On this page

In battery bank sizing, conversion and idle losses sit between your load list and your usable battery depth of discharge (DoD). On a 120V/60Hz North American AC output (or 230V/50Hz UK/AU output), an inverter converts DC battery power to AC with conversion losses included in loaded efficiency, plus no-load tare only while enabled without an AC load. On the DC side, any load fed through a voltage regulator, buck/boost converter, or isolated DC-DC stabilizer incurs its own conversion efficiency penalty before the battery bank sees the load.


Conversion Stage Specifications and Nameplate Parameters

Check each device's datasheet or nameplate for the exact parameters below before finalizing the bank-wide energy budget. For detailed inverter efficiency curves, surge ratings, and standby search-mode behavior, see inverter efficiency and idle draw.

Energy Budget Branch Typical Input / Output Parameters to Check on Nameplate Loss Mechanism
AC Inverter Load 12.8V / 25.6V / 51.2V LiFePO4 (or 12.0V / 24.0V / 48.0V AGM) to 120V/60Hz AC (230V/50Hz UK/AU) Continuous efficiency curve (eta_inv) at expected load fraction, not just peak Switching, transformer, and thermal losses proportional to AC load
Inverter No-Load Idle Draw DC bus to inverter control & output stage No-load power (P_idle in W or standby A at nominal V) and unloaded powered hours (t_idle) Continuous tare draw while the inverter is switched on at 0W AC load
Regulated DC-DC Branch 24V or 48V bank to 12V regulated DC (or 12V stabilized output for sensitive loads) Converter efficiency (eta_dcdc), continuous output A/W, and quiescent no-load draw (P_q_dcdc) Buck/boost switching and regulation losses across the DC-DC stage
Direct Unregulated DC Branch Direct 12.8V / 25.6V / 51.2V bus to native-voltage DC loads Operating voltage window vs. bank absorb/cutoff range No converter loss; only round-trip DC wiring voltage drop (<=3% critical, <=10% non-critical)

Bank-Wide Energy Budget Formulas

Use plain-text watt-hour accounting so all branches add cleanly on the battery side before applying chemistry DoD limits:

1. AC Inverter Battery Demand (Wh):
   E_ac_batt = (E_ac_load / eta_inv) + (P_idle * t_idle)

2. Regulated DC-DC Branch Battery Demand (Wh):
   E_dc_reg_batt = (E_dc_reg_load / eta_dcdc) + (P_q_dcdc * t_dcdc_idle)

3. Direct Unregulated DC Branch Battery Demand (Wh):
   E_dc_direct_batt = E_dc_direct_load

4. Total Daily Battery-Side Demand (Wh):
   E_total_batt = E_ac_batt + E_dc_reg_batt + E_dc_direct_batt

5. Required Nameplate Bank Capacity (Wh):
   C_nameplate_Wh = E_total_batt / DoD_usable
  • LiFePO4 baseline: 12.8V / 25.6V / 51.2V nominal (typical absorb 14.2–14.6V / 28.4–29.2V / 56.8–58.4V), usable DoD 80–90% (default 85%, or 0.85).
  • AGM / lead-acid baseline: 12.0V / 24.0V / 48.0V nominal, usable DoD 50% (0.50).

Worked Example (Illustrative Assumptions)

Assume a 25.6V nominal LiFePO4 bank (85% usable DoD) powering a small cabin/RV daily budget with 120V/60Hz AC output (same calculation structure applies to 230V/50Hz UK/AU units using the unit's nameplate eta_inv and P_idle):

  • AC load (illustrative): 900 Wh/day at 120V/60Hz AC; inverter nameplate efficiency at typical load = 88% (0.88), no-load idle draw = 18W, inverter powered 24 hours/day, including 18 hours without an AC load.
    • E_ac_batt = (900 / 0.88) + (18 * 18) = 1,022.7 + 324.0 = 1,346.7 Wh
  • Regulated DC-DC branch (illustrative): 24V-to-12V buck converter feeding 12V DC appliances and a CPAP DC power supply totaling 420 Wh/day; converter efficiency = 92% (0.92), quiescent draw = 1.5W, powered 24 hours/day including 12 hours without a load.
    • E_dc_reg_batt = (420 / 0.92) + (1.5 * 12) = 456.5 + 18.0 = 474.5 Wh
  • Direct 24V DC branch (illustrative): Native 24V lighting and ventilation totaling 200 Wh/day.
    • E_dc_direct_batt = 200.0 Wh
  • Total battery-side demand:
    • E_total_batt = 1,346.7 + 474.5 + 200.0 = 2,021.2 Wh/day
    • Raw load sum was 900 + 420 + 200 = 1,520 Wh/day; conversion and idle losses add 501.2 Wh/day (+33.0%).
  • Required nameplate LiFePO4 capacity (at 85% usable DoD):
    • C_nameplate_Wh = 2,021.2 / 0.85 = 2,377.9 Wh (approx. 92.9 Ah at 25.6V nominal).

Step-by-Step Sizing Procedure

  1. Separate the load list by bus and conversion stage. Group loads into AC inverter loads (120V/60Hz or 230V/50Hz), regulated DC-DC loads (such as 24V/48V-to-12V step-down branches or stabilized 12V-to-12V outputs), and direct native-voltage DC loads.
  2. Pull part-load efficiency from equipment datasheets. Record eta_inv and eta_dcdc at the actual operating load wattage rather than the peak efficiency headline. Refer to inverter efficiency and idle draw when evaluating low-load inverter efficiency and eco/search modes.
  3. Count unloaded powered hours (t_idle). Multiply inverter P_idle by the hours the inverter remains switched on without an AC load. Include DC-DC converter quiescent draw (P_q_dcdc) for hours the converters are energized without a load.
  4. Compute total battery-side Wh and apply DoD. Sum all branches to get E_total_batt, then divide by 0.85 (LiFePO4 default) or 0.50 (AGM/lead-acid) to determine minimum nameplate Wh in battery bank sizing.
  5. Check cold-temperature and low-voltage margins. If ambient temperatures drop to <=+5°C (41°F), verify the battery BMS minimum charge temperature (some commercial packs lock out charging at +5°C / 41°F, and charging is hard-blocked at <=0°C / 32°F unless self-heated), as reduced charge acceptance leaves less margin for unbudgeted idle draw.

Sign-Off Criteria

  • Every AC load watt-hour figure is divided by the inverter's realistic operating-point efficiency (eta_inv), not 1.0 or peak catalog efficiency.
  • Inverter no-load idle draw (P_idle * t_idle) is explicitly added for the daily powered duration without an AC load.
  • Every regulated DC-DC branch (step-down, step-up, or isolated stabilizer) includes converter efficiency (eta_dcdc) and quiescent draw for energized hours without a load.
  • Total battery-side Wh (E_total_batt) is divided by chemistry usable DoD (80–90% for LiFePO4, 50% for AGM/lead-acid) before selecting bank Ah and nominal voltage (<=60V DC).

Real Failure Modes

  • Oversized inverter running 24/7 for tiny AC loads: A high-capacity inverter with 25–40W no-load idle draw consumes 600–960 Wh over 24 hours without an AC load, often exceeding the actual AC load and draining small banks overnight.
  • Sizing with peak efficiency instead of light-load efficiency: Inverters and DC-DC converters rated at 92–95% peak efficiency frequently operate at 70–80% efficiency below 10% of rated output, understating battery draw during overnight baseline loads.
  • Unchecked DC-DC converter standby drain: Leaving a 24V-to-12V or 48V-to-12V converter permanently wired to the battery bus without a switch or low-quiescent spec causes steady parasitic discharge during multi-day storage.
  • Skipping the usable DoD divisor after adding losses: Calculating E_total_batt accurately but buying a battery bank equal to E_total_batt in nameplate Wh causes premature BMS low-voltage cutoff on LiFePO4 or accelerated sulfation on AGM/lead-acid.