On this page

Use the bank capacity established in general bank sizing as your starting baseline, then test whether the chosen nominal voltage (12V, 24V, or 48V DC, strictly <=60V DC) and BMS or chemistry discharge limits can carry the simultaneous load without tripping protection or collapsing bus voltage.


Core Operating Baselines and Voltage Boundaries

Battery-side discharge current rises as terminal voltage falls. Sizing at nominal voltage (12.8V, 25.6V, or 51.2V for LiFePO4; 12.0V, 24.0V, or 48.0V for AGM/lead-acid) underestimates real current at the end of a discharge cycle or during a heavy motor startup sag.

Nominal System Voltage Chemistry Nominal Voltage Typical Absorb / Max Charge Illustrative V_min Under Load Typical Continuous C-Rate Ceiling Notes
12V LiFePO4 12.8V 14.2–14.6V 10.5–11.5V 0.5C–1.0C (per BMS/cell datasheet) Usable DoD 80–90% (default 85%)
12V AGM / Lead-Acid 12.0V 14.4–14.8V 10.5–11.0V 0.2C–0.5C (Peukert-limited) Usable DoD 50%
24V LiFePO4 25.6V 28.4–29.2V 21.0–23.0V 0.5C–1.0C (per BMS/cell datasheet) Usable DoD 80–90% (default 85%)
24V AGM / Lead-Acid 24.0V 28.8–29.6V 21.0–22.0V 0.2C–0.5C (Peukert-limited) Usable DoD 50%
48V LiFePO4 51.2V 56.8–58.4V 42.0–46.0V 0.5C–1.0C (per BMS/cell datasheet) Usable DoD 80–90% (default 85%); <=60V DC bus
48V AGM / Lead-Acid 48.0V 57.6–59.2V 42.0–44.0V 0.2C–0.5C (Peukert-limited) Usable DoD 50%; keep charging <=60V DC

Check the inverter low-voltage cutoff (LVD) setting, battery BMS under-voltage protection threshold, and battery datasheet maximum continuous and peak discharge ratings before finalizing V_min.


Plain-Text Discharge Current Formulas

Calculate AC inverter demand and native DC demand separately, then sum them at the battery terminals:

  1. Inverter DC Continuous Current: I_inv_cont = P_ac_cont / (V_min * eff_inv)

    • P_ac_cont: Total concurrent AC load in watts (120V/60Hz North America baseline; 230V/50Hz UK/AU regional AC).
    • eff_inv: Inverter conversion efficiency at that load point from the inverter datasheet (illustrative default: 0.85 to 0.90).
  2. Native DC Continuous Current: I_dc_cont = P_dc_cont / V_min

    • P_dc_cont: Total concurrent DC load in watts (refrigeration, pumps, lighting, communications, CPAP DC supply).
    • If a DC load is rated in amps at nominal voltage rather than watts, convert to watts first (W = A_rated * V_rated) for regulated DC-DC loads, or use rated amps directly for resistive loads.
  3. Total Continuous Battery-Side Current: I_total_cont = I_inv_cont + I_dc_cont

  4. Peak / Surge Battery-Side Current: I_total_peak = (P_ac_surge / (V_min_sag * eff_surge)) + I_dc_surge

    • P_ac_surge: Highest simultaneous AC starting surge plus running AC loads (in watts), capped by the inverter's rated surge output.
    • V_min_sag: Minimum battery terminal voltage during the surge pulse (always <= V_min).
    • Record the required peak duration in seconds (for example, 0.5–3 seconds for compressor/pump locked-rotor startup, or 5–15 seconds for heavy inductive/resistive overlap).
  5. Bank C-Rate Verification: C_cont = I_total_cont / Ah_bank C_peak = I_total_peak / Ah_bank

    • For parallel strings (N_p batteries in parallel), do not assume exact 50/50 current sharing. Apply a per-string imbalance margin (illustrative 20–25%): I_per_string = (I_total / N_p) * 1.25

Worked Example: 24V LiFePO4 Multi-Load Budget

Illustrative system assumptions (verify all ratings against your equipment nameplates):

  • Bank: 25.6V 200Ah LiFePO4 (5,120 Wh nominal), configured as two 25.6V 100Ah batteries in parallel (2P), each with a 100A continuous / 200A 3-second peak BMS.
  • Inverter: 2,000W continuous / 4,000W surge (120V/60Hz AC output; same DC math applies to 230V/50Hz units with equivalent watt/efficiency ratings).
  • Illustrative inverter efficiency: 0.88 continuous, 0.85 at surge.
  • Illustrative V_min (and surge V_min_sag): 22.0V DC.
  • Concurrent continuous loads: 1,600W AC + 180W DC.
  • Peak event: 2,400W motor startup surge on top of 1,600W AC (4,000W total AC surge for 2 seconds) + 180W DC.

Calculations:

  • I_inv_cont = 1,600W / (22.0V * 0.88) = 82.6 A
  • I_dc_cont = 180W / 22.0V = 8.2 A
  • I_total_cont = 82.6 A + 8.2 A = 90.8 A
  • C_cont = 90.8 A / 200 Ah = 0.45C
  • I_inv_surge = 4,000W / (22.0V * 0.85) = 213.9 A
  • I_total_peak = 213.9 A + 8.2 A = 222.1 A (for 2 seconds)
  • C_peak = 222.1 A / 200 Ah = 1.11C
  • Per-string share with 25% imbalance margin (2P):
    • Continuous per battery: (90.8 A / 2) * 1.25 = 56.8 A (within 100A BMS continuous rating)
    • Peak per battery: (222.1 A / 2) * 1.25 = 138.8 A for 2 seconds (within 200A 3-second BMS peak rating)

Step-by-Step Sizing and Verification Procedure

  1. Inventory Concurrent Continuous Loads: List every AC and DC load that can run simultaneously for 15 minutes or longer. Do not sum loads that are mutually exclusive unless an interlock prevents simultaneous operation.
  2. Identify Worst-Case Peak Events and Durations: Find the largest motor, compressor, pump, or inverter-charger transfer surge that can occur while base loads are active. Record both total watts and duration in seconds from the appliance and inverter datasheets.
  3. Select V_min and Inverter Efficiency: Pull the inverter's low-voltage cutoff and efficiency curve at full load. If the inverter manual specifies a lower cutoff than the battery BMS, use the higher of the two cutoffs (or the voltage at which the inverter still holds regulation before tripping).
  4. Compute I_total_cont and I_total_peak: Run the formulas above at V_min. Compare I_total_cont against 1.25x continuous conductor/fuse sizing rules (for loads >=3 hours) and verify the main DC bus voltage drop stays within <=3% for critical circuits.
  5. Check Bank C-Rate and BMS Limits:
    • LiFePO4: Verify I_total_cont <= combined BMS continuous rating (with parallel imbalance margin) and I_total_peak + duration <= BMS peak trip curve.
    • AGM / Lead-Acid: Apply the Peukert exponent from the battery datasheet when C_cont exceeds 0.2C. High discharge rates reduce effective amp-hour capacity and accelerate terminal voltage sag.
  6. Verify Temperature Derating: Check the battery datasheet discharge curve at your lowest expected operating ambient temperature (e.g., 32°F / 0°C or 14°F / -10°C). Cold cells exhibit higher internal resistance, causing deeper V_min_sag under peak load and earlier low-voltage inverter trips. (Separately, flag <=41°F / +5°C to verify BMS minimum charge temperature and hard-block charging at <=32°F / 0°C unless self-heated.)
  7. Coordinate Protection and Conductors: Confirm the main battery fuse time-current curve clears faults without nuisance-tripping on I_total_peak for its required duration, fuse voltage rating >= maximum charging voltage (e.g., >58.4V on a 51.2V LiFePO4 bank), and cable ampacity (75°C copper, 0.02097 ohm·mm²/m, AWG / mm²) >= fuse rating.

Sign-Off Criteria

A battery bank passes discharge-current verification only when every condition below is met:

  • I_total_cont at V_min is <= the bank's continuous discharge rating (and <= per-string BMS continuous rating divided by 1.25 imbalance factor for parallel banks).
  • I_total_peak and its duration in seconds fall inside all three limits simultaneously: inverter surge rating, BMS peak current/duration window, and main fuse time-current non-trip curve.
  • Voltage sag at I_total_peak remains above the inverter low-voltage cutoff and any critical DC load brownout threshold (such as CPAP DC power supplies).
  • Main DC conductors and terminals are rated for >=1.25x continuous current (>=3 hours) and <=3% voltage drop on critical runs.

Real Failure Modes

  • BMS Instantaneous Trip on Inverter Capacitor Precharge or Motor Surge: A single 12.8V 100Ah LiFePO4 battery with a 100A BMS may advertise "200A peak for 3 seconds," yet trip in <50 milliseconds when an inverter's input capacitors charge or a 1,500W inductive load starts at low state of charge. Always check both the short-circuit/microsecond threshold and the multi-second surge rating.
  • Parallel String Current Imbalance: Unequal cable lengths, corroded lugs, or mismatched state of charge between parallel 12V, 24V, or 48V batteries can push 65–75% of I_total_peak through one battery, tripping its BMS and cascading the full load onto the remaining strings until the entire bank shuts down.
  • Peukert Collapse on AGM / Lead-Acid Banks: Drawing 0.5C from a 12.0V or 24.0V AGM bank rated at the 20-hour (0.05C) rate can cut usable capacity by 30–40% and pull terminal voltage below 10.5V / 21.0V mid-cycle, causing premature inverter LVD even though amp-hour math at 0.05C looked adequate.
  • Cold-Weather Voltage Sag: Operating a LiFePO4 or AGM bank near or below 32°F (0°C) increases internal impedance. Even when discharging is permitted down to -4°F (-20°C), a heavy I_total_peak pulse can drop terminal voltage below V_min and trip the inverter while the battery still has >40% state of charge.
  • Sizing at Nominal Voltage Instead of V_min: Calculating a 2,400W inverter load at 51.2V (46.9A before efficiency) instead of 44.0V at 0.85 efficiency (64.2A) under-sizes conductors, trips undersized breakers, and overheats 75°C-rated terminals during extended low-SoC runs.