch pulls without nuisance trips.
Assign unattended bilge pumps by disconnect architecture.
- Wire the automatic float switch directly to the house bank (upstream of the main house disconnect and any LVD relay) through a dedicated over-current fuse when the house bank has large reserve Ah and the vessel sits unattended for days.
- Wire to the starter bank only when the house bank is routinely disconnected or depleted, and verify the pump's duty cycle and float-switch standby draw leave sufficient cranking reserve.
Size conductors and over-current protection per circuit.
- Measure total round-trip conductor length (
2 * one-waylength in feet or meters). - Calculate voltage drop using 75°C copper resistivity (
0.02097 ohm·mm²/m):
EnforceV_drop = I_load * (0.02097 * L_round_trip_m / Area_mm2) Drop_pct = (V_drop / V_nominal) * 100<=3%drop on critical circuits (ignition, navigation, refrigeration, communications, bilge pumps) and<=10%on non-critical cabin lighting. - Select the larger conductor required by voltage drop or derated ampacity (
>=1.25xcontinuous >=3h load), honoring terminal temperature ratings (often 75°C) and avoiding undersized SAE J1128 thin-wall assumptions or copper-clad aluminum (CCA) cable traps. - Verify
fuse rating <= cable ampacity,fuse max voltage >= max charging voltage, andprospective fault current <= fuse AICat operating voltage.
- Measure total round-trip conductor length (
Sign-Off Criteria
- Starter bank maintains engine cranking above the OEM minimum cranking voltage with all house loads switched off or isolated.
- Zero hotel loads (refrigeration, cabin lighting, inverters) draw from the starter bank when the engine is off.
- Inverter and winch surge currents are verified against both the house BMS peak-current duration limit and the fuse time-current curve.
- Unattended bilge pump operates when the main house disconnect switch is open and when the house LVD is active.
- Every circuit meets
<=3%(critical) or<=10%(non-critical) voltage drop at round-trip length, with fuse voltage rating>=bank absorption voltage and AIC>=prospective fault current. - LiFePO4 house charging sources block charge current at
<=0°C (32°F)unless self-heated, and<=+5°C (41°F)BMS cutoffs are verified against pack specs.
Real Failure Modes
- Depleted cranking reserve from misassigned hotel loads: Leaving a 12V compressor fridge or inverter on the starter bank overnight drops a 12.0V AGM bank below 50% DoD, preventing engine start and stranding the vehicle or vessel.
- BMS over-current trip blacking out safety loads: Connecting a high-inrush windlass or large inverter to an undersized LiFePO4 house bank triggers a millisecond BMS short-circuit or over-current cutoff. If navigation electronics or bilge pumps share that protected bus, they lose power simultaneously.
- Bilge pump disabled by house LVD or main switch: Wiring an automatic bilge pump downstream of the house battery switch or LVD relay leaves the vessel unprotected when parked or when the house bank reaches low-voltage cutoff.
- Fuse voltage or AIC mismatch on 48V LiFePO4 banks: Using a 58V-rated terminal fuse on a 51.2V nominal LiFePO4 bank that absorbs at 58.4V exceeds the fuse's voltage rating and risks arc-flash failure under fault.
- Cold-charge lithium plating: Allowing alternator or solar charging into a LiFePO4 house bank at or below
0°C (32°F)without a BMS low-temperature lockout or active self-heating causes permanent cell damage.