On this page
Conditions that change the calculation:
- Intermittent vs. continuous operation: Thermostatic loads (compressors, heaters) cycle on and off based on ambient temperature, whereas networking, monitoring, and lighting run continuously at fixed power while switched on.
- AC conversion and tare overhead: Running 120V/60Hz AC loads (North America baseline; 230V/50Hz in UK/AU) through an inverter adds conversion losses (typically 10–15%) plus continuous no-load idle tare draw for every hour the inverter remains enabled without an AC load.
- Energy budget vs. concurrent peak: Daily watt-hours (Wh/day) determine battery bank capacity in general battery bank sizing, whereas simultaneous running watts plus motor startup surge determine inverter rating, BMS peak discharge limit, and DC wire/fuse sizing.
Load Classification & Audit Specifications
| Load Category | Power Metric to Record | Duty Cycle Formula / Source | Inverter Loss & Tare | Primary Sizing Output |
|---|---|---|---|---|
| Continuous DC (router, shunt, LED lights) | Measured running W (or V_bus * A_running) |
1.0 (100% while switched on) |
None (direct <=60V DC bus) | Daily Wh, continuous DC amps |
| Intermittent / Thermostatic DC (12V/24V fridge, water pump) | Running W during active compressor/pump cycle | Active_Minutes / Total_Cycle_Minutes (varies with ambient °F / °C) |
None (direct <=60V DC bus) | Daily Wh, cycle peak amps |
| Regulated DC Interface (CPAP via DC-DC converter) | Running W with exact humidifier/heated-tube setting | 1.0 during sleep hours (verify DC input V/A on nameplate) |
None if DC-DC; apply efficiency if on AC | Overnight Wh, voltage-drop-sensitive DC branch |
| AC Appliance via Inverter (120V/60Hz or 230V/50Hz) | Running W and startup surge W from nameplate/watt-meter | Active_Hours * Duty_Cycle |
Divide Wh by inverter efficiency (0.85–0.90); add Idle_W * Idle_Hours |
Daily DC-side Wh, inverter continuous & surge W |
Illustrative Mixed DC and AC Daily Energy Budget
The table below shows a 24-hour energy audit for an off-grid cabin or RV operating on a nominal 12.8V LiFePO4 (or 12.0V AGM) DC bus with a 120V/60Hz AC inverter (note: UK/AU 230V/50Hz inverters follow the same Wh math on the DC side). All wattage, runtime, duty cycle, and efficiency values below are illustrative assumptions; verify actual running watts and idle draw on each device nameplate or an inline meter.
| Load Item | Bus / Interface | Running Power (W) | Active Hours / Day | Duty Cycle | Conversion Factor | Daily Energy (Wh/day) |
|---|---|---|---|---|---|---|
| DC Compressor Fridge | 12V DC | 45 W | 24 h | 0.35 (35%) | 1.00 | 378 Wh |
| LED Cabin Lighting | 12V DC | 24 W | 5 h | 1.00 (100%) | 1.00 | 120 Wh |
| Cellular Router & Monitor | 12V DC | 10 W | 24 h | 1.00 (100%) | 1.00 | 240 Wh |
| CPAP (DC-DC, no humidifier) | 12V -> 24V DC | 20 W | 8 h | 1.00 (100%) | 0.92 (DC-DC eff.) | 174 Wh |
| Laptop & Charger (AC) | 120V/60Hz AC | 65 W | 4 h | 1.00 (100%) | 0.85 (Inverter eff.) | 306 Wh |
| Inverter Idle Tare | 12V DC | 15 W | 8 h (12 h on minus 4 h AC load) | 1.00 (100%) | 1.00 | 120 Wh |
| Total Daily Energy | — | — | — | — | — | 1,338 Wh/day |
Note on CPAP supply calculations: Enabling a heated humidifier or heated hose can raise CPAP running power from ~20 W to 60–90 W. Always check the CPAP power brick or DC converter nameplate for exact input voltage and current requirements, and size the DC branch circuit for low voltage drop.
Converting Daily Wh to Bank Ah by Nominal Voltage
Using the illustrative 1,338 Wh/day total:
Daily_Ah = Total_Daily_Wh / V_nominal
Required_Bank_Ah = Daily_Ah / Usable_DoD
- LiFePO4 (85% default usable DoD; 80–90% range):
- 12.8V nominal:
1,338 / 12.8 = 104.5 Ah/day->104.5 / 0.85 = 123.0 Ahminimum bank (for 1 day of autonomy). - 25.6V nominal:
1,338 / 25.6 = 52.3 Ah/day->52.3 / 0.85 = 61.5 Ahminimum bank. - 51.2V nominal:
1,338 / 51.2 = 26.1 Ah/day->26.1 / 0.85 = 30.7 Ahminimum bank.
- 12.8V nominal:
- AGM / Lead-Acid (50% usable DoD):
- 12.0V nominal:
1,338 / 12.0 = 111.5 Ah/day->111.5 / 0.50 = 223.0 Ahminimum bank. - 24.0V nominal:
1,338 / 24.0 = 55.8 Ah/day->1,338 / (24.0 * 0.50) = 111.5 Ahminimum bank. - 48.0V nominal:
1,338 / 48.0 = 27.9 Ah/day->1,338 / (48.0 * 0.50) = 55.8 Ahminimum bank.
- 12.0V nominal:
Step-by-Step Multi-Load Audit Procedure
- Inventory every load on the <=60V DC bus and AC inverter output. Record the operating voltage (12V, 24V, or 48V nominal DC; 120V/60Hz or 230V/50Hz AC), steady-state running watts, and startup surge watts from the equipment nameplate. If a nameplate lists only maximum amps, measure actual running watts with a clamp meter or inline watt-meter.
- Calculate effective daily Wh for each DC load.
For cycling loads (fridges, fans, pumps), measure run-time vs. off-time over at least one full hour under realistic ambient temperature (DC_Load_Wh = Running_W * Active_Hours * Duty_CycleDuty_Cycle = Run_Minutes / Total_Minutes). - Calculate AC load Wh including inverter efficiency and idle tare.
Check the inverter datasheet for no-load draw (AC_Bank_Wh = (AC_Running_W * Active_Hours * Duty_Cycle) / Inverter_Efficiency Tare_Wh = Inverter_Idle_W * Inverter_Idle_HoursInverter_Idle_W) and efficiency curve at your typical load percentage rather than peak efficiency. - Separate concurrent peak demand from the 24-hour energy total.
Sum the running watts of all loads that can operate simultaneously, then add the single largest motor or compressor startup surge:
UseConcurrent_Peak_W = Sum(Simultaneous_Running_W) + Max_Single_Surge_WConcurrent_Peak_W(converted to DC amps at low-voltage cutoffV_minand inverter efficiency) to verify BMS discharge limits, inverter capacity, and DC overcurrent protection. - Apply temperature and autonomy margins before finalizing bank size.
Multiply
Daily_Ahby your required days of autonomy and divide by usable DoD (85% default for LiFePO4; 50% for AGM/lead-acid) in general battery bank sizing. In cold climates, verify cold-weather capacity derating and flag charging limits at <=+5°C (41°F) with a hard charge block at <=0°C (32°F) unless using self-heated packs.
Sign-Off Criteria
- Every DC load (12V/24V/48V nominal, strictly <=60V DC bus) and AC load (120V/60Hz or 230V/50Hz) uses measured or verified running watts rather than fuse-rating maximums.
- Intermittent and thermostatic loads explicitly apply a documented duty cycle (
0.0–1.0). - AC loads include both inverter conversion efficiency and
Inverter_Idle_W * Inverter_Idle_Hours. - Total daily energy (
Wh/dayandAh/day) is reported separately fromConcurrent_Peak_W. - Final bank Ah reflects chemistry-specific usable DoD (80–90% default 85% for LiFePO4; 50% for AGM/lead-acid).
Real Failure Modes
- Summing nameplate maximums for daily Wh: Treating a 10A-fused DC port or a 15A AC nameplate rating as continuous 24-hour draw inflates the calculated battery bank by 2x–5x, adding unnecessary cost and weight.
- Ignoring inverter idle tare: Leaving a 2,000W inverter powered on without AC load for 24 hours/day at 20W no-load draw consumes
480 Wh/day—often more energy than the lighting, router, and fridge combined. - Static duty cycle assumptions in hot weather: A DC compressor fridge running a 30% duty cycle at 20°C (68°F) can climb above 65% duty cycle at 35°C (95°F), doubling its daily Wh consumption and depleting an unbuffered bank overnight.
- Using daily average watts to size the inverter and BMS: A system averaging 60 W across 24 hours (
1,440 Wh/day) still trips a 100A BMS or shuts down an undersized inverter if a 1,200W AC microwave and a compressor startup surge occur simultaneously.
Part of Battery Bank Sizing