On this page

For general shunt wiring, zero-current calibration, and chemistry-neutral monitor basics, see Battery Monitor Setup.

Conditions That Change These Settings

  • Chemistry (Flooded vs. AGM/Gel): Flooded lead-acid (FLA) banks lose more energy to gassing and internal resistance than sealed AGM or gel banks, requiring a higher Peukert exponent (1.20 to 1.30) and lower charge efficiency (80% to 85%).
  • Bank Age and Sulfation: Aged or partially sulfated banks draw higher finishing current at full charge and lose recharge efficiency; raise tail current to 3.0% to 4.0% of C20 and lower charge efficiency by 3% to 5% if the bank stalls before syncing.
  • Ambient Temperature: Lead-acid chargers use temperature compensation (typically -3 mV to -5 mV/°C per 2.0V cell). In hot environments above 35°C (95°F), compensated absorption voltage drops and can fall below a fixed charged voltage threshold, preventing 100% sync.
  • Solar Variability: On MPPT solar systems where passing clouds cause brief current drops during absorption, extend the charged detection time from 3 minutes to 5–10 minutes to prevent premature 100% sync.

Lead-Acid Monitor Parameter Baselines

Verify exact absorption, float, and temperature-compensation values on the battery datasheet and charger nameplate before programming. All 48.0V bank parameters below remain strictly at or below 60V DC.

Parameter Flooded Lead-Acid (FLA) AGM (Absorbed Glass Mat) Gel Notes / Adjustment Basis
Nominal Voltage 12.0V / 24.0V 12.0V / 24.0V / 48.0V 12.0V / 24.0V / 48.0V Keep DC bus strictly <=60V DC
Capacity Rating Basis C20 (20-hour rate) C20 (20-hour rate) C20 (20-hour rate) Use nameplate C20 Ah at 25°C (77°F)
Peukert Exponent (n) 1.20 to 1.30 1.15 to 1.25 1.10 to 1.20 Calculate from C20 and C5 ratings if published
Charge Efficiency Factor (CEF) 80% to 85% 85% to 90% 85% to 90% Reduce by 3% to 5% for aged banks
Tail Current (% of C20) 2.0% to 4.0% 1.5% to 2.5% 1.5% to 2.0% Higher values prevent sync hang on older FLA
Charged Detection Time 3 to 5 min 3 to 5 min 3 to 5 min Increase to 5 to 10 min for variable solar
Usable DoD / Low-SoC Alarm 50% DoD (50% SoC floor) 50% DoD (50% SoC floor) 50% DoD (50% SoC floor) Set pre-alarm at 55% to 60% SoC

Voltage Thresholds by System Voltage (at 25°C / 77°F)

Set V_charged above the charger's float voltage and 0.2V to 0.4V (12V-scaled) below the charger's absorption voltage.

Nominal Bank Voltage Typical Absorb Range Typical Float Range Recommended V_charged
12.0V 14.2V to 14.8V 13.2V to 13.8V 13.9V to 14.4V
24.0V 28.4V to 29.6V 26.4V to 27.6V 27.8V to 28.8V
48.0V 56.8V to 58.8V 52.8V to 55.2V 55.6V to 57.6V

Peukert and Charge Efficiency Math (Plain-Text Formulas)

Shunt monitors apply the Peukert exponent to adjust displayed discharge current for capacity loss at high rates:

I_rated = C20 / 20 I_effective = I_actual * (I_actual / I_rated)^(n - 1)

To derive the Peukert exponent n directly from two datasheet discharge ratings (C20 over t1 = 20 h at current I1, and C5 over t2 = 5 h at current I2):

n = (log10(t1) - log10(t2)) / (log10(I2) - log10(I1))

During recharging, the monitor multiplies measured charge amp-hours by the Charge Efficiency Factor (CEF):

Ah_recovered = Ah_input * (CEF / 100)

Illustrative Calculation (12.0V 200 Ah AGM Bank)

Assume a 12.0V, 200 Ah (C20) AGM bank (I_rated = 200 / 20 = 10 A), Peukert exponent n = 1.15, and CEF = 88%, running a continuous 50 A DC inverter load:

  1. Effective discharge rate: I_effective = 50 * (50 / 10)^(1.15 - 1) = 50 * 5^0.15 = 63.7 A.
  2. Time to 50% usable DoD (100 Ah usable): 100 Ah / 63.7 A = 1.57 hours (versus 2.00 hours if erroneously left at n = 1.00).
  3. Recharge input required to restore 100 Ah: 100 Ah / 0.88 = 113.6 Ah of charger output before the monitor reaches 100% SoC.

Step-by-Step Configuration Procedure

  1. Verify Bank Nameplate and Wiring: Confirm total C20 capacity (add parallel strings, keep series voltage), chemistry type, and that every negative load and charger return passes through the shunt's load side (B- to battery negative only).
  2. Program Capacity and Peukert Exponent: Enter the C20 Ah rating and set n from the table above or the datasheet C20/C5 calculation.
  3. Set Charge Efficiency Factor: Enter 80% to 85% for flooded banks or 85% to 90% for AGM/gel banks.
  4. Match V_charged to the Charger: Read the charger's 25°C (77°F) absorption and float setpoints. Set V_charged midway to 0.2V–0.4V (12V-scaled) below absorption, ensuring it stays at least 0.3V (12V), 0.6V (24V), or 1.2V (48V) above float.
  5. Set Tail Current and Detection Time: Calculate Tail Current (A) = C20 * (Tail % / 100). Enter 3 to 5 minutes for AC/alternator charging or 5 to 10 minutes for solar MPPT charging.
  6. Set Alarm Floor and Zero Shunt: Configure the low-SoC alarm at 50% (or pre-alarm at 55%–60%). Disconnect all loads and chargers and run the monitor's zero-current calibration.

Sign-Off Criteria

  • Zero-Current Baseline: With all DC loads and charging sources isolated, the monitor reads 0.0 A (±0.1 A).
  • Accurate Sync Behavior: During a full charge cycle, SoC remains below 100% throughout bulk and early absorption, syncing to 100% only after bank voltage holds above V_charged and charge current drops below the tail-current threshold for the full detection window.
  • Float Immunity: When the charger transitions to float, SoC does not re-trigger or falsely jump to 100% if absorption was interrupted.
  • Load-Rate Alignment: Under a steady high-rate DC load, the monitor's time-remaining estimate reflects Peukert derating rather than linear C20 / I_actual math.

Common Failure Modes

  • Leaving LiFePO4 Defaults Active (n = 1.05, CEF = 99%): The monitor ignores high-rate sag and recharge losses, displaying 65%–70% SoC when the lead-acid bank has already reached its 50% usable DoD limit, accelerating plate sulfation.
  • Premature 100% Sync on Solar: Setting V_charged too close to float or using a 1-minute detection time lets passing clouds drop charge current below tail current while voltage briefly lingers above V_charged, resetting SoC to 100% on a partially charged bank.
  • Chronic Sync Failure in Hot Weather: High ambient temperatures (>35°C / 95°F) cause temperature-compensated chargers to lower absorption voltage below a static V_charged setting, causing SoC to drift steadily downward over multiple cycles.
  • Tail Current Set Too Low for Aged Flooded Banks: Older flooded cells with elevated self-discharge may never taper below 1.0% of C20, preventing the monitor from ever syncing to 100% until tail current is raised to 3.0%–4.0%.