On this page
For general shunt wiring, zero-current calibration, and chemistry-neutral monitor basics, see Battery Monitor Setup.
Conditions That Change These Settings
- Chemistry (Flooded vs. AGM/Gel): Flooded lead-acid (FLA) banks lose more energy to gassing and internal resistance than sealed AGM or gel banks, requiring a higher Peukert exponent (
1.20 to 1.30) and lower charge efficiency (80% to 85%). - Bank Age and Sulfation: Aged or partially sulfated banks draw higher finishing current at full charge and lose recharge efficiency; raise tail current to
3.0% to 4.0%ofC20and lower charge efficiency by3% to 5%if the bank stalls before syncing. - Ambient Temperature: Lead-acid chargers use temperature compensation (typically
-3 mV to -5 mV/°Cper 2.0V cell). In hot environments above35°C (95°F), compensated absorption voltage drops and can fall below a fixed charged voltage threshold, preventing 100% sync. - Solar Variability: On MPPT solar systems where passing clouds cause brief current drops during absorption, extend the charged detection time from
3 minutesto5–10 minutesto prevent premature 100% sync.
Lead-Acid Monitor Parameter Baselines
Verify exact absorption, float, and temperature-compensation values on the battery datasheet and charger nameplate before programming. All 48.0V bank parameters below remain strictly at or below 60V DC.
| Parameter | Flooded Lead-Acid (FLA) | AGM (Absorbed Glass Mat) | Gel | Notes / Adjustment Basis |
|---|---|---|---|---|
| Nominal Voltage | 12.0V / 24.0V | 12.0V / 24.0V / 48.0V | 12.0V / 24.0V / 48.0V | Keep DC bus strictly <=60V DC |
| Capacity Rating Basis | C20 (20-hour rate) |
C20 (20-hour rate) |
C20 (20-hour rate) |
Use nameplate C20 Ah at 25°C (77°F) |
Peukert Exponent (n) |
1.20 to 1.30 |
1.15 to 1.25 |
1.10 to 1.20 |
Calculate from C20 and C5 ratings if published |
| Charge Efficiency Factor (CEF) | 80% to 85% |
85% to 90% |
85% to 90% |
Reduce by 3% to 5% for aged banks |
Tail Current (% of C20) |
2.0% to 4.0% |
1.5% to 2.5% |
1.5% to 2.0% |
Higher values prevent sync hang on older FLA |
| Charged Detection Time | 3 to 5 min |
3 to 5 min |
3 to 5 min |
Increase to 5 to 10 min for variable solar |
| Usable DoD / Low-SoC Alarm | 50% DoD (50% SoC floor) |
50% DoD (50% SoC floor) |
50% DoD (50% SoC floor) |
Set pre-alarm at 55% to 60% SoC |
Voltage Thresholds by System Voltage (at 25°C / 77°F)
Set V_charged above the charger's float voltage and 0.2V to 0.4V (12V-scaled) below the charger's absorption voltage.
| Nominal Bank Voltage | Typical Absorb Range | Typical Float Range | Recommended V_charged |
|---|---|---|---|
| 12.0V | 14.2V to 14.8V |
13.2V to 13.8V |
13.9V to 14.4V |
| 24.0V | 28.4V to 29.6V |
26.4V to 27.6V |
27.8V to 28.8V |
| 48.0V | 56.8V to 58.8V |
52.8V to 55.2V |
55.6V to 57.6V |
Peukert and Charge Efficiency Math (Plain-Text Formulas)
Shunt monitors apply the Peukert exponent to adjust displayed discharge current for capacity loss at high rates:
I_rated = C20 / 20
I_effective = I_actual * (I_actual / I_rated)^(n - 1)
To derive the Peukert exponent n directly from two datasheet discharge ratings (C20 over t1 = 20 h at current I1, and C5 over t2 = 5 h at current I2):
n = (log10(t1) - log10(t2)) / (log10(I2) - log10(I1))
During recharging, the monitor multiplies measured charge amp-hours by the Charge Efficiency Factor (CEF):
Ah_recovered = Ah_input * (CEF / 100)
Illustrative Calculation (12.0V 200 Ah AGM Bank)
Assume a 12.0V, 200 Ah (C20) AGM bank (I_rated = 200 / 20 = 10 A), Peukert exponent n = 1.15, and CEF = 88%, running a continuous 50 A DC inverter load:
- Effective discharge rate:
I_effective = 50 * (50 / 10)^(1.15 - 1) = 50 * 5^0.15 = 63.7 A. - Time to 50% usable DoD (
100 Ahusable):100 Ah / 63.7 A = 1.57 hours(versus2.00 hoursif erroneously left atn = 1.00). - Recharge input required to restore
100 Ah:100 Ah / 0.88 = 113.6 Ahof charger output before the monitor reaches 100% SoC.
Step-by-Step Configuration Procedure
- Verify Bank Nameplate and Wiring: Confirm total
C20capacity (add parallel strings, keep series voltage), chemistry type, and that every negative load and charger return passes through the shunt's load side (B-to battery negative only). - Program Capacity and Peukert Exponent: Enter the
C20Ah rating and setnfrom the table above or the datasheetC20/C5calculation. - Set Charge Efficiency Factor: Enter
80% to 85%for flooded banks or85% to 90%for AGM/gel banks. - Match
V_chargedto the Charger: Read the charger's 25°C (77°F) absorption and float setpoints. SetV_chargedmidway to0.2V–0.4V(12V-scaled) below absorption, ensuring it stays at least0.3V(12V),0.6V(24V), or1.2V(48V) above float. - Set Tail Current and Detection Time: Calculate
Tail Current (A) = C20 * (Tail % / 100). Enter3 to 5 minutesfor AC/alternator charging or5 to 10 minutesfor solar MPPT charging. - Set Alarm Floor and Zero Shunt: Configure the low-SoC alarm at
50%(or pre-alarm at55%–60%). Disconnect all loads and chargers and run the monitor's zero-current calibration.
Sign-Off Criteria
- Zero-Current Baseline: With all DC loads and charging sources isolated, the monitor reads
0.0 A(±0.1 A). - Accurate Sync Behavior: During a full charge cycle, SoC remains below
100%throughout bulk and early absorption, syncing to100%only after bank voltage holds aboveV_chargedand charge current drops below the tail-current threshold for the full detection window. - Float Immunity: When the charger transitions to float, SoC does not re-trigger or falsely jump to
100%if absorption was interrupted. - Load-Rate Alignment: Under a steady high-rate DC load, the monitor's time-remaining estimate reflects Peukert derating rather than linear
C20 / I_actualmath.
Common Failure Modes
- Leaving LiFePO4 Defaults Active (
n = 1.05,CEF = 99%): The monitor ignores high-rate sag and recharge losses, displaying65%–70%SoC when the lead-acid bank has already reached its50%usable DoD limit, accelerating plate sulfation. - Premature 100% Sync on Solar: Setting
V_chargedtoo close to float or using a1-minutedetection time lets passing clouds drop charge current below tail current while voltage briefly lingers aboveV_charged, resetting SoC to100%on a partially charged bank. - Chronic Sync Failure in Hot Weather: High ambient temperatures (
>35°C / 95°F) cause temperature-compensated chargers to lower absorption voltage below a staticV_chargedsetting, causing SoC to drift steadily downward over multiple cycles. - Tail Current Set Too Low for Aged Flooded Banks: Older flooded cells with elevated self-discharge may never taper below
1.0%ofC20, preventing the monitor from ever syncing to100%until tail current is raised to3.0%–4.0%.