On this page
For overall system topology—including parallel and series-parallel tradeoffs—see Bank Design.
When Series Wiring Is the Right Choice (and What Changes It)
Use series wiring when your DC bus or inverter requires 24V or 48V nominal (for example, to feed a North America 120V/60Hz AC inverter or a UK/AU 230V/50Hz AC inverter at lower DC current) and you are building the bank from lower-voltage discrete batteries.
Three conditions change whether series wiring is viable:
- BMS series-voltage rating (LiFePO4): Every battery in a series string must have an internal BMS explicitly rated on its nameplate for the full bank voltage. When one BMS opens during a fault or high-voltage cutoff, the full string voltage appears across its MOSFETs. Many 12.8V LiFePO4 batteries are rated for 1S or 2S maximum (up to 29.2V) and suffer permanent BMS damage if wired 4S (up to 58.4V).
- Native high-voltage availability: For a 48V nominal (51.2V LiFePO4) bus, a native 51.2V battery or parallel 51.2V units eliminates inter-battery series drift. Use 4 x 12.8V or 2 x 25.6V units in series only when each unit is rated for 48V-class series operation and you have a plan to monitor or balance the string.
- Unit matching: Every battery in the string must share the same chemistry, nominal voltage, Ah rating, age, and state of charge before connection.
Series Configuration Specifications (<=60V DC Bus)
All battery and DC bus operating and charging voltages must remain strictly <=60V DC.
| Target Nominal Bus | Typical Series Arrangement | Nominal Bank Voltage | Typical Absorb Voltage | Usable DoD | Bank Ah & Continuous Current |
|---|---|---|---|---|---|
| 12V (AGM / Lead-Acid) | 2 x 6.0V in series | 12.0V | 14.4V–14.8V (check nameplate) | 50% | Equal to 1 unit |
| 24V (AGM / Lead-Acid) | 2 x 12.0V in series | 24.0V | 28.8V–29.6V (check nameplate) | 50% | Equal to 1 unit |
| 24V (LiFePO4) | 2 x 12.8V in series | 25.6V | 28.4V–29.2V | 80%–90% (85% default) | Equal to 1 unit |
| 48V (AGM / Lead-Acid) | 4 x 12.0V or 2 x 24.0V in series | 48.0V | 57.6V–59.2V (strictly <=60V DC) | 50% | Equal to 1 unit |
| 48V (LiFePO4) | 4 x 12.8V or 2 x 25.6V in series | 51.2V | 56.8V–58.4V | 80%–90% (85% default) | Equal to 1 unit |
Sizing and Rating Formulas (Plain Text)
V_nominal_bank = N_series x V_nominal_unitV_max_charge = N_series x V_absorb_unitAh_bank = Ah_unit(single series string)Wh_total = V_nominal_bank x Ah_unitWh_usable = Wh_total x DoD(0.85default for LiFePO4;0.50for AGM/lead-acid)I_continuous_max = I_unit_continuous(governed by the lowest-rated unit or BMS in the string)
Illustrative Example: Four 12.8V 100Ah LiFePO4 batteries (each rated on its nameplate for 4S series operation, 100A continuous BMS, 14.4V absorb) wired in series yield:
V_nominal_bank = 4 x 12.8V = 51.2VV_max_charge = 4 x 14.4V = 57.6VAh_bank = 100AhWh_total = 51.2V x 100Ah = 5,120WhWh_usable = 5,120Wh x 0.85 = 4,352WhI_continuous_max = 100A(5,120Wnominal DC)
Protection, Cable, and Temperature Baselines
- Fuse voltage and interrupting rating: Verify
V_fuse_max >= V_max_chargeandprospective_fault_current <= fuse_AICat operating voltage. A 51.2V LiFePO4 bank charging to 58.4V exceeds 58V-rated terminal fuses; use fuses rated >=70V or >=80V DC (such as Class T) on 48V-class banks, and keepfuse_ampacity <= cable_ampacity. - Cable sizing: Size inter-battery jumpers and main bank leads for
>= 1.25xcontinuous current (>=3 hours) and<= 3%voltage drop on critical DC runs using round-trip length (2 x one-way) and 75°C copper resistivity (0.02097 ohm*mm²/m). Honor terminal temperature limits (typically 75°C) and avoid SAE J1128 thin-wall automotive or copper-clad aluminum (CCA) cable. - Cold charging: Flag ambient or cell temperatures
<= +5°C (41°F)to verify the BMS minimum charge temperature on the equipment nameplate (some commercial packs lock out charging at+5°C). Hard-block charging at<= 0°C (32°F)unless the batteries are equipped with an integrated self-heating system.
Step-by-Step Series Wiring Procedure
- Confirm nameplate series limits: Check each battery's datasheet or label for maximum allowed series count (e.g.,
2S maxvs4S max) and maximum charge voltage. - Pre-charge and match every unit individually: Charge each battery separately to 100% state of charge using a single-unit charger, let them rest 2–4 hours, and confirm open-circuit voltages match within
0.05V(for 12V-class units) or0.10V(for 24V-class units). - Fabricate identical inter-battery jumpers: Cut all series jumper cables to the shortest practical, uniform length using 75°C-rated (or higher) fine-strand copper marine/UL cable and properly sized, crimped lugs.
- Install series links first: Connect
+of Battery 1 to-of Battery 2, continuing down the string until only one main-terminal (Battery 1) and one main+terminal (final battery) remain open. Torque every terminal bolt to the manufacturer's specification. - Install overcurrent protection and main DC leads: Mount the main fuse or DC breaker within 7 inches (180 mm) of the open main
+terminal, then connect the main+and-leads to the DC busbar or inverter DC input (which supplies your North America 120V/60Hz or UK/AU 230V/50Hz AC loads). - Configure charger and monitoring: Set absorb and float voltages to match the bank (
N_series x unit_spec, strictly<= 60V DC), and install an inter-battery voltage monitor or active equalizer if running multi-unit LiFePO4 series strings.
Commissioning and Sign-Off Criteria
Verify the following before placing the bank into regular service:
- Total bank voltage: Open-circuit voltage at the main terminals equals
N_series x V_unitwithin0.2V. - String balance under load and charge: Individual battery voltages remain within
0.05V–0.10Vof one another under a 10%–20% continuous load and near the end of the absorb phase. - Protection compliance: Main fuse maximum voltage rating exceeds
V_max_charge(no 32V fuses on 24V/48V banks; no 58V fuses on 58.4V LiFePO4 banks), and fuse amp rating does not exceed cable ampacity. - Thermal check: After 15–30 minutes at rated continuous load, no inter-battery lug or jumper exhibits localized heating.
- Low-temperature interlock: Charge controller or BMS cold-temp cutoff is verified if the installation operates at or below
+5°C (41°F).
Common Failure Modes
- BMS MOSFET destruction on cutoff: Wiring 12.8V LiFePO4 batteries in 4S when their internal BMS is only rated for 1S or 2S causes the full 56.8V–58.4V charge bus to appear across a single BMS when it opens, destroying the discharge/charge FETs.
- Progressive string imbalance (walk-out): Minor differences in self-discharge or internal resistance cause one battery to hit high-voltage disconnect early while others are only at 85%–90% SoC, cutting usable bank capacity and causing premature charger shutdowns.
- Underrated fuse arcing: Using a 58V-rated fuse on a 51.2V LiFePO4 bank that absorbs at 58.4V—or using 32V automotive fuses on a 24V/48V bank—can allow a fault arc to sustain instead of clearing cleanly.
- Mixing battery age, capacity, or chemistry: Placing a degraded or smaller-Ah unit in series forces it into over-discharge at the bottom of every cycle and over-voltage at the top.
In this section
- Series Wiring Lead-Acid Batteries Lead-acid 6V GC2 and 12V units wire in series up to 24V flooded or 48V sealed within 60V DC if all units match and no 12V loads tap a midpoint.
- Series Wiring LiFePO4 Batteries Wire LiFePO4 batteries in series only when BMS MOSFETs are rated for full string charge voltage and every pack is charged to 100% before assembly.
Part of Battery Bank Design