On this page
This conversion sets the minimum nameplate capacity inside the overall battery sizing workflow. Use 85% usable DoD (within an 80–90% planning band) for LiFePO4 at 12.8V, 25.6V, or 51.2V nominal, and 50% usable DoD for AGM or sealed lead-acid at 12.0V, 24.0V, or 48.0V nominal (keeping all battery and DC bus voltages strictly at or below 60V DC).
If the system runs high-rate loads—such as a North America 120V/60Hz inverter or a UK/AU 230V/50Hz inverter—at discharge rates faster than the battery's rated C-rate, or operates in cold temperatures, apply rate and temperature derating before finalizing nameplate Ah.
Chemistry Depth of Discharge and Nominal Voltage Baselines
Nameplate amp-hours (Ah) cannot be compared directly across chemistries because nominal cell voltage and allowable depth of discharge differ. Convert energy requirements in watt-hours (Wh) first, then divide by the nominal bank voltage.
| Chemistry | Nominal Bank Voltages | Typical Absorb Voltage | Planned Usable DoD | Rate Sensitivity (Peukert) | Cold Charge Cutoff |
|---|---|---|---|---|---|
| LiFePO4 | 12.8V / 25.6V / 51.2V | 14.2–14.6V / 28.4–29.2V / 56.8–58.4V | 85% default (80–90% band) | Low across 0.2C–1C continuous | Verify BMS <= +5°C (41°F); hard block <= 0°C (32°F) unless self-heated |
| AGM / Sealed Lead-Acid | 12.0V / 24.0V / 48.0V | Per nameplate (<= 60V DC bus limit) | 50% maximum for routine cycling | High above C/20 rate | Verify charger temperature compensation on datasheet |
Notes on system boundaries and nameplate checks:
- 60V DC bus ceiling: All battery and DC bus voltages (including charging and bulk/absorb peaks) must remain at or below 60V DC.
- Nameplate C-rate: Lead-acid Ah ratings are typically specified at the 20-hour rate (C/20) at 25°C (77°F), whereas LiFePO4 ratings are commonly specified at C/5 or C/1. Verify the exact reference C-rate and cutoff voltage on the battery datasheet.
- BMS reserve and DoD band: Using 85% DoD for LiFePO4 leaves a 15% buffer above the BMS low-voltage disconnect so normal cycling does not trip protection under transient load sag.
Step-by-Step Conversion from Usable Wh to Nameplate Ah
Follow this sequence using plain-text arithmetic after summing all DC loads and inverter-adjusted AC loads (accounting for inverter efficiency and idle tare draw).
- Determine required usable energy (
E_usablein Wh): Sum the daily or autonomy-period energy demand in Wh at the DC bus. - Apply chemistry DoD (
DoD_planned):E_nameplate (Wh) = E_usable (Wh) / DoD_plannedUse0.85for LiFePO4 (or0.80–0.90if the system design specifies a tighter/wider reserve) and0.50for AGM/sealed lead-acid. - Apply discharge-rate and temperature derating (
F_rate,F_temp):E_adjusted (Wh) = E_nameplate (Wh) / (F_rate * F_temp)- For LiFePO4 at moderate discharge rates (<= 0.5C) and >= 10°C (50°F),
F_rateis typically0.98–1.00. - For AGM/sealed lead-acid discharged faster than C/20 (common with 120V/60Hz or 230V/50Hz inverter loads), check the manufacturer's Peukert curve or C-rate capacity table (for example, a C/5 discharge can reduce effective lead-acid capacity to roughly 75–85% of its C/20 rating).
- For cold operation below 20°C (68°F), apply the datasheet temperature derating factor (
F_temp); lead-acid loses substantial usable capacity near 0°C (32°F), and LiFePO4 experiences increased voltage sag under heavy draw.
- For LiFePO4 at moderate discharge rates (<= 0.5C) and >= 10°C (50°F),
- Convert to nameplate amp-hours (
C_nameplatein Ah):C_nameplate (Ah) = E_adjusted (Wh) / V_nominalUse12.8V,25.6V, or51.2Vfor LiFePO4; use12.0V,24.0V, or48.0Vfor AGM/sealed lead-acid. - Round up to standard battery increments and verify current limits: Confirm the resulting bank meets continuous and surge DC current requirements (including BMS continuous/peak limits for LiFePO4).
Worked Sizing Comparison (Illustrative 2,500 Wh Usable Demand)
Assuming an illustrative daily usable DC-bus requirement of 2,500 Wh at 25°C (77°F) with moderate discharge rates (F_rate = 1.0, F_temp = 1.0):
- LiFePO4 at 85% DoD:
E_nameplate = 2,500 Wh / 0.85 = 2,941.2 Wh- At 12.8V nominal:
2,941.2 Wh / 12.8V = 229.8 Ah(select >= 230 Ah, e.g., three 12.8V 100Ah batteries in parallel = 300 Ah / 3,840 Wh nameplate). - At 25.6V nominal:
2,941.2 Wh / 25.6V = 114.9 Ah(select >= 115 Ah). - At 51.2V nominal:
2,941.2 Wh / 51.2V = 57.4 Ah(select >= 58 Ah).
- At 12.8V nominal:
- AGM / Sealed Lead-Acid at 50% DoD (at C/20 rate):
E_nameplate = 2,500 Wh / 0.50 = 5,000 Wh- At 12.0V nominal:
5,000 Wh / 12.0V = 416.7 Ah(must be upsized further if average discharge rate is faster than C/20). - At 24.0V nominal:
5,000 Wh / 24.0V = 208.3 Ah(must be upsized further if average discharge rate is faster than C/20). - At 48.0V nominal:
5,000 Wh / 48.0V = 104.2 Ah(must be upsized further if average discharge rate is faster than C/20).
- At 12.0V nominal:
Discharge-Rate Behavior and Temperature Constraints
Discharge rate and cell temperature alter both delivered Wh and terminal voltage under load:
- Peukert effect in lead-acid: Drawing 50A–150A DC to feed an inverter causes a much steeper capacity drop in AGM/sealed lead-acid than in LiFePO4. Always size lead-acid banks against the capacity curve matching the actual discharge duration (e.g., C/5 or C/10), not the headline C/20 number.
- Flat voltage curve in LiFePO4: LiFePO4 holds near 12.8V / 25.6V / 51.2V through most of its discharge, keeping inverter DC current lower and avoiding premature low-voltage cutouts—provided total bank Ah is large enough that load current stays within the BMS continuous rating.
- Cold-temperature charging vs. discharging:
- Flag <= +5°C (41°F) during design review to verify the LiFePO4 BMS minimum charge temperature on the datasheet; some commercial packs lock out charging at +5°C.
- Enforce a hard block on LiFePO4 charging at <= 0°C (32°F) unless the battery includes an active self-heating system rated for the ambient environment.
- Do not rely on full nameplate capacity during sub-freezing discharges; verify the manufacturer's low-temperature discharge curve and low-voltage cutoff margin.
Sign-Off Criteria
Before approving a battery bank capacity specification, verify all five items against equipment nameplates and system requirements:
- Wh-first calculation verified: Nameplate Wh equals
E_usable / DoD_plannedusing 80–90% (85% default) for LiFePO4 or 50% for AGM/sealed lead-acid, before dividing by nominal voltage (12.8/25.6/51.2Vor12.0/24.0/48.0V). - Voltage ceiling respected: Maximum charging and operating voltage of the selected bank configuration is strictly
<= 60V DC. - Rate and temperature derated: Lead-acid banks serving high-draw inverters are derated from C/20 to the actual discharge C-rate; cold-climate banks include datasheet temperature derating and BMS cold-charge protection (
<= +5°Ccheck,<= 0°Chard block unless self-heated). - Current headroom confirmed: Selected bank Ah and parallel/series configuration deliver required continuous and surge DC current without exceeding the BMS continuous/peak rating or tripping low-voltage disconnect under sag.
- Nameplate C-rate matched: Battery Ah is taken from the manufacturer's datasheet at a defined C-rate and cutoff voltage, not an unverified marketing label.
Common Sizing Failure Modes
- Converting Ah before applying DoD or mixing 12V and 12.8V: Sizing by Ah at 12.0V and applying it to a 12.8V LiFePO4 bank (or vice versa) introduces a ~6.7% energy error, while forgetting the 50% vs. 85% DoD divider leaves lead-acid banks severely undersized and sulfated.
- Ignoring Peukert losses on inverter loads: Using a C/20 lead-acid rating to run a high-wattage 120V/60Hz or 230V/50Hz inverter causes rapid voltage sag, early inverter low-voltage shutdown, and less than 50% of rated Wh delivered.
- Designing to 100% DoD on LiFePO4: Planning 100% usable capacity leaves zero margin for BMS cell-balancing drift, cold-weather voltage sag, or surge loads, causing unexpected BMS disconnects that cut power to the entire DC bus.
- Overlooking cold-charge lockouts: A bank sized for 85% DoD still fails in winter if the LiFePO4 BMS locks out charging at +5°C (41°F) or 0°C (32°F) without self-heating, stranding the system with depleted state of charge despite available solar or alternator power.
In this section
- Lead-Acid Usable Capacity, 50% DoD, and Peukert Derating Size AGM, gel, and flooded lead-acid banks at a 50% depth of discharge baseline and apply Peukert derating when sustained loads exceed the C20 rate.
- LiFePO4 Usable Capacity and 85% DoD Sizing Size LiFePO4 banks at 85% usable depth of discharge across a flat 12.8V, 25.6V, or 51.2V curve while keeping margin above BMS low-voltage cutoff.
Part of Battery Bank Sizing